Dalamatic Cased, DLMC 1/2/15 through 4/8/15
14
Fan Starter
Control Box
Disconnect
1FU
2FU
3FU
208-230V
60 Hz/3Ph
IL1
IL2
IL3
1M
1OL
1T1
1T2
1T3
230V
115V
H1
H2
H3
H4
X1
X2
stop
start
1M
1M
1TGS
fan
motor
OFF time
ON time
program
pins
program jumper
pressure
switch
timing
logic
power
supply
control
logic
4FU, 3A
105 to 135 V
50-60 Hz
solenoid
valves
COM
L1
L2
L3
Disconnect, fuses, low voltage blower starter, and 1TGS switch are customer-supplied.
Note: Check that the program jumper is attached to the correct program pin number
for the number of solenoid outputs used.
Use wiring diagram provided with unit
Wiring by others
Wiring by factory
L1 L2
2
1
Solid-State Timer Typical Wiring Diagram
Input
105-135V/50-60Hz/1Ph
Output Solenoids
The load is carried and turned ON and OFF by the 200
watt maximum-load-per-output solid-state switch.
Pulse ON Time
Factory set at 100-milliseconds, or 1/10-second.
Do not adjust pulse ON time
unless the proper test equipment
is available. Too much or too little ON time can
cause shortened filter life.
Pulse OFF Time
Factory set at 10-seconds, adjustable from 1.5-sec
minimum to maximum 30-seconds.
Operating Temperature Range
-20° F to 130° F
Transient Voltage Protection
50 kW transient volts for 20-millisecond duration once
every 20 seconds, 1% duty cycle.
Solenoid Valves
115-Volt at 19.7 watts each