VPRS-430 OPERATION MANUAL
Issue : 2009.03
ED : 1
VPRS-430 OPERATION MANUAL 8 /30
●
When cables are connected, battery should be separated from the
rectifier system except one point of the conductor at each cell.
●
Start operation after the connections of battery wire, load, and
grounding wire are taken apart from NFB and fuses.
●
Connect the battery wire, load and grounding wire while the load side
has been unloaded.
●
External transmission signal should be used at 60V or lower of input
voltage and 0.5A or lower of circuit current.
●
Before you take apart or insert the RS232C and RS485 ports of the
control module, turn off the control module switch.
●
When you take apart or insert the rectifier unit from/to the rectifier
system, turn off the rectifier unit switch.
●
Rectifier unit should be inserted and taken apart in line with the guide
rail of the rectifier system.
●
Tightly join the unit fixing screws, and then, turn on the input switch
of the rectifier unit.
●
As AC input may be fed to turned on system while power is failed,
special care should be paid to check and maintain the AC input.