Flow Chart for NATIONAL BUILDING CODE

N

Y

LEDR Blinking Fast

Local Alarm On

Remote Alarm On

Buzzer Pulsing

Nuisance Delay

Time Out ?

Dip Switch Setting

Dip1-

On: 15 Seconds

Dip2/Dip3- On/On: 0 Second.
Dip4-

On.

Power On

Locked ?

Door Pushing ?

LEDR Off

LEDG Blinks every 5S.

Local Alarm Off

Remote Alarm On

Y

N

Y

LEDR Blinking Slowly

Local Alarm On

Remote Alarm Off

Buzzer On

Release Delay

Time Out ?

Y

LEDR/G Blinking Alt.

Local Alarm Off

Remote Alarm Off

Lock Release

N

Still Locked ?

N

LEDR On

Local Alarm Off

Remote Alarm Off

Reset to Relock

?

Y

Relock

N

Y

Dip1-

Release Delay 15

seconds only.

Dip2/Dip3- Nuisance delay not allowed

Relock occurs only when Reset 
Switch Input from open to close.

NOTE:

NOTE:

N

(for CANADA)

Buzzer Off

Buzzer Off

 

 

 

Flow Chart for BURGLAR ALARM

N

Y

LEDR Blinking Fast

Local Alarm On

Remote Alarm On

Buzzer Pulsing

Nuisance Delay

Time Out ?

Power On

Locked ?

Door Pushing ?

LEDR Off

LEDG Blinks every 5S.

Local Alarm Off

Remote Alarm On

Y

N

Y

LEDR Blinking Slowly

Local Alarm On

Remote Alarm Off

Buzzer On

Alarm Period

Time Out ?

Y

LEDR/G Blinking Alt.

Local Alarm Off

Remote Alarm On

N

Still Locked ?

N

LEDR On

Local Alarm Off

Remote Alarm Off

Reset ? 

Y

System Reset

N

Y

Dip1/Dip2-

Remote Alarm Period can
be infinity.

Dip3/Dip4-

Nuisance Delay permitted
up to 6 seconds.

System reset occurs only when 
Reset Switch Input is close.

NOTE:

NOTE:

N

Dip Switch Setting

Dip1/Dip2- On/On: 0 Second.

On/Off: 2 Seconds.
Off/On: 4 Seconds.
Off/Off: 6 Seconds

Dip3/Dip4- 

On/Off: 15 Seconds.

Off/On: 30 Seconds.
Off/Off: Infinity

On/On: 0 Second.

Buzzer Off

Buzzer Off

Remote

 

Summary of Contents for EM 3000-EW AH

Page 1: ...on the door is fail safe power to lock and locked the local buzzer is off the Local Alarm Relay SPDT 1C is deenergized and the Remote Alarm Relay DPDT 2C is energized The system will start the exit se...

Page 2: ...fast Sound pulsingly Voice IV ON OFF Exit Switch to Open Red on OFF Voice III OFF OFF Local Normal Condition Nuisance Delay Release Delay Door Release Reset to Power on Door Locked Period Normal Condi...

Page 3: ...ry setting Not BOCA Dip switch 4 ON 1 5 S e c R e le a s e D e la y D ip S w itc h 1 3 0 S e c 1 O N 0 S e c N u is a n c e D e la y D ip S w itc h 2 3 2 3 4 1 S e c 2 S e c 3 S e c N o n B O C A B O...

Page 4: ...t Max 8 second periods for Voice III Voice IV Illegal intruder The security alarm is activated Security personnel has been alerted and would arrive momentarily Max 10 second periods for Voice IV Voice...

Page 5: ...em will start the delay sequences only when these two inputs are shorted Voice Control Output S2 S1 G 5V Four terminal block outputs to control Voice Module Request to Exit Input EXIT Normally Open Th...

Page 6: ...message by speaking to the microphone on the voice module or by connecting ANA to computer earphone output and playback the voice message thru such as Windows Media Player The messages can also be rec...

Page 7: ...nly when Reset Switch Input from open to close NOTE NOTE N Buzzer Off Buzzer Off Flow Chart for NFPA 101 N Y LEDR Blinking Fast Local Alarm On Remote Alarm On Buzzer Pulsing Nuisance Delay Time Out Di...

Page 8: ...Y LEDR Blinking Fast Local Alarm On Remote Alarm On Buzzer Pulsing Nuisance Delay Time Out Dip Switch Setting Dip1 On 15 Sec Off 30 Sec Dip2 Dip3 On Off 1 Second Dip4 Off Power On Locked Door Pushing...

Page 9: ...to close NOTE NOTE N for CANADA Buzzer Off Buzzer Off Flow Chart for BURGLAR ALARM N Y LEDR Blinking Fast Local Alarm On Remote Alarm On Buzzer Pulsing Nuisance Delay Time Out Power On Locked Door Pus...

Reviews: