background image

10

Auto Generator Start (AGS)

On RV’s equipped with an optional AGS Kit, the vehicle generator will automatically 

start when any zone calls for cooling and will shut off when zones reach set point.

The Auto Generator Start (AGS) function will be implemented by an individual power 

module board configured for this function by setting the 

GEN Start

 DIP switch ON. 

On the AGS power module board a relay shall be used to provide a start signal to 

the generator. The normally open relay contacts are utilized and the closure of these 

contacts provides the signal to start the generator. The AGS relay shall be activated 

when any zone or stage requires cooling, heat pump, dehumidifier or heat strip oper

-

ation. When a zone calls for heating, cooling or dehumidification, the AGS relay shall 

be closed, followed by a time delay to allow the generator to warm up after which 

time the output relay will be activated on the zone that initiated the heating, cooling or 

dehumidification request. When the heat/cool and dehumidify requests in all zones 

have been satisfied, the AGS relay will open and the generator will shut-down.

Load Shed

 

The Dometic CCC 2 thermostat has provisions for Load Shedding. The AC power 

module board shall provide the 12 VDC source for the Load Shed signal. This 12 

VDC source shall be turned ON one second before the compressor relay when the 

system calls for the compressor to be ON. The Load Shed source shall remain on 

when compressor is caused to turn OFF due to being disable by either a Freeze 

Sensor or a Load Shed condition. The load shed source signal will be switched to 

the Load Shed input by the normally open contacts or an off-board relay from the RV 

power management system. When the Load Shed signal is detected, the compres

-

sor shall turn OFF.

Defrost Cycle (Heat Pump Models Only)

To  avoid  frost formation  on  the  outside  coil  and  to obtain maximum  performance 

when the outside temperature is less than 42º F. and greater than 30º F., a defrost 

cycle will be initiated. While operating in this temperature range the compressor con

-

tinuous run time is limited to 25 minutes. When this time is accumulated, the fan will 

shut off, the refrigerant flow will be reversed, and the compressor will continue to run 

for 4.5 minutes. During this 4.5 minute period, the LCD will toggle between HP and 

Defrost. The refrigerant flow will then be reversed and after a 30 second delay the 

fan will resume operation. This cycle will remove any frost formation on the outside 

coil. This cycle will repeat itself until the outside temperature is greater than 42º F. If 

the outside temperature becomes less than 30º F. the heat pump will shut OFF and 

the auxiliary heat (if provided) will turn on.

Compressor Time Delay

A time delay of approximately two minutes occurs any time the compressor is re

-

quired to begin the cooling or heat pump cycle.

Power Interruption

In the event the power to the air conditioner or control is interrupted, the system will 

restart with the previous set points once power is restored.

LCD Error Code

When the system determines that one of the faults listed below has occurred an error 

code will be displayed in the LCD for the zone in which the error occurred.  During 

normal operation, a blinking zone number indicates a fault has occurred. The error 

code is displayed in place of the temperature set-point. 

Error Code:

E1  Loss of communication between the CCC 2 thermostat and all system power 

module boards. System will shut down.

E1  Loss of communication between the CCC 2 thermostat and an individual system 

power  module  board. The  LED  will  display  error  code  EI  and  the  zone  num

-

ber that lost communication. Any additional zones that loose communication will 

blink in addition to the current zone.

E2  Open circuit or out-of-range indoor temperature sensor. All heat , cool, and de

-

humidify operations will be locked out. Manual fan operation will continue.

E3  Shorted Indoor Temperature Sensor. All heat, cool, and dehumidify operation will 

be locked out. Manual fan operation will continue.

E4  Open circuit or out of range Outdoor Temperature Sensor (select models). Heat  

pump and dehumidification operation will be locked out. Air conditioner, furnace, 

heat strip and fan operation can continue to operate. 

E5  Open circuit or out of range Freeze Sensor. Air conditioner and dehumidification 

operation will be locked out. Heat pump, furnace, heat strip and fan operation 

can continue to operate but displays the last temperature set-point. 

E6  Open circuit Humidity Sensor (Select Models). Air conditioner and dehumidifica

-

tion will be locked out. Heat pump, furnace heat strip and fan can continue to 

operate.

E7  Loss of 120 VAC power to all power module boards on the system. The system 

will shut down. 

E8 Invalid zone configuration. The heat pump and heat strip DIP switches are both 

set to the ON position in one zone. Heat pump, heat strip, air conditioner, and  

dehumidify operation will be locked out in the affected zone.

E9 Invalid zone configuration. The dehumidifier DIP switch and either the heat pump 

or heat strip DIP switches are set to the ON position in one zone. Heat pump, 

heat strip, air conditioner, and dehumidify operation will be locked out in the af

-

fected zone.

Summary of Contents for 3312024 series

Page 1: ...Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026 XXX With Dehumidify 3312024 XXX With Out Dehumidify ...

Page 2: ... the operation of the CCC 2 thermostat review the following diagrams and accompanying text that explain the functional characteristics of this system Your CCC 2 thermostat is equipped with a liquid crystal display LCD that identifies the mode of operation OFF Cool Heat Pump Fan Heat Strip Auto Furnace or Aqua temperature set point zone identification 1 2 3 4 fan speed Auto Low Med High program 1 a...

Page 3: ... Mode Off Time 10 00 PM Your Dometic CCC 2 thermostat has been pre programmed Review settings below and adjust the settings to your personal comfort level Note Any time the CCC 2 is in an idle stage not illuminated you will need to wake it up by pressing any button on the CCC 2 before it will recognize a new setting at tempt Quick reference to LCD icons Temperature Humidity Set Point or Error Code...

Page 4: ... sensor is located in the roof top unit The CCC 2 thermostat temperature measuring range is between 5 F and 105 F When the roof top unit is exposed to direct sunlight the upper limit of the CCC 2 thermostat could be reached even though the actual outdoor temperature is lower than 105 F Outside tempera tures above 105 F will be displayed as 105 F Clock Setting Press the CLOCK button to initiate the...

Page 5: ...page 8 for more information on auto fan Mode Selection Press the MODE button and the LCD will display the first available mode Each suc cessive press will advance to the next available mode Continue to press the MODE button until the desired mode appears Depending on the systems installed your choices will be OFF COOL AUTO HP FURN or AQUA HS and FAN See Mode Description on page 6 7 for more inform...

Page 6: ...t on the CCC 2 When the system calls for heating there will be a delay of approximately two minutes During this delay the hour glass icon will be displayed in the LCD In auto fan the compressor will turn ON first followed by the fan in approximately 15 seconds In this mode there are 4 fan speed selections LOW The fan operates continuously at low speed The compressor cycles On and OFF MED The fan o...

Page 7: ...on on page 2 To set the 1 degree differential simultaneously press PROGRAM button and up button dIF1 will appear in the display while the buttons are pressed To set the 2 degree differential simultaneously press the PROGRAM button and the down button dIF2 will appear in the display while the buttons are pressed In this mode there are 4 fan speed selections LOW The fan operates continuously at low ...

Page 8: ... humidity is above the humidity set point the compressor will cycle ON and if the fan is in the AUTO mode it will run on LOW speed If LOW MED or HIGH speed is selected the fan will run in the speed selected When the humidity is 5 or less than the humidity set point the compressor will cycle OFF The dehumidify feature does not permit operation under the following conditions Outdoor temperature is b...

Page 9: ...Stage must be set to the ON position in order to configure the power module board for the on demand secondary stage operation in this example Zone 2 and Ext Stage DIP switches are in the ON position In this stage configuration the CCC 2 thermostat temperature set point will be used for both the primary and the secondary stage air conditioner heat pump Only one indoor temperature sensor is required...

Page 10: ...cle will repeat itself until the outside temperature is greater than 42º F If the outside temperature becomes less than 30º F the heat pump will shut OFF and the auxiliary heat if provided will turn on Compressor Time Delay A time delay of approximately two minutes occurs any time the compressor is re quired to begin the cooling or heat pump cycle Power Interruption In the event the power to the a...

Page 11: ...e settings are changed a system reset will need to be done before the CCC 2 thermostat will recognize the updated selection To do a system reset Make sure the CCC 2 thermostat is in the OFF mode Simultaneously press the MODE and ZONE buttons The LCD will display IniT and all available zones Release the MODE and ZONE buttons Press the ON OFF button to exit system set up System Reset Procedure ...

Page 12: ...ain of the vehicle may be reduced by 1 Parking the RV in a shaded area 2 Using window shades blinds and or curtains 3 Keeping windows and doors shut or minimizing usage 4 Avoiding the use of heat producing appliances Operation on High Fan Cooling mode will give optimum or maximum efficiency in high humidity or high outside temperatures Starting the air conditioner early in the morning and giving i...

Reviews: