background image

13

 

e.  Heat Pump - On heat pump models the #7 dip 

switch is in the "ON" position from the factory. 

Non heat pump models leave in the "OFF" 

position.

 

f.  Furnace - If a Furnace/Aqua heat system has 

been connected to this unit, the furnace dip 

switch must be placed in the “ON” position.

 

g.  Dehumidify - Dehumidify is not used on this 

unit. Leave in the “OFF” position.

 

h.  Gen start selection - Leave in the “OFF” posi

-

tion.

 

i.  Replace the unit electrical box cover and out 

side plastic shroud.

 

j.  Repeat  this  procedure  for  each  additional 

zone.

 

 

a.  Each CCC thermostat can have up to 4 zones. 

When  only  one  unit  is  installed  it  becomes 

Zone 1 and no dip switch setting is required. 

Each additional unit must be assigned a zone 

(2 through 4). Each unit must have a different 

zone setting.

b.  Heat  strip  selection  -  On  heat  strip  models 

the #1 dip switch is in the "ON" position from 

the  factory.  Non  heat  strip  models  leave  in 

the "OFF" position.

c.  Furnace selection - when a furnace has been 

connected to a zone, place the furnace dip 

switch “ON” for that zone.

d.  Differential - differential is the temperature 

difference  between  the  “ON/OFF”  cycle  of 

the thermostat in the furnace mode. The nor-

mal differential is preset in the circuit board 

with the dip switch set to the “OFF” position. 

In  some  situations,  it  may  be  necessary  to 

decrease the differential. The location of the 

thermostat may create a condition where the 

normal differential will not maintain your com

-

fort zone. If this occurs, the differential can 

be  shortened  by  placing  the  differential  dip 

switch to the “ON” position.

Note: 

Setting the differential dip switch should only be re

-

quired when installation conditions are less than desirable 

and is not covered under the limited warranty.

 

 

e.  Stage selection - stage is not used on these 

units. Leave in the “OFF” position.

 

 

f.  Gen start selection - leave in the “OFF” posi

-

tion.

 

 

g.  Replace the unit electrical box cover.

 

h.  Repeat this procedure for each additional 

zone 

 

 

 

a.  Ext. Stage - Ext. Stage is not used on this unit. 

Leave in the “OFF” position.

 

b.  Zone selection - Each CCC 2 thermostat can 

have  up  to  4  zones.  When  only  one  unit  is 

installed it becomes Zone 1 and no dip switch 

setting is required. Each additional unit must 

be assigned a zone (2 through 4). Each unit 

must have a different zone setting.

 

c.  Stage selection - Stage is not used on this unit. 

Leave in the “OFF” position.

 

d.  Heat Strip - On heat strip models the #6 dip 

switch is in the "ON" position from the factory. 

Non heat strip models leave in the "OFF" 

position.

On Position

Off Position

FIG. 23

CCC Dip Switch Selection

CCC 2 Dip Switch Selection

 

2.  System Reset

 

a. CCC system

 

 

After setting the dip switches in the electronic 

control, do a system reset.

i.  Turn the ON/OFF switch to the 

“OFF”

 

position. 

ii.  Simultaneously  press  and  hold  the 

MODE 

and 

ZONE

  push-buttons  while 

turning the 

ON/OFF

 switch to 

“ON”

FF  should  appear  in  LCD  display  un

-

til the mode and zone push-buttons are 

 

released.

iii.  When a dip switch is turned on after initial 

configuration, a system reset will need to 

be done before the CCC thermostat will 

recognize the updated selection.

 

b.  CCC 2 system

 

 

After setting the dip switches in the electronic 

control, do a system reset.

i.  Reconnect the 12 VDC and 120 VAC power 

supplies.

ii.  Make sure the  CCC 2 thermostat is in the 

“OFF”

 mode. 

iii.  Simultaneously  press  the 

MODE

 and 

ZONE 

buttons. The LCD will display “IniT” 

and all available zones.

iv.  Release the 

MODE

 and 

ZONE

 buttons.

v.  Press the 

ON/OFF

 button to exit system 

set up.

vi.  When a dip switch is turned on after initial 

configuration, a system reset will need to 

be done before the CCC 2 thermostat will 

recognize the updated selection.

 

3.  System Checkout

 

 

Verify that all features of the installed system work. 

See CCC and CCC 2 thermostat Operating Instruc-

tions or User’s Guide. Reconnect the 12 VDC and 

120 VAC power supplies. Check fan speeds, cool-

ing mode, heat pump mode, and furnace mode (if 

connected). If the features do not work disconnect 

the 12 VDC and 120 VAC power supplies and 

verify that all wiring is correct and that the correct 

dip switches have been turned on. 

Summary of Contents for 641415.30 series

Page 1: ...ilt In Optional 3106486 XXX 641732 Digital Board Built In N A 641735 Digital Board Built In N A 641835 CCC 2 Board Built In Optional 3311931 XXX 641932 LCD Board Built In N A 641935 LCD Board Built In N A Heat Pump 651515 CCC Board Built In Optional 3106486 XXX 651516 CCC Board Built In Optional 3106486 XXX 651815 CCC 2 Board Built In Optional 3311931 XXX 651816 CCC 2 Board Built In Optional 33119...

Page 2: ...tio and window awnings will reduce heat gain by removing the direct exposure to the sun They also add a nice area to enjoy company dur ing the cool of the evening D Condensation Note The manufacturer of this unit will not be responsible for damage caused by condensed moisture on ceilings or other surfaces Air contains moisture and this moisture tends to condense on cold surfaces When air enters th...

Page 3: ...15 80X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641915C85X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641916 30X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C35X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916 80X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C85X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641932 30X 11 000 10 5 53 0 3 5 ...

Page 4: ...Amount of insulation in walls and roof Geographical location where the RV will be used Personal comfort level required 1 For one unit installation The unit should be mounted slightly forward of center front to back and centered from side to side 2 For two unit installations Install one unit 1 3 and one unit 2 3 s from front of RV and centered from side to side It is preferred that the unit be inst...

Page 5: ...3 a This supply wire must be located in the front portion of the 14 1 4 x 14 1 4 1 8 open ing b The power MUST be on an appropriately sized separate time delay fuse or circuit breaker The proper size protection can be determined from the chart on page 3 c Make sure at least 15 of supply wire extends into the roof opening This insures an easy connection at the junction box d Wiring MUST comply with...

Page 6: ...enerator Start Kit CCC and CCC 2 Only a If an Automatic Generator Start AGS kit will be installed an additional 4 conductor com munication cable must be routed from the last unit to the location of the AGS kit Follow AGS kit instructions for installation E Choosing Thermostat Location 1 CCC and CCC 2 WITHOUT Indoor Temperature Sensor Analog Digital and Single Zone LCD Thermostat The proper locatio...

Page 7: ...allation e CCC 2 Thermostat Installation i Carefully separate the thermostat base plate from the thermostat cover Insert a small screw driver into the slot on bot tom of thermostat and disengage the tab See FIG 8 FIG 7 CCC 2 Thermostat Rear View Wall Disengage Tab CCC 2 Thermostat FIG 8 ii Insert the 4 conductor communication cable through the hole in base plate Align thermostat base plate with ho...

Page 8: ... Orange wire to the HS HP terminal White wire to the FUR terminal if appli cable f Inspect all connections to make sure they are tight and not touching any other terminals or wires g Push the wires back through the base into the wall Place cover on the thermostat and push until an audible click is heard 5 SZLCD Thermostat Note The wire colors listed for the three conductor cable match the wire col...

Page 9: ...Power Supply 2 Remove air distribution box and mounting hard ware from the air distribution box kit carton 3 Remove wire tie holding center of rear aluminum bracket to plastic template 4 Reach up into the return air opening and pull the unit electrical wires down for later connection 5 Mount the junction box with screws to the framing in front of the 14 1 4 x 14 1 4 1 8 opening See FIG 15 Return A...

Page 10: ... Trim Duct 1 2 to 1 Below Ceiling Template Ceiling Template Mounting Bolt Mounting Bolt Front Do Not Disturb Thermostat Bulb PROPERTY DAMAGE HAZARD If bolts are left loose there may not be an adequate roof seal or if over tightened damage may occur to the unit base or ceiling template Tighten to torque specifications listed in this manual Install 2 Screws In Tabs Duct Adapter Screw Holes Must Line...

Page 11: ...tive 12 VDC terminal at the sup ply battery Failure to obey this warning may cause damage to equipment c Connect red white wire protruding from the units return air opening to the seven wire cable thermostat 7 5 terminal d Connect the green wire protruding from the units return air opening to the seven wire ca ble thermostat GND terminal e Connect the yellow wire protruding from the units return a...

Page 12: ...er s Guide Reconnect the 12 VDC and 120 VAC power sup plies Check fan speeds cooling mode heat pump mode and furnace mode if connected If features do not work disconnect the 12 VDC and 120 VAC power supplies and verify that all wiring is correct K System Configuration Reset Check Out CCC and CCC 2 Thermostat Only Now that the system is installed it is necessary to do a system configuration reset a...

Page 13: ...ional zone a Ext Stage Ext Stage is not used on this unit Leave in the OFF position b Zone selection Each CCC 2 thermostat can have up to 4 zones When only one unit is installed it becomes Zone 1 and no dip switch setting is required Each additional unit must be assigned a zone 2 through 4 Each unit must have a different zone setting c Stage selection Stage is not used on this unit Leave in the OF...

Page 14: ...ator coil This is indicated by very cold out put at very low air speed and the icing can be seen through the hole network with the filters re moved If this should occur inspect the filter and clean if dirty Make sure air vents are open and not obstructed Units have a greater tendency to frost when the outside temperature is relatively low This may be prevented by adjusting the ther mostat control ...

Page 15: ...15 FIG 25 WIRING DIAGRAM 6414 Series OPTIONAL ...

Page 16: ...0 12 20 7 7 7 5 7 2035 6625 75 86 233 5 9 21 8 7256 21 72 7 67 7 5 6 1625 5 725 5 1 5 1 8 7 6 5 2 7 7 02725 5 51 51 7 50 3 66 51 1 237 5 37 5 5 67 57 9 9 2 6 851 2 6 851 51 1 225 7 03 6 1625 32 5 02 8 2 5 7 03 287 225 6 1625 3 02 6 21 620 127 86 7 5 0 17 5 0 7 6 7 7 6415 Series ...

Page 17: ...5 1 725 5 1 72 767 7 6833 9 851 851 9 5 7 5 25 200 9 8 8 9 72 767 7 1 7 1 87 51 57 21 21 8 7256 2 86 233 5 9 5 6 1625 5 5 8 20 12 02725 62 5 25 57 7 5 1 725 86 6 5 2 5 8 7 5 67 57 3 5 7 7 5 37 5 237 641915 641916 Series 641932 641935 Series ...

Page 18: ... 9 37 5 237 5 7 7 5 67 57 3 5 7 8 5 2 5 6 287 225 7 03 6 1625 62 5 25 57 7 5 1 725 86 02725 12 20 8 5 5 5 6 1625 9 86 233 5 2 21 8 7256 21 51 57 7 1 87 1 767 7 72 9 8 8 9 200 25 5 5 7 9 851 851 9 6833 767 7 72 725 5 1 5 1 3 66 75 6518 Series ...

Reviews: