dormakaba Mounting instructions
Product description
WN 059876 45532
Observe country-specific regulations when using on
fire barriers, fire protection doors and smoke barriers.
2.2 Foreseeable misuse
Do not control any further alarm devices with the
hold-open system’s fire detector, e.g. transmission
device for fire alarms.
2.3 Prerequisites for the operation of hold-
open systems
The use of hold-open systems is subject to special
provisions due to the official approval regulations.
These provisions relate in particular to acceptance,
ongoing monitoring and maintenance. Follow the
instructions in the information sheet on the use of
hold-open systems.
Additional requirements apply for use as fire/smoke
protection closure in conjunction with external RMZ
and RM. A separate verification of suitability is
required for the respective fire/smoke protection door.
1
If the lower surface of the ceiling on one or both sides
of the door is more than 1 m above the lower edge of
the lintel, an additional ceiling smoke detector must
be mounted on each side of the door and must be
connected with the RMZ. Measure the distance to the
smoke-impermeable ceiling.
1
RMZ
2
TS 97 FL XEA
3
Connection box
4
Manual release button for door-holding devices.
The manual release button must not be covered
by the opened door.
5
Ceiling smoke detector
2.4 Requirements for the electrical
installation by the customer
Carry out the following electrical installations before
mounting the TS 97 FLR-K XEA:
• Connect the 230 V AC power supply to the RMZ. A
circuit breaker B-10A/B-16A must be present in the
supply circuit. The circuit breaker also serves as a
disconnecting device to disconnect the RMZ from
the power supply. The transverse section of the
mains power supply must only be a max. 3 x 1.5 mm²
(NYM).
• Connect the cables for the 24 V DC power supply
from the RMZ to the TS 97 FLR-K XEA door closer.
The supplied cable loop may only be used when the
door closer is mounted on the hinge side.
• Connect the cables to the manual switches and/or
additional RM-N smoke detectors.
3 Product description
The TS 97 FLR-K XEA is a slide rail door closer with
freewheel function and smoke detector panel. The
door closes automatically in the following cases:
• In case of power failure
• In case of fire
• In conjunction with an external manual switch.
7° - 0°
145° - 0°
3
1
2
4
6
5
Fig. 1
TS 97 FLR-K XEA overview
(1)
Slide rail with RMZ (without cladding)
(2)
Lever arm
(3)
TS 97 FL XEA (without cladding)
(4)
Adjusting screw for adjusting the closing force
(5)
Valve for adjusting the closing speed
(6)
Valve for adjusting the end stop
3.1 RMZ
The RMZ supplies the door closer with 24 V DC
voltage. In the event of an alarm or power failure, the
RMZ switches off the power supply (tripping) and
the door closes. The freewheel is reactivated again by
a manual reset and a single opening of the door. An
HT manual release button must be connected to the
RMZ. Ceiling RM smoke detectors can be optionally
connected. 2 LEDs show the current operating status.
The RMZ is configured via the DIP switches.
3.2 DIP switch on the RMZ
The RMZ’s functions are set via the DIP switches.
Changes are only accepted after pressing the reset
button (for settings see Chapter 4.3).