5
G-Ubivis XEA
2020-11
WN 058974 45532
dormakaba Operating instructions
Product description
3.2 Operating elements
Fig. 3
3.2.1
3.2.2
Operating elements
3.2.1 Switches
Fig. 4
Switch
A
Installation position
Switch
B
Reset switch
Switches
3.2.1.1 LED selector switch (Switch A)
Switch
A
must always point downwards after
mounting.
DIN-L on the hinge side or
DIN-R on the opposite side to the hinge
(delivery state)
DIN-R on the hinge side or
DIN-L on the opposite side to the hinge
3.2.1.2 Reset type selector switch
(Switch B)
Automatic reset
(delivery state)
If smoke or test gas is no longer present in
the smoke chamber after an alarm has been
triggered, the smoke detector panel will
automatically re-arm.
The operation indicator flashes green 1 x every
28 s.
Manual reset
A manual restart is required for use in
emergency exit systems (according to IfBt
Communication 5/98, pt. 3.1.4) in order to
manually re-arm the smoke detector panel
after an alarm has been triggered.
If there is no more smoke or test gas in the
smoke chamber, press the reset button. The
operation indicator flashes green 1 x every
28 s.
TIPS AND RECOMMENDATIONS
After changing switch B, the battery must
be disconnected and reconnected after 30 s
to take over the set function.
3.2.2 Reset button and control LEDs
3.2.2.1 Reset button
The reset buttons are located on the top and bottom
of the beam.
The reset buttons both have the same functions.
•
Arming with manual reset
To arm the smoke detector after the alarm has
been triggered, press the reset button.
•
Error acknowledgment
Press the reset button to acknowledge an error
message.
•
Release and reactivate the door-holding device
To release the door-holding device, press the reset
button for more than 5 s.
The LED flashes green 2 x every 7 s.
The door leaf may be held open 30 s after triggering
the hold-open system.
To reactivate the door holder, press the reset button
for 1 s.
•
In automatic mode
The magnet system attracts, but a small air gap
remains between the anchor plate and the magnet
system. In this state, the coil can be ejected. This is
indicated by the LED flashing yellow 5 x. The system
is still ready for operation.
If there is no feedback from the EMF’s anchor
position, this is indicated by the LED flashing yellow
6 x. The system is still ready for operation.
The EMF can be reactivated by pressing the reset
button. The errors are acknowledged.
Fig. 5
Reset button