4
TS 97 FLR-K XEA
2019-08
dormakaba Mounting instructions
Mounting
WN 059876 45532
3.2.1 Terminal assignment of the RMZ
3 GND
Connection of external
detectors with
terminating resistor
Total
output
max. 9.8 W
12 + 24 V
14
1 +
Output 24 V DC
door-holding device(s)
4 –
2
External manual release
with terminating resistor (43 kOhm)
10
7 NO
Potential free changeover
contact low voltage (SELV)
24 V AC/DC, 1 A
8 NC
9 C
11
Potential-free terminal
16
Bus
3.2.2 The RMZ’s operating status display
Functions of the LEDs
LED on
LED off
Operation indicator LED 1 (green/red)
Operation: green
Smoke detector alarm: red
Manual release button alarm: red
Service display LED 2 (yellow)
Maintenance due: flashing
Contamination: flashing
Malfunction: permanent
Malfunction: flashing
Incorrect wiring to the ceiling smoke detector/manual
release button
3.3 Optional components
• Concealed cable loop for the door closer’s power
supply via the door leaf, e.g. dormakaba KÜ 480 and
LK12
• Additional smoke detector RM-N
3.4 Technical data
3.4.1 Door closer
Supply voltage operating
voltage
Power consumption
24 V DC +/- 15 %
approx. 3 W
Ambient temperature:
-15°C to +40°C
Rel. humidity:
up to 93%
(non condensing)
Protection class:
IP 54
3.4.2 RMZ
Input:
230 V AC +10 %/–15 %
120 mA/28 VA/50 Hz
Output:
24 V DC/460 mA/11 W
Protection class:
IP 30
Protection category:
II
Smoke switch:
24 V DC/50 mA
Temperature:
-20 °C/+40 °C
Rel. humidity:
max. 93 % without
condensation
4 Mounting
The figures in the picture section of this manual show
the
mounting for DIN-L. For DIN-R, the instructions must
be mirror-inverted.
4.1 Mounting variants
The TS 97 FLR-K XEA can be mounted DIN-L or DIN-R
on the hinge side or opposite side to the hinge.
4.2 Mounting the door closer and slide rail
2 - 9
Carry out the mounting according to the enclosed
illustrated instructions.
4.3 Make electrical connections to the
RMZ
10
1.
Connect the 230 V connection cable. To maintain
the protection category II (protective
insulation), lay the 230-V supply with double
insulation up to the connection terminal.
2.
Ensure the strain relief of the mains power supply
leading to the RMZ. The protective earth must
not be used electronically. Connect the provided
protective earth to the support terminal (PE).
3.
Close the touch protection.
4.
Screw the touch protection on.
5.
Connect the cable from the door closer.
7.
Connect the HT manual release button and the
optional ceiling smoke detectors to the RMZ
according to the enclosed wiring diagrams.
4.4 Set DIP switches
11
1.
Set the DIP switches to the appropriate position.
1 OFF = automatic reset
(delivery state)
ON = manual reset
(A manual reset is required
for freewheel door closers)
For this type of function, stick the
enclosed label on the housing
2 OFF = 1-radial operation (line)
ON = 2-radial operation (star)
3 OFF = without optional ceiling smoke
detector
ON = with optional ceiling smoke detector