WIRE GAUGE

 SD-2 DETECTOR TO MAIN SOLENOID CONNECTION

MAIN

HOLD OPEN

ELECTROMAGNET

Strip approximately 1/4" of plastic insulation from the end of the two solenoid wires supplied.  Connect

one end each of the electromagnet wires to terminals 6 & 9 of the SD-2 detector as shown.  

 SD-2

15

7

5

14

13

12

11

10

9

1

6

4

3

2

8

No. OF

ELECTRO-

MAGNET

(E4)

No. OF

ELECTRO-

MAGNET

(E3)

No. OF

ELECTRO-

MAGNET

(E2)

No. OF

ELECTRO-

MAGNET

(E1)

POWER

SUPPLY

TO NEXT HOLD

OPEN ELECTROMAGNET

WIRE LENGTH

TO E4

(D4)

WIRE LENGTH

TO E3

(D3)

WIRE LENGTH

TO E2

(D2)

WIRE LENGTH

TO E1

(D1)

WIRE GAUGE: The maximum wire gauge for wiring the SD-2 detector module is #18 AWG. The method for 

determining wire gauge is given below. NOTE: A minimum of 20.4 VDC must be supplied to each solenoid 

in the run.

S1, S2, S3 etc. are the number of solenoids at each subsequent station. D1 is the distance from the

power supply to the first solenoid station. D2, D3, D4 etc. are the distances from the previous solenoid 

station to the next solenoid station in the run. To determine the correct wire gauge multiply E1 times D1.

Add that quantity to E2 times D2. Repeat the same procedure for each electromagnet to test the last unit in

the run. Compare the quantity calculated to the chart below. The calculated value must be less than or 

equal to the value corresponding to the appropriate wire gauge.

     10 GAUGE-11,788   12 GAUGE-7,407   14 GAUGE-4,669   16 GAUGE-2,997   18 GAUGE-1,843
The procedure described above can be expressed in the following equation: (E1xD1) + (E2xD2) + (E3xD3)

....(EnxDn) The above values correspond to the wire gauge to be used. If the calculated value is 1,843

#18 AWG wire can be run and connected directly to the detector module. If the calculated value exceeds

1,843 larger wiring will be required. Since the detector will only accept #18 AWG wire, a wiring splice will

be necessary as illustrated below.

#16-#12

#16-#12

#16-#12

#16-#12

#18

#18

NOTE: FOR ULC INSTALLATIONS, 18 GAUGE

WIRE IS REQUIRED TO DETECTOR

INS NO.

PAGE

Rev.

08280990

7 of 14

08/13

Summary of Contents for 8900 EMR

Page 1: ...to which it is interconnected Single installations or groups of installations can be connected to the alarm initiation circuit of a compatible UL ULC listed fire alarm control unit in 4 wire or 6 wire configurations Additional functions are provided to separately power the hold open electromagnets directly from the alarm control panel as well as connections for a remote alarm indicator lamp 8900 E...

Page 2: ...ector Slide detector slot under standoff T DE RH T DE LH NOTE NO TOP PLUG ON PT MOUNTS Remove 1 wire access plug according to the installation type 6 NOTE If construction is still being completed near detector installation DO NOT install detector at this time or protect the detector from construction dust contaminants SURFACE CONDUIT C HINGE NOTE Three access wire holes on optional surface wired u...

Page 3: ...OOR LEFT HAND DOOR RIGHT HAND DOOR 8 8900T RIGHT HAND DOOR LEFT HAND DOOR Attach main arm to door closer 4 QTY METAL FRAMES WOOD FRAMES 4 QTY Place arm on top pinion as shown 45 angle Secure with pinion screw 6mm HEX KEY 6mm HEX KEY QTY 1 INS NO PAGE Rev 08280990 3 of 14 08 13 ...

Page 4: ...EEP LATCH POSITIONING VALVE INTENSITY INCREASE Adjust spring tension if required using a 1 4 wrench NOTE 8956 supplied with size 6 setting CRITICAL 8916 supplied with size 3 spring setting SPRING TENSION ADJUSTER SPRING DOOR WIDTH INTERIOR 8956 4 0 CLOSER 8916 TYPE 3 6 3 6 3 0 2 6 6 6 Adjust according to chart 0 16 8 OF SPRING FULL TURNS ADJUSTER 0 6 6 4 5 SIZE MAX 125 150 WEIGHT DOOR 200 200 ULC ...

Page 5: ...TORY IF REMOTE DETECTORS ARE USED IN THIS APPLICATION TERMINAL 3 14 1 2 6 9 8 7 15 4 5 13 10 N O 8 N C 9 COM 10 ELECTRICAL SPECIFICATIONS Voltage input Maximum input current Maximum output to Remote Contact ratings 24 VDC 10 15 24 VAC 10 15 24 VDC 161 mA 1 solenoid 310 mA 2 solenoids 24 VAC 161 mA 1 solenoid 310 mA 2 solenoids 300 mA Alarm and or accessory contacts 1 25 A at 24 VDC or 3 A at 120 V...

Page 6: ... terminal 3 of the first unit to terminal 3 of the second unit and connect terminal 14 of the first unit to terminal 14 of the second unit Continue this process for any subsequent units to be powered from the same power supply 24 VAC DC POWER SUPPLY 1 2 3 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 ...

Page 7: ...he first solenoid station D2 D3 D4 etc are the distances from the previous solenoid station to the next solenoid station in the run To determine the correct wire gauge multiply E1 times D1 Add that quantity to E2 times D2 Repeat the same procedure for each electromagnet to test the last unit in the run Compare the quantity calculated to the chart below The calculated value must be less than or equ...

Page 8: ... 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 1 Up to 5 SD 2 detectors with or without connection to an auxiliary unit or remote area detector may be interconnected This limitation applies only to interconnected units and assumes a power supply large enough to handle this load if the power supply is common to all units interconnected Separate power supplies may be used f...

Page 9: ...wiring section Perform wiring connections as illustrated below NOTE The SD 2 is wired as the E O L end of line device for the remote detector Therefore it must act as the last item in the loop CONTROL UNIT 24VAC DC POWER SUPPLY UL ULC LISTED AUDIBLE SIGNAL APPLIANCE OR REMOTE DETECTOR CAUTION SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 ...

Page 10: ...TIATING CIRCUIT CONNECTIONS FOR SIX 6 WIRE INSTALLATION RETURN LOOP ALARM RELAY EOL USED IN 4 WIRE APPLICATIONS ONLY REMOTE DETECTOR INITIATING CIRCUIT UL ULC LISTED 1 Make all connections as outlined previously for all units required by the job specifications 2 Make all signal initiating connections as illustrated in the appropriate figure below Note wiring differences for units with remote detec...

Page 11: ...t 2 The last unit in the run must be connected in the same manner as unit 3 5 More than three 3 SD 2 detectors are connected by inserting additional units with connections to detector 3 in the same manner as it is shown connected to detector 2 Detector 2 would 4 Connections for two 2 SD 2 detectors would consist of detector 1 in figure below connected unit of the run as illustrated EOL USED IN 4 W...

Page 12: ...detector connect a volt meter to the two test terminals Voltage output terminals are provided to measure the sensitivity of the smoke detector The normal range is between 1 27 3 38 Vdc SENSITIVITY TEST TERMINALS to ten 10 seconds to indicate the unit is connections The LED will blink every seven 7 After installation is completed check all LED operating properly The LED should remain continually re...

Page 13: ...cleaned at least once a year Detectors in dusty environ ments must be tested and cleaned more often Detectors must also be tested and cleaned imme diately after a fire Failure to maintain detectors may result in needless false alarms 21 20 3 An auxiliary door stop by others must be installed to limit the maximum degree of door swing Failure to do so may result in damage to the unit 19 1 SNAP VALVE...

Page 14: ...as identified by a date code located on the bottom of the can of 1990 or later This date code can be read as first numeral last digit of year so that a B0xxx 1990 and B9xxx 1989 3 in accordance with the instructions stated above If the preceding requirements are not met the use of Smoke Detector Tester is unacceptable and DORMA cannot guarantee the proper operation of detectors that have been subj...

Reviews: