41
0: Not memorized
1: Memorized
Through the setting of this parameter whether the value changed by UP-DOWN will be
memorized after stopping can be selected.
When P060 is set to 1, if restart after stopping, the value at stopping will be memorized. If restart
after power off, the values at power off will not be memorized, but the value set by P000 will be
memorized. When P060 is set to 0, if restart after stopping, it will return to the value of P000, the value
changed by up-down will not be memorized.
P062 Timer 1 Time
Set Range: 0.0~10.0 Unit: 0.1S Factory Setting: 0
P063 Timer 2 Time
Set Range: 0~100 Unit: 1S Factory Setting: 0
Timer 1 is a timer of 0.1S~10.0S and Timer 2 is a timer of 1S~100S.
When the timer for multi-input terminal is opened or closed the timer starts to count time. When
the set time is reached the corresponding multi-output contact will act. When the timer is cut off, the
timer for multi-output will reset. During running, if the machine stops due to fault, the timer will count
time normally and not suspend; if the machine stops due to power off, the timer will reset automatically.
P064 Counter
Set Range: 0~9999 Unit: 1 Factory Setting: 0
An external terminal of multi-function can be used as a trigger for the counter. When the counter
reaches set value P064 the corresponding multi-function output contact will act. After the counter is
reset and returns it will start counting again. A proximity switch or optoelectronic switch can be used
for the trigger signals.
P065 Intermediate Counter
Set Range: 0~9999 Unit: 1 Factory Setting: 0
Intermediate Counting Value is one value within counting range. When the counter reaches this
value the corresponding multi-function output contact will act and output one pulse signal. It is valid
when the set value of P065 is smaller than P064.
P066 Skip Frequency 1
P067 Skip Frequency 2
P068 Skip Frequency 3
Set Range: 0.00~600.00Hz Unit: 0.1Hz Factory Setting: 0.0
P069 Skip Frequency Range
Set Range: 0.1~10.00Hz Unit: 0.1Hz Factory Setting: 0.5
F
P068 Frequency
P067 P069
P066 P069
Summary of Contents for DLM1-01D5S2G