I. FLOW CHARTS
Flow Chart for STANDRD BUILDING CODE
N
Y
LEDR Blinking Fast
Local Alarm On
Remote Alarm On
Buzzer Pulsing
Nuisance Delay
Time Out ?
Dip Switch Setting
Dip1-
On: 15 Sec. Off: 30 Sec.
Dip2/Dip3- On/On: 0 Second.
Dip4-
On.
Power On
Locked ?
Door Pushing ?
LEDR Off
LEDG Blinks every 5S.
Local Alarm Off
Remote Alarm On
Y
N
Y
LEDR Blinking Slowly
Local Alarm On
Remote Alarm Off
Buzzer On
Release Delay
Time Out ?
Y
LEDR/G Blinking Alt.
Local Alarm Off
Remote Alarm Off
Lock Release
N
Still Locked ?
N
LEDR On
Local Alarm Off
Remote Alarm Off
Reset to Relock
?
Y
Relock
N
Y
Dip1-
Release Delay can be
15 or 30 seconds.
Dip2/Dip3- Nuisance delay not allowed.
Relock occurs only when Reset
Switch Input from open to close.
NOTE:
NOTE:
N
Buzzer Off
Buzzer Off
Flow Chart for NFPA 101
N
Y
LEDR Blinking Fast
Local Alarm On
Remote Alarm On
Buzzer Pulsing
Nuisance Delay
Time Out ?
Dip Switch Setting
Dip1-
On: 15 Sec. Off: 30 Sec.
Dip2/Dip3- On/On: 0 Second.
On/Off: 1 Second.
Off/On: 2 Seconds
Off/Off: 3 Seconds.
Dip4-
On.
Power On
Locked ?
Door Pushing ?
LEDR Off
LEDG Blinks every 5S.
Local Alarm Off
Remote Alarm On
Y
N
Y
LEDR Blinking Slowly
Local Alarm On
Remote Alarm Off
Buzzer On
Release Delay
Time Out ?
Y
LEDR/G Blinking Alt.
Local Alarm Off
Remote Alarm Off
Lock Release
N
Still Locked ?
N
LEDR On
Local Alarm Off
Remote Alarm Off
Reset to Relock
?
Y
Relock
N
Y
Dip1-
Release Delay can be
15 or 30 seconds.
Dip2/Dip3- Nuisance delay permitted
up to 3 seconds.
Relock occurs only when Reset
Switch Input from open to close.
NOTE:
NOTE:
N
Buzzer Off
Buzzer Off