With door in closed position, rotate spindle 45° with wrench. Place arm on spindle. 

Open door and secure with pinion screw.

C HINGE

HINGE C

Attach arm to slide shoe. Use 3/16 inch hex head wrench.

9

ROTATE

PINION

45°

6mm HEX KEY

ROTATE

PINION

45°

6mm HEX KEY

10

BACKCHECK OR DELAYED ACTION

NOTE: DELAYED ACTION IS AN OPTIONAL FEATURE.

DECREASE

Adjust sweep, latch and backcheck valves.

CAUTION: DO NOT REMOVE VALVES.

LATCH

RANGE

BACKCHECK

BACKCHECK RANGE

RANGE

ACTION

SWEEP (SPEED)

INCREASE

DELAYED ACTION

RANGE

LATCH

(SPEED)

(TIME)

11

DELAYED

SWEEP

DECREASE

SWEEP & LATCH

POSITIONING VALVE

(INTENSITY)

INCREASE

Adjust spring tension, if required, using a 1/4" wrench.

NOTE:

8956 supplied with size 6 setting.

CRITICAL

8916 supplied with size 3 spring setting. 

-

+

SPRING TENSION

ADJUSTER

SPRING

DOOR WIDTH

INTERIOR

8956

4'-0"

CLOSER

8916

TYPE

3'-6"

3'-6"

3'-0"

2'-6"

+6

6+

Adjust according to chart.

0

+16

+8

OF SPRING

FULL TURNS

ADJUSTER

0

6

6

4

5

SIZE

MAX.

125
150

WEIGHT

DOOR

200

200

ULC LABELED UNITS ONLY

ADJUST SPRING TENSION ACCORDING TO THE FOLLOWING CHART.

8916

8956

CLOSER

TYPE

ADJUSTING NUT

5

+8

6

6

0

+16

SPRING

SIZE

4

OF SPRING

FULL TURNS

0

250

6+

+6

NOTE: DO NOT ADJUST SPRING LOWER THAN SIZE 3

6mm HEX KEY

6mm HEX KEY

Place arm on top pinion as shown @ 45° angle. Secure with pinion screw. 

Attach main arm to door closer.

 8905DE

INS NO.

PAGE

Rev.

08280990

4 of 14

08/13

Summary of Contents for 8900 EMR

Page 1: ...to which it is interconnected Single installations or groups of installations can be connected to the alarm initiation circuit of a compatible UL ULC listed fire alarm control unit in 4 wire or 6 wire configurations Additional functions are provided to separately power the hold open electromagnets directly from the alarm control panel as well as connections for a remote alarm indicator lamp 8900 E...

Page 2: ...ector Slide detector slot under standoff T DE RH T DE LH NOTE NO TOP PLUG ON PT MOUNTS Remove 1 wire access plug according to the installation type 6 NOTE If construction is still being completed near detector installation DO NOT install detector at this time or protect the detector from construction dust contaminants SURFACE CONDUIT C HINGE NOTE Three access wire holes on optional surface wired u...

Page 3: ...OOR LEFT HAND DOOR RIGHT HAND DOOR 8 8900T RIGHT HAND DOOR LEFT HAND DOOR Attach main arm to door closer 4 QTY METAL FRAMES WOOD FRAMES 4 QTY Place arm on top pinion as shown 45 angle Secure with pinion screw 6mm HEX KEY 6mm HEX KEY QTY 1 INS NO PAGE Rev 08280990 3 of 14 08 13 ...

Page 4: ...EEP LATCH POSITIONING VALVE INTENSITY INCREASE Adjust spring tension if required using a 1 4 wrench NOTE 8956 supplied with size 6 setting CRITICAL 8916 supplied with size 3 spring setting SPRING TENSION ADJUSTER SPRING DOOR WIDTH INTERIOR 8956 4 0 CLOSER 8916 TYPE 3 6 3 6 3 0 2 6 6 6 Adjust according to chart 0 16 8 OF SPRING FULL TURNS ADJUSTER 0 6 6 4 5 SIZE MAX 125 150 WEIGHT DOOR 200 200 ULC ...

Page 5: ...TORY IF REMOTE DETECTORS ARE USED IN THIS APPLICATION TERMINAL 3 14 1 2 6 9 8 7 15 4 5 13 10 N O 8 N C 9 COM 10 ELECTRICAL SPECIFICATIONS Voltage input Maximum input current Maximum output to Remote Contact ratings 24 VDC 10 15 24 VAC 10 15 24 VDC 161 mA 1 solenoid 310 mA 2 solenoids 24 VAC 161 mA 1 solenoid 310 mA 2 solenoids 300 mA Alarm and or accessory contacts 1 25 A at 24 VDC or 3 A at 120 V...

Page 6: ... terminal 3 of the first unit to terminal 3 of the second unit and connect terminal 14 of the first unit to terminal 14 of the second unit Continue this process for any subsequent units to be powered from the same power supply 24 VAC DC POWER SUPPLY 1 2 3 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 ...

Page 7: ...he first solenoid station D2 D3 D4 etc are the distances from the previous solenoid station to the next solenoid station in the run To determine the correct wire gauge multiply E1 times D1 Add that quantity to E2 times D2 Repeat the same procedure for each electromagnet to test the last unit in the run Compare the quantity calculated to the chart below The calculated value must be less than or equ...

Page 8: ... 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 1 Up to 5 SD 2 detectors with or without connection to an auxiliary unit or remote area detector may be interconnected This limitation applies only to interconnected units and assumes a power supply large enough to handle this load if the power supply is common to all units interconnected Separate power supplies may be used f...

Page 9: ...wiring section Perform wiring connections as illustrated below NOTE The SD 2 is wired as the E O L end of line device for the remote detector Therefore it must act as the last item in the loop CONTROL UNIT 24VAC DC POWER SUPPLY UL ULC LISTED AUDIBLE SIGNAL APPLIANCE OR REMOTE DETECTOR CAUTION SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 10 9 1 6 4 3 2 8 SD 2 15 7 5 14 13 12 11 ...

Page 10: ...TIATING CIRCUIT CONNECTIONS FOR SIX 6 WIRE INSTALLATION RETURN LOOP ALARM RELAY EOL USED IN 4 WIRE APPLICATIONS ONLY REMOTE DETECTOR INITIATING CIRCUIT UL ULC LISTED 1 Make all connections as outlined previously for all units required by the job specifications 2 Make all signal initiating connections as illustrated in the appropriate figure below Note wiring differences for units with remote detec...

Page 11: ...t 2 The last unit in the run must be connected in the same manner as unit 3 5 More than three 3 SD 2 detectors are connected by inserting additional units with connections to detector 3 in the same manner as it is shown connected to detector 2 Detector 2 would 4 Connections for two 2 SD 2 detectors would consist of detector 1 in figure below connected unit of the run as illustrated EOL USED IN 4 W...

Page 12: ...detector connect a volt meter to the two test terminals Voltage output terminals are provided to measure the sensitivity of the smoke detector The normal range is between 1 27 3 38 Vdc SENSITIVITY TEST TERMINALS to ten 10 seconds to indicate the unit is connections The LED will blink every seven 7 After installation is completed check all LED operating properly The LED should remain continually re...

Page 13: ...cleaned at least once a year Detectors in dusty environ ments must be tested and cleaned more often Detectors must also be tested and cleaned imme diately after a fire Failure to maintain detectors may result in needless false alarms 21 20 3 An auxiliary door stop by others must be installed to limit the maximum degree of door swing Failure to do so may result in damage to the unit 19 1 SNAP VALVE...

Page 14: ...as identified by a date code located on the bottom of the can of 1990 or later This date code can be read as first numeral last digit of year so that a B0xxx 1990 and B9xxx 1989 3 in accordance with the instructions stated above If the preceding requirements are not met the use of Smoke Detector Tester is unacceptable and DORMA cannot guarantee the proper operation of detectors that have been subj...

Reviews: