6.2 Setting the PARTIAL OPEN width
The PARTIAL OPEN width can be adjusted with the
PDA. The PDA can also be used to disable the setting
via program switch, so that settings can only be made
with the PDA.
reduced opening width = partial opening width
6.3 Emergency Breakout
6.4 Start-up following a power failure
The opening width of the door can be adjusted
individually. Starting from the full opening width, a
may be set (e.g. in winter to reduce drafts.)
1.
Close the door.
2.
Set program switch to PERMANENT OPEN
The door opens at low (creep) speed.
3.
As soon as the door reaches the desired partial
opening width, set the program switch to
PARTIAL OPEN
and the main switch to close
.
The door stops
The control unit stores the desired position.
The door performs a closing cycle.
The program switch is set to AUTOMATIC, PARTIAL
OPEN or EXIT ONLY.
After a power failure, the control unit performs a self-
check of approx. 5 sec. for safety reasons.
The door then closes at low (creep) speed and
resumes the preset program function.
·
·
·
·
·
The door stops immediately
Breakout any panel:
·
The leaves may be moved manually.
ESA II Controller
and Wiring Manual