![Dometic 641415.30 series Installation Instructions Manual Download Page 12](http://html1.mh-extra.com/html/dometic/641415-30-series/641415-30-series_installation-instructions-manual_2518167012.webp)
12
FIG. 19
P o s i t i o n
ADB Walls
Inside And
Against End
Of Template
Walls
Raise Back
End Of ADB
To Ceiling
Push Here To Engage
Latches, Then Remove Labels
2. Push up on the ADB at the locations indicated by
the paper labels to engage the snap locks. There
will be a quiet click heard when each latch en
-
gages. See FIG. 19.
3. Hold the air distribution box to the ceiling with one
hand and install two coarse threaded 3.5 mm X 19
mm sharp pointed screws in the location shown in
FIG. 20.
4. Auxiliary screws may be installed at the locations
shown. These are
NOT
required to secure the ADB
to the template, but may be desired for aesthetic
purposes in some ceiling geometries. See FIG. 20.
Auxiliary Screw Locations
Auxiliary Screw
Locations
FIG. 20
Install 2 Primary
Mount Screw First
5. Filter installation. Slide filters into slots in air dis
-
tribution box. The outward curved side of the filter
handle faces the ceiling. See FIG. 20.
This completes the digital, analog, and LCD thermostat
unit installation. (Proceed to section K to complete the CCC
and CCC 2 thermostat installation)
Verify that all features of the system work. See digital,
analog, or LCD thermostat Operating Instructions or User's
Guide. Reconnect the 12 VDC and 120 VAC power sup-
plies. Check fan speeds, cooling mode, heat pump mode,
and furnace mode (if connected). If features do not work,
disconnect the 12 VDC and 120 VAC power supplies and
verify that all wiring is correct.
K. System Configuration, Reset & Check Out
(CCC and CCC 2 Thermostat Only)
Now that the system is installed, it is necessary to do a
system configuration, reset and check out.
1. Electronic Control Configuration
Depending on the equipment options installed by the
recreational vehicle manufacturer, the appropriate
dip switches will need to be switched to the "ON"
position. Placing the switch in the "ON" position
selects that option. See FIGS. 21, 22 & 23.
Note:
Dip switches are in the "OFF" position when shipped
from the factory except on heat strip and (heat pump CCC 2
only) models. On these models the appropriate dip switch,
heat strip or (heat pump CCC 2 only), is in the "ON" posi
-
tion from the factory. To gain access to the dip switches,
the outside plastic shroud must be removed from the unit.
Next remove the electrical box cover. The electrical box
will be on the curb side of the RV after installation. See
FIGS. 21, 22 & 23.
Dip Switches
FIG. 21
CCC
Dip Switches
CCC 2
Ext. Stage
Zone 2
Zone 3
Stage
Heat Strip
Heat Pump
Furnace
Dehumidify
Gen Start
Zone 4
FIG. 22
Dip Switches
CCC
CCC 2
Heat Strip
Zone 2
Zone 3
Zone 4
Furnace
Differential
Stage
Gen Start