Dometic 641415.30 series Installation Instructions Manual Download Page 12

12

FIG. 19

P o s i t i o n 

ADB Walls 

Inside And 

Against End 

Of Template 

Walls

Raise  Back  

End Of ADB 

To Ceiling

Push Here To Engage

Latches, Then Remove Labels

 

2.  Push up on the ADB at the locations indicated by 

the paper labels to engage the snap locks. There 

will  be  a  quiet  click  heard  when  each  latch  en

-

gages. See FIG. 19.

 

 

3.  Hold the air distribution box to the ceiling with one 

hand and install two coarse threaded 3.5 mm X 19 

mm sharp pointed screws in the location shown in 

FIG. 20.

 

4.  Auxiliary screws may be installed at the locations 

shown. These are 

NOT

 required to secure the ADB 

to the template, but may be desired for aesthetic 

purposes in some ceiling geometries. See FIG. 20.

Auxiliary Screw Locations

Auxiliary Screw

Locations

FIG. 20

Install 2 Primary 

Mount Screw First

 

5.  Filter installation. Slide filters into slots in air dis

-

tribution box. The outward curved side of the filter 

handle faces the ceiling. See FIG. 20.

This completes the digital, analog, and LCD  thermostat 

unit installation. (Proceed to section K to complete the CCC 

and CCC 2 thermostat installation)

Verify  that  all  features  of  the  system  work.  See  digital, 

analog, or LCD  thermostat Operating Instructions or User's 

Guide. Reconnect the 12 VDC and 120 VAC power sup-

plies. Check fan speeds, cooling mode, heat pump mode, 

and furnace mode (if connected). If features do not work, 

disconnect the 12 VDC and 120 VAC power supplies and 

verify that all wiring is correct.

K.  System Configuration, Reset & Check Out 

(CCC and CCC 2 Thermostat Only) 

Now that the system is installed, it is necessary to do a 

system configuration, reset and check out.

 

1.  Electronic Control Configuration

  

Depending on the equipment options installed by the 

recreational vehicle manufacturer, the appropriate 

dip switches will need to be switched to the "ON" 

position. Placing the switch in the "ON" position 

selects that option. See FIGS. 21, 22 & 23.

Note: 

Dip switches are in the "OFF" position when shipped 

from the factory except on heat strip and (heat pump CCC 2 

only) models. On these models the appropriate dip switch, 

heat strip or (heat pump CCC 2 only), is in the "ON" posi

-

tion from the factory. To gain access to the dip switches, 

the outside plastic shroud must be removed from the unit.  

Next remove the electrical box cover. The electrical box 

will be on the curb side of the RV after installation. See 

FIGS. 21, 22 & 23.

Dip Switches

FIG. 21

CCC

Dip Switches

CCC 2

Ext. Stage
Zone 2
Zone 3

Stage
Heat Strip
Heat Pump
Furnace
Dehumidify
Gen Start

Zone 4

FIG. 22

Dip Switches

CCC

CCC 2

Heat Strip
Zone 2

Zone 3
Zone 4
Furnace
Differential
Stage
Gen Start

Summary of Contents for 641415.30 series

Page 1: ...ilt In Optional 3106486 XXX 641732 Digital Board Built In N A 641735 Digital Board Built In N A 641835 CCC 2 Board Built In Optional 3311931 XXX 641932 LCD Board Built In N A 641935 LCD Board Built In N A Heat Pump 651515 CCC Board Built In Optional 3106486 XXX 651516 CCC Board Built In Optional 3106486 XXX 651815 CCC 2 Board Built In Optional 3311931 XXX 651816 CCC 2 Board Built In Optional 33119...

Page 2: ...tio and window awnings will reduce heat gain by removing the direct exposure to the sun They also add a nice area to enjoy company dur ing the cool of the evening D Condensation Note The manufacturer of this unit will not be responsible for damage caused by condensed moisture on ceilings or other surfaces Air contains moisture and this moisture tends to condense on cold surfaces When air enters th...

Page 3: ...15 80X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641915C85X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641916 30X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C35X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916 80X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C85X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641932 30X 11 000 10 5 53 0 3 5 ...

Page 4: ...Amount of insulation in walls and roof Geographical location where the RV will be used Personal comfort level required 1 For one unit installation The unit should be mounted slightly forward of center front to back and centered from side to side 2 For two unit installations Install one unit 1 3 and one unit 2 3 s from front of RV and centered from side to side It is preferred that the unit be inst...

Page 5: ...3 a This supply wire must be located in the front portion of the 14 1 4 x 14 1 4 1 8 open ing b The power MUST be on an appropriately sized separate time delay fuse or circuit breaker The proper size protection can be determined from the chart on page 3 c Make sure at least 15 of supply wire extends into the roof opening This insures an easy connection at the junction box d Wiring MUST comply with...

Page 6: ...enerator Start Kit CCC and CCC 2 Only a If an Automatic Generator Start AGS kit will be installed an additional 4 conductor com munication cable must be routed from the last unit to the location of the AGS kit Follow AGS kit instructions for installation E Choosing Thermostat Location 1 CCC and CCC 2 WITHOUT Indoor Temperature Sensor Analog Digital and Single Zone LCD Thermostat The proper locatio...

Page 7: ...allation e CCC 2 Thermostat Installation i Carefully separate the thermostat base plate from the thermostat cover Insert a small screw driver into the slot on bot tom of thermostat and disengage the tab See FIG 8 FIG 7 CCC 2 Thermostat Rear View Wall Disengage Tab CCC 2 Thermostat FIG 8 ii Insert the 4 conductor communication cable through the hole in base plate Align thermostat base plate with ho...

Page 8: ... Orange wire to the HS HP terminal White wire to the FUR terminal if appli cable f Inspect all connections to make sure they are tight and not touching any other terminals or wires g Push the wires back through the base into the wall Place cover on the thermostat and push until an audible click is heard 5 SZLCD Thermostat Note The wire colors listed for the three conductor cable match the wire col...

Page 9: ...Power Supply 2 Remove air distribution box and mounting hard ware from the air distribution box kit carton 3 Remove wire tie holding center of rear aluminum bracket to plastic template 4 Reach up into the return air opening and pull the unit electrical wires down for later connection 5 Mount the junction box with screws to the framing in front of the 14 1 4 x 14 1 4 1 8 opening See FIG 15 Return A...

Page 10: ... Trim Duct 1 2 to 1 Below Ceiling Template Ceiling Template Mounting Bolt Mounting Bolt Front Do Not Disturb Thermostat Bulb PROPERTY DAMAGE HAZARD If bolts are left loose there may not be an adequate roof seal or if over tightened damage may occur to the unit base or ceiling template Tighten to torque specifications listed in this manual Install 2 Screws In Tabs Duct Adapter Screw Holes Must Line...

Page 11: ...tive 12 VDC terminal at the sup ply battery Failure to obey this warning may cause damage to equipment c Connect red white wire protruding from the units return air opening to the seven wire cable thermostat 7 5 terminal d Connect the green wire protruding from the units return air opening to the seven wire ca ble thermostat GND terminal e Connect the yellow wire protruding from the units return a...

Page 12: ...er s Guide Reconnect the 12 VDC and 120 VAC power sup plies Check fan speeds cooling mode heat pump mode and furnace mode if connected If features do not work disconnect the 12 VDC and 120 VAC power supplies and verify that all wiring is correct K System Configuration Reset Check Out CCC and CCC 2 Thermostat Only Now that the system is installed it is necessary to do a system configuration reset a...

Page 13: ...ional zone a Ext Stage Ext Stage is not used on this unit Leave in the OFF position b Zone selection Each CCC 2 thermostat can have up to 4 zones When only one unit is installed it becomes Zone 1 and no dip switch setting is required Each additional unit must be assigned a zone 2 through 4 Each unit must have a different zone setting c Stage selection Stage is not used on this unit Leave in the OF...

Page 14: ...ator coil This is indicated by very cold out put at very low air speed and the icing can be seen through the hole network with the filters re moved If this should occur inspect the filter and clean if dirty Make sure air vents are open and not obstructed Units have a greater tendency to frost when the outside temperature is relatively low This may be prevented by adjusting the ther mostat control ...

Page 15: ...15 FIG 25 WIRING DIAGRAM 6414 Series OPTIONAL ...

Page 16: ...0 12 20 7 7 7 5 7 2035 6625 75 86 233 5 9 21 8 7256 21 72 7 67 7 5 6 1625 5 725 5 1 5 1 8 7 6 5 2 7 7 02725 5 51 51 7 50 3 66 51 1 237 5 37 5 5 67 57 9 9 2 6 851 2 6 851 51 1 225 7 03 6 1625 32 5 02 8 2 5 7 03 287 225 6 1625 3 02 6 21 620 127 86 7 5 0 17 5 0 7 6 7 7 6415 Series ...

Page 17: ...5 1 725 5 1 72 767 7 6833 9 851 851 9 5 7 5 25 200 9 8 8 9 72 767 7 1 7 1 87 51 57 21 21 8 7256 2 86 233 5 9 5 6 1625 5 5 8 20 12 02725 62 5 25 57 7 5 1 725 86 6 5 2 5 8 7 5 67 57 3 5 7 7 5 37 5 237 641915 641916 Series 641932 641935 Series ...

Page 18: ... 9 37 5 237 5 7 7 5 67 57 3 5 7 8 5 2 5 6 287 225 7 03 6 1625 62 5 25 57 7 5 1 725 86 02725 12 20 8 5 5 5 6 1625 9 86 233 5 2 21 8 7256 21 51 57 7 1 87 1 767 7 72 9 8 8 9 200 25 5 5 7 9 851 851 9 6833 767 7 72 725 5 1 5 1 3 66 75 6518 Series ...

Reviews: