14

L. Furnace/Aqua Temperature Differential 

Setting (CCC 2 Only)

This system can be configured to operate using an ON/OFF 

differential of either 1 degree F. or 2 degree F. See FIG. 24.

 

1.  To  set  the  differential,  simultaneously  press  the 

PROGRAM

 button and the   up button on the 

CCC 2 thermostat. "diF1" will appear in the display 

while the buttons are pressed. See FIG. 24. To 

set the 2 degree differential, simultaneously press 

the 

PROGRAM

 button and the   down  button. 

"diF2 will appear in the display while the buttons 

are pressed.

FIG. 24

MAINTENANCE

A.  Air Filters

 

1.  Periodically (a minimum of every 2 weeks of op

-

eration) slide out the return air filters located on 

the end of the air distribution box. Wash the filters 

with soap and warm water, let dry and then rein

-

stall.

Note:

 To insure easy future removal the filters need to be 

replaced with the domed side of their handle positioned 

towards the ceiling.

Note:

 Never run the unit without both return air filters in 

place. This will plug the unit evaporator coil with dirt and 

may  substantially  degrade  the  performance  of  the  unit 

over time.

B.  Air Distribution Box Housing

 

1.  Clean air distribution box housing with a soft cloth 

dampened with a mild detergent. Never use furni-

ture polish or scouring powders.

C.  Fan Motor

 

1.  The  blower  motor  is  factory  lubricated  and  re

-

quires no service.

D.  Frost Formation On Cooling Coil

 

1.  Frost on a small portion of the coil is not unusual. 

Under  certain  conditions,  ice  may  form  on  the 

evaporator coil. This is indicated by very cold out

-

put  at  very  low  air  speed  and  the  icing  can  be 

seen through the hole network with the filters re

-

moved. If this should occur, inspect the filter and 

clean if dirty. Make sure air vents are open and 

not obstructed. Units have a greater tendency to 

frost  when  the  outside  temperature  is  relatively 

low. This may be prevented by adjusting the ther

-

mostat control knob to a warmer setting (counter 

clockwise). Should frosting continue, operate on 

any fan 

ONLY

 setting until the cooling coil is free 

of frost; then resume normal operation. If frost 

condition persist, contact your local service cen

-

ter for assistance.

SERVICE-UNIT DOES NOT OPERATE

If your unit fails to operate or operates improperly, check 

the following before calling your service center.

A.

  If RV connected to motor generator, check to be sure 

motor generator is running and producing power.

B.

  If RV connected to power supply by a land line, check 

to be sure line is sized properly to run unit load and it 

is plugged into power supply.

C.

  Check your fuse or circuit breaker to see if it is open. 

Insure  fuse  is  not  burnt,  or  circuit  breaker  is  "ON" 

and not activated.

D.

  After the above checks, call your local service center 

for further help. This unit must be serviced by quali

-

fied service personnel only.

E.

  When calling for service, always give the following:

 

1.  Unit model and serial number found on identification 

label located on base pan of unit bottom. (Remove 

filter and view through network of holes) 

 

2.  Air distribution box model and serial number found 

on rating plate located on ceiling template. Observe 

this rating plate through the air distribution box right 

side vent opening.

Summary of Contents for 641415.30 series

Page 1: ...ilt In Optional 3106486 XXX 641732 Digital Board Built In N A 641735 Digital Board Built In N A 641835 CCC 2 Board Built In Optional 3311931 XXX 641932 LCD Board Built In N A 641935 LCD Board Built In N A Heat Pump 651515 CCC Board Built In Optional 3106486 XXX 651516 CCC Board Built In Optional 3106486 XXX 651815 CCC 2 Board Built In Optional 3311931 XXX 651816 CCC 2 Board Built In Optional 33119...

Page 2: ...tio and window awnings will reduce heat gain by removing the direct exposure to the sun They also add a nice area to enjoy company dur ing the cool of the evening D Condensation Note The manufacturer of this unit will not be responsible for damage caused by condensed moisture on ceilings or other surfaces Air contains moisture and this moisture tends to condense on cold surfaces When air enters th...

Page 3: ...15 80X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641915C85X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641916 30X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C35X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916 80X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C85X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641932 30X 11 000 10 5 53 0 3 5 ...

Page 4: ...Amount of insulation in walls and roof Geographical location where the RV will be used Personal comfort level required 1 For one unit installation The unit should be mounted slightly forward of center front to back and centered from side to side 2 For two unit installations Install one unit 1 3 and one unit 2 3 s from front of RV and centered from side to side It is preferred that the unit be inst...

Page 5: ...3 a This supply wire must be located in the front portion of the 14 1 4 x 14 1 4 1 8 open ing b The power MUST be on an appropriately sized separate time delay fuse or circuit breaker The proper size protection can be determined from the chart on page 3 c Make sure at least 15 of supply wire extends into the roof opening This insures an easy connection at the junction box d Wiring MUST comply with...

Page 6: ...enerator Start Kit CCC and CCC 2 Only a If an Automatic Generator Start AGS kit will be installed an additional 4 conductor com munication cable must be routed from the last unit to the location of the AGS kit Follow AGS kit instructions for installation E Choosing Thermostat Location 1 CCC and CCC 2 WITHOUT Indoor Temperature Sensor Analog Digital and Single Zone LCD Thermostat The proper locatio...

Page 7: ...allation e CCC 2 Thermostat Installation i Carefully separate the thermostat base plate from the thermostat cover Insert a small screw driver into the slot on bot tom of thermostat and disengage the tab See FIG 8 FIG 7 CCC 2 Thermostat Rear View Wall Disengage Tab CCC 2 Thermostat FIG 8 ii Insert the 4 conductor communication cable through the hole in base plate Align thermostat base plate with ho...

Page 8: ... Orange wire to the HS HP terminal White wire to the FUR terminal if appli cable f Inspect all connections to make sure they are tight and not touching any other terminals or wires g Push the wires back through the base into the wall Place cover on the thermostat and push until an audible click is heard 5 SZLCD Thermostat Note The wire colors listed for the three conductor cable match the wire col...

Page 9: ...Power Supply 2 Remove air distribution box and mounting hard ware from the air distribution box kit carton 3 Remove wire tie holding center of rear aluminum bracket to plastic template 4 Reach up into the return air opening and pull the unit electrical wires down for later connection 5 Mount the junction box with screws to the framing in front of the 14 1 4 x 14 1 4 1 8 opening See FIG 15 Return A...

Page 10: ... Trim Duct 1 2 to 1 Below Ceiling Template Ceiling Template Mounting Bolt Mounting Bolt Front Do Not Disturb Thermostat Bulb PROPERTY DAMAGE HAZARD If bolts are left loose there may not be an adequate roof seal or if over tightened damage may occur to the unit base or ceiling template Tighten to torque specifications listed in this manual Install 2 Screws In Tabs Duct Adapter Screw Holes Must Line...

Page 11: ...tive 12 VDC terminal at the sup ply battery Failure to obey this warning may cause damage to equipment c Connect red white wire protruding from the units return air opening to the seven wire cable thermostat 7 5 terminal d Connect the green wire protruding from the units return air opening to the seven wire ca ble thermostat GND terminal e Connect the yellow wire protruding from the units return a...

Page 12: ...er s Guide Reconnect the 12 VDC and 120 VAC power sup plies Check fan speeds cooling mode heat pump mode and furnace mode if connected If features do not work disconnect the 12 VDC and 120 VAC power supplies and verify that all wiring is correct K System Configuration Reset Check Out CCC and CCC 2 Thermostat Only Now that the system is installed it is necessary to do a system configuration reset a...

Page 13: ...ional zone a Ext Stage Ext Stage is not used on this unit Leave in the OFF position b Zone selection Each CCC 2 thermostat can have up to 4 zones When only one unit is installed it becomes Zone 1 and no dip switch setting is required Each additional unit must be assigned a zone 2 through 4 Each unit must have a different zone setting c Stage selection Stage is not used on this unit Leave in the OF...

Page 14: ...ator coil This is indicated by very cold out put at very low air speed and the icing can be seen through the hole network with the filters re moved If this should occur inspect the filter and clean if dirty Make sure air vents are open and not obstructed Units have a greater tendency to frost when the outside temperature is relatively low This may be prevented by adjusting the ther mostat control ...

Page 15: ...15 FIG 25 WIRING DIAGRAM 6414 Series OPTIONAL ...

Page 16: ...0 12 20 7 7 7 5 7 2035 6625 75 86 233 5 9 21 8 7256 21 72 7 67 7 5 6 1625 5 725 5 1 5 1 8 7 6 5 2 7 7 02725 5 51 51 7 50 3 66 51 1 237 5 37 5 5 67 57 9 9 2 6 851 2 6 851 51 1 225 7 03 6 1625 32 5 02 8 2 5 7 03 287 225 6 1625 3 02 6 21 620 127 86 7 5 0 17 5 0 7 6 7 7 6415 Series ...

Page 17: ...5 1 725 5 1 72 767 7 6833 9 851 851 9 5 7 5 25 200 9 8 8 9 72 767 7 1 7 1 87 51 57 21 21 8 7256 2 86 233 5 9 5 6 1625 5 5 8 20 12 02725 62 5 25 57 7 5 1 725 86 6 5 2 5 8 7 5 67 57 3 5 7 7 5 37 5 237 641915 641916 Series 641932 641935 Series ...

Page 18: ... 9 37 5 237 5 7 7 5 67 57 3 5 7 8 5 2 5 6 287 225 7 03 6 1625 62 5 25 57 7 5 1 725 86 02725 12 20 8 5 5 5 6 1625 9 86 233 5 2 21 8 7256 21 51 57 7 1 87 1 767 7 72 9 8 8 9 200 25 5 5 7 9 851 851 9 6833 767 7 72 725 5 1 5 1 3 66 75 6518 Series ...

Reviews: