background image

Dalamatic Cased, DLMC 1/2/15 through 4/8/15

 18

Instruct all personnel on safe use and maintenance 

procedures.

Use proper equipment and adopt 

all safety precautions needed for 

servicing equipment.  
Use appropriate access equipment. The 

standard collector is not equipped with access 

platforms unless noted on specification 

drawings.
Electrical service or maintenance work must 

be performed by a qualified electrician and 

comply with all applicable national and local 

codes.
Turn power off and lock out electrical 

power sources before performing service or 

maintenance work.
Do not install in classified hazardous 

atmospheres without an enclosure rated for 

the application.
Turn compressed air supply OFF, bleed and 

lock out lines before performing service or 

maintenance work.

Do not set compressed-air 

pressure above 100-psig as 

component damage can occur.
All compressed air components must be sized 

to meet the system requirements of 90-100 psig 

supply pressure.
The compressed-air supply must be oil 

and moisture free. Contamination in the 

compressed air used to clean filters will result 

in poor cleaning, cleaning valve failure, or poor 

collector performance.
Purge compressed air lines to remove 

debris before connecting to the collector’s 

compressed air manifold.

Operational Checklist

1.  Monitor the physical condition of the collector and 

repair or replace any damaged components. 

 

Routine inspections will minimize downtime and 

maintain optimum system performance. This 

is particularly important on continuous-duty 

applications. 

Maintenance Information

2.  Periodically check the compressed air components 

and replace compressed air filters.

 

Drain moisture following the manufacturer’s 

instructions. With the compressed air supply ON, 

check the cleaning valves, solenoid valves, and 

tubing for leaks. Replace as necessary. 

3.  Monitor pressure drop across filters.
 

Abnormal changes in pressure drop may indicate a 

change in operating conditions and possibly a fault 

to be corrected.  For example, prolonged lack of 

compressed air will cause an excess build-up of dust 

on the filters resulting in increased pressure drop. 

Cleaning off-line with no airflow usually restores the 

filters to normal pressure drop.

4.  Monitor exhaust.
5.  Monitor dust disposal.

Filter Removal and Installation

Use proper safety and protective 

equipment when removing 

contaminants and filters.
Dirty filters may be heavier than they appear.
Use care when removing filters to avoid 

personal injury and/or property damage.
Turn power off and lock out electrical 

power sources before performing service or 

maintenance work.

Do not operate with missing or 

damaged filters.

Summary of Contents for Dalamatic Cased DLMC 1/2/15

Page 1: ...ete Donaldson Company reserves the right to change design and specifications without prior notice Illustrations are for reference only as actual product may vary Dalamatic Cased DLMC 1 2 15 1 3 15 1 4 15 1 5 15 1 7 15 2 2 15 2 3 15 2 4 15 2 5 15 2 6 15 2 8 15 3 3 15 3 5 15 3 6 15 3 7 15 3 8 15 4 5 15 and 4 8 15 Units Built After July 2006 Installation and Operation Manual Installation Operation an...

Page 2: ...son assumes no responsibility or liability for the suitability of any fire and or explosion mitigation strategy or any items incorporated into a collector as part of an owner operators hazard mitigation strategy Improper operation of a dust control system may contribute to conditions in the work area or facility that could result in severe personal injury and product or property damage Check that ...

Page 3: ...ation Codes and Procedures 4 Installation 4 Foundations or Support Framing 5 Collector Location 5 Site Selection 5 Rigging Instructions 5 Hoisting Information 5 Standard Equipment 7 Shipping Information 8 Collector Installation 9 Provisional Anchor Bolt Recommendations 9 Manifold Installation 11 Compressed Air Installation 11 Electrical Wiring 12 Solid State Timer Installation 13 Helix Tube Filter...

Page 4: ... DLMC provides continuous filtration and high collection efficiency while maintaining a relatively constant system resistance Standard sizes range from 323 to 5164 sq ft 30 to 480 sq meters of filter area A solid state timer provides the interface for filter cleaning control Options include a pyramid hopper for use with a 55 gallon drum or rotary airlock a trough hopper for use with a screw convey...

Page 5: ...ral Acceleration S1 0 6 g Installed Collector Base Elevation Grade Risk Category II Compressed air supply psig 90 100 Housing rating inches water gauge 20 Control power 120 Volt 50 60 Hz If collector was supplied with a Record Drawing the specifications on the drawing will supersede the standard specifications above Pyramid Hopper Typical Side View Pyramid Hopper UMA Hopper with 4 cu ft Bins Troug...

Page 6: ...et tube positioned over each filter distributes a pulse of compressed air through the filter As the compressed air enters the filter airflow is temporarily reversed dislodging the dust cake formed on the outside of the filter The dust cake falls into the hopper and exits through the hopper outlet outlet header sealing frame and ring accumulated dust cake filter clean air plenum dirty air plenum ai...

Page 7: ...ompressed air manifold Installation Use proper equipment and adopt all safety precautions needed for servicing equipment Electrical service or maintenance work must be performed by a qualified electrician and comply with all applicable national and local codes Turn power off and lock out electrical power sources before performing service or maintenance work Do not install in classified hazardous a...

Page 8: ...s and may require engineering Foundation and support framing must be capable of supporting dead live wind seismic and other applicable loads Consult a qualified engineer for final selection of foundation or support framing Note Collectors with explosion vents are not available in portable configurations Site Selection This collector can be located on a foundation or structural framing Provide clea...

Page 9: ...ctor s casing Check the Specification Control drawing for weight and dimensions of the collector and components to ensure adequate crane capacity Allow only qualified crane or forklift operators to lift the equipment Refer to applicable OSHA regulations and local codes when using cranes forklifts and other lifting equipment Lift collector and accessories separately and assemble after collector is ...

Page 10: ...onal not shown tubesheet seal frame filter bag and cage insert dirty air inlet clean air outlet solenoid enclosure top inspection panel blow pipe jet tube lifting lug Typical Installation Collector shown with rear inlet and front outlet Other options include side inlets and outlets and a top outlet to be used with a mounted TBI fan Typical systems include one of several hopper arrangements designe...

Page 11: ...25 lb Bank Add 150 lb for 72 in legs Includes electrical valves tubing and manifold Example Model DLM 6 4 15 6 banks wide x 4 tiers high 1 Find the number of banks in the first column and follow the row to the 4 Tier column 2 This collectors ships with two upper sections L 3 Hopper and legs ship separate Banks 2 Tier 3 Tier 4 Tier 5 Tier 6 Tier 7 Tier 8 Tier 1 1 A 1 E 1 J 1 E 1 N 1 A 1 S 1 E 1 S 1...

Page 12: ...on over the hopper and lower slowly 12 Use drift pins to align holes Install bolts loosely until all bolts are in place If the collector has vertical site joints apply sealant as shown before bolting together 13 Install the bolts at the clean air plenum base to hopper flange first 14 Access the tubesheet seal plate joining bolts through the front access doors Take special care with sealant at the ...

Page 13: ...ide of the bolt pattern Apply generously to prevent leakage Sealant Detail remove and discard after section is installed 2 pieces Sealant Detail top inspection panel removed bolt on external flange stiffener Note the opening is only for the inspection panel and should not be used as an inlet Sealant Detail ...

Page 14: ...lve bleed type regulator with gauge filter and automatic condensate valve in the compressed air supply line 3 Set compressed air supply pressure to a level suitable for the filters 90 psig The pulse cleaning controls are factory set to clean one or more filters every 10 seconds during a cleaning cycle Compressed Air Installation Turn compressed air supply OFF bleed and lock out lines before perfor...

Page 15: ...Do not install in classified hazardous atmospheres without an enclosure rated for the application All electrical wiring and connections including electrical grounding should be made in accordance with the National Electric Code NFPA No 70 latest edition Check local ordinances for additional requirements that apply The appropriate wiring schematic and electrical rating must be used See collector s ...

Page 16: ...e end of the OFF time the timer energizes the corresponding solenoid valve to provide the ON time cleaning pulse for one diaphragm valve and then steps to the next until all filters have been cleaned To pulse when the fan is OFF install a toggle switch as shown on the Solid State Timer Wiring Diagram When the toggle switch is ON the timer receives power and energizes the solenoid valves pulse clea...

Page 17: ...ed Use wiring diagram provided with unit Wiring by others Wiring by factory L1 L2 2 1 Solid State Timer Typical Wiring Diagram Input 105 135V 50 60Hz 1Ph Output Solenoids The load is carried and turned ON and OFF by the 200 watt maximum load per output solid state switch Pulse ON Time Factory set at 100 milliseconds or 1 10 second Do not adjust pulse ON time unless the proper test equipment is ava...

Page 18: ... aside 4 Starting on one side of the collector place a helix tube filter in a seal frame slot as shown Helix Tube Filter Installation Be careful to not scrape the filters when slipping them through the seal frame 5 Install a second helix tube filter adjacent to the prior helix tube filter 6 Install a venturi on both adjacent helix tube filters and place a clamp over one end of both venturis Instal...

Page 19: ...amp hex nut Venturi Installation 7 Repeat to install all helix tubes 8 Replace jet tubes with the open end pressed firmly into its locator and the orifices directed toward the helix tube filter See Helix Tube Filter Detail 8 Reinstall jet tube retainer bars on collectors 4 tiers tall or taller ...

Page 20: ...st to avoid personal injury 12 Turn the Solid State Timer ON and check that valves operate in the proper sequence by monitoring the LEDs on the front panel 13 Verify operation of interlocks and audible warning system if equipped Instruct all personnel on safe use and maintenance procedures Electrical work during installation service or maintenance must be performed by a qualified electrician and c...

Page 21: ...necting to the collector s compressed air manifold Operational Checklist 1 Monitor the physical condition of the collector and repair or replace any damaged components Routine inspections will minimize downtime and maintain optimum system performance This is particularly important on continuous duty applications Maintenance Information 2 Periodically check the compressed air components and replace...

Page 22: ...mps and withdraw the cage and filter bag Remove bag and inspect cage for excess corrosion broken mesh or other damage and replace as necessary Filter Bag Installation 1 Slide the new filter bag over the wire support frame shown in Filter Bag Assembly Slide bag carefully until top of bag is tight against the support frame flange 2 Starting at one side of the collector place a filter bag assembly in...

Page 23: ... them back in the collector 7 Reinstall jet tube retainer bars HelixTube Filter Removal 1 Open access door and remove jet tube retainer 2 Remove jet tubes and set aside Cover the openings to the diaphragm valves To remove jet tube unbolt the top of the jet tube from the top 3 Remove the hex nuts securing the insert clamps Remove the clamps and set aside 4 Remove venturis and helix tubes Set ventur...

Page 24: ...t helix tube filters and place a clamp over one end of both venturis Install a nut and tighten using a deep well socket and extension Do not overtighten Maximum recommended torque is 20 ft lb Note Tighten bottom clamp first 4 Repeat to install all helix tubes 5 Replace jet tubes with the open end pressed firmly into its locator and the orifices directed toward the helix tube filter See Jet Tube In...

Page 25: ...f the fan Location must be clear of all obstructions such as utility lines or roof overhang To avoid personal injury and or damage to equipment ensure fan blowers are properly attached to equipment The use of a damper or variable fan drive VFD is required to control airflow through the collector Lack of a control damper or VFD will shorten filter life The Torit Backward Inclined TBI fan blower can...

Page 26: ...ir plenum and the low pressure tap is located in the clean air plenum 1 Choose a convenient accessible location on or near the collector for mounting that provides the best visual advantage 2 Plug the pressure ports on the back of the gauge using two 1 8 in NPT pipe plugs supplied Install two 1 8 in NPT male adapters supplied with the gauge into the high and low pressure ports on the side of the g...

Page 27: ...and low pressure ports Tighten screws 3 On the back of the gauge remove four 6 32 x 5 16 in screws and plastic enclosure Set aside Add two jumper wires supplied by customer Remove the jumper from the pressure switch located on the timer board if equipped Using the 3 4 in conduit opening wire the gauge as shown Reassemble and fasten enclosure securely 4 Thirty five feet of plastic tubing is supplie...

Page 28: ...gh pressure port low pressure port 1 8 in NPT x 90 male elbow 1 8 in NPT adapter 3 8 in flat washer dirty air plenum 1 8 in NPT adapter 1 8 in NPT x 90 elbow static pressure tee 1 8 in NPT x 90 male elbow 1 8 in NPT adapter 3 8 in flat washer clean air plenum 1 8 in NPT coupling mounting bracket Photohelic Gauge Installation ...

Page 29: ...ters creating a pressure drop The Delta P Controller measures the pressure drop and provides a visual display in inches water gauge or metric SI collectors of daPa Filter Cleaning When the pressure drop across the filters reaches the High Pressure On setpoint the controller closes an output relay allowing a timer to trigger the cleaning valves sequentially When the controller senses that the press...

Page 30: ... Delta P Plus Controller offers three filter cleaning options 1 Differential Pressure Cleaning DFF When the pressure drop across the filters reaches the Controller s High Pressure On setpoint the Controller closes an output relay allowing a sequential timer to trigger the cleaning valves When the Controller senses that the pressure drop has decreased to the Low Pressure Off setpoint the relay open...

Page 31: ... complete collector failure For example if the motor of a screw conveyor that is not interlocked stops the filter housing will gradually fill with dust until completely choked Compressor failure could also cause similar blockage If interlocking electrical components and possible flow interruption is not an option installing an alarm system can help prevent sudden system failure Use zero speed swit...

Page 32: ... the venting of an explosion must be safely directed outdoors away from areas occupied by personnel to reduce risk of personal injury and or property damage The risk of personal injury and or property damage can be minimized or avoided by locating vented equipment outside buildings and away from normally occupied areas Explosion vents should be inspected regularly to confirm physical and operation...

Page 33: ...s Incorrect manifold pressure Check pulse pressure at manifold See Rating and Specifications in this manual Excess moisture in the compressed air supply Check that the compressed air supply is oil and moisture free No pulse to diaphragm valves Check the solenoid and diaphragm valves by feeling the rubber hose for pulse Feel the vent opening on the solenoid valve for pulse If all valves are affecte...

Page 34: ...r is not full and that the equipment served is operating Turn fan OFF and allow the controller to perform several complete cleaning cycles Remove each filter bag vacuum outside surfaces and reinstall Replace damaged or torn filters Obstructed ductwork Check and remove obstructions Clean air outlet discharging dust Filter bags not installed correctly See Filter Bag Replacement Torn or damaged filte...

Page 35: ......

Page 36: ...ers including electric motors fans and control components After Donaldson has been given adequate opportunity to remedy any defects in material or workmanship Donaldson retains the sole option to accept return of the goods with freight paid by the purchaser and to refund the purchase price for the goods after confirming the goods are returned undamaged and in usable condition Such a refund will be...

Reviews: