Measuring principle of HVAC temperature sensors in general:
The measuring principle of temperature sensors is based on an internal sensor that outputs a temperature-dependent resistance signal.  
The type of the internal sensor determines the output signal. The following active ⁄ passive temperature sensors are distinguished: 

a)  Pt 100 measuring resistor  (according to DIN EN 60 751)
b)   Pt 1000 measuring resistor  (according to DIN EN 60751)
c)  Ni 1000 measuring resistor  (according to DIN EN 43 760, TCR = 6180 ppm ⁄ K)
d)  Ni 1000_TK 5000 measuring resistor  (TCR = 5000 ppm ⁄ K)
e)  LM235Z, semiconductor IC  (10 mV ⁄ K, 2.73 V ⁄ °C). Ensure correct po ⁄– when connecting!
f)  NTC  (according to DIN 44070)
g) PTC
h)  KTY silicon temperature sensors

The most important resistance characteristics are shown on the last page of these operating instructions. According to their characteristics,  individual 
temperature sensors exhibit different slopes in the range between 0 °C and +100 °C (TK value). Maximum-possible measuring ranges also vary from 
sensor to sensor (for some examples to this see under technical data).

Design of HVAC temperature sensors in general:
Sensors are distinguished by shape type as follows: surface-contacting sensors, cable temperature sensors, and housing-type and built-in  temperature 
sensors.
–  On surface-contacting sensors, the temperature sensor has at least one contact area that must be brought in contact, e.g. with the surface of radia-

tors or pipes. If the contact area is not positioned correctly relative to the surface to be measured, significant temperature measurement errors may 
occur. Good contact area and temperature conduction must be ensured, dirt and unevenness must be avoided, and heat-conductive paste is to be 
used where necessary. 

– On cable temperature sensors, the temperature sensor is installed inside a sensor sleeve, from which a connecting cable is leading out. In addition 

to the standard insulating materials PVC, silicone, and fibreglass with stainless steel texture, other versions are also available that may allow a wider 
range of application.

–  On housing-type sensors, the temperature sensor is embedded in a respective housing. Different designs of housing are available, e.g. with an external 

sensor sleeve (see outside temperature sensor ATF2). Housing-type sensors are normally distinguished into in-wall (FSTF) and on-wall (RTF, ATF) types 
and indoor and wet room versions. Connection terminals are placed on a plate inside the connecting housing.

–  Duct and built-in temperature sensors are distinguished into temperature sensors with interchangeable measuring insert and without interchangeable 

measuring insert. Connection parts are placed inside a connecting head. Standard process connection for immersion sensors is a pipe thread (sizes in 
inches) and a mounting flange for duct sensors. However, it may be designed differently. When a built-in sensor has a neck tube, the  application range 
is usually somewhat wider since ascending heat cannot flow directly and immediately into the connecting head. This is to be noted especially when 
transmitters are installed. The temperature sensor in built-in sensors is always placed inside the front part of the protective tube. On temperature 
sensors with short reaction times, protective tubes are stepped. 

Note!
Select immersion depth for built-in sensors so that the error caused by heat dissipation stays within the admissible error margins. A standard value is: 10 
x diameter of protection tube + sensor length. In connection with housing-type sensors, particularly with outdoor sensors, please consider the influence 
of thermal radiation. For that purpose, a sunshade and radiation protector SS-02 can be attached. 

G  

General notes

Component  ......................................................................... max. thermal load

Connecting cable
PVC, normal ..............................................................................................+70 °C
PVC, heat-stabilized ............................................................................. +105 °C
Silicone ................................................................................................... +180 °C
PTFE  ....................................................................................................... +200 °C
Fibreglass insulation with stainless steel texture  ........................ +400 °C

Housing ⁄ Sensor
see table "Technical Data"

Maximum thermal load on components:

On principle, all temperature sensors shall be  protected 
against unacceptable overheating!

Standard values for individual components and  materials 
selected are shown for operation under  
neutral  atmos phere and otherwise normal conditions  
(see table to the right).

For combinations of different insulating materials,  
the  lowest temperature limit shall always apply.

G  

Resistance characteristics of passive temperature sensors  (see last page)

In order to avoid damages  ⁄ errors, preferably shielded cables are to be used.  
Laying measuring cables parallel with current-carrying  cables must in any case be avoided. EMC directives shall be  observed! 
These instruments must be installed by authorised specialists only!

ATTENTION,  NOTE !  Testing current influences the thermometer‘s 
measuring accuracy due to intrinsic heating and therefore, should 
 never be greater than as specified below:
Sensor current, maximum 

 I 

max

Pt1000  (thin-layer)  .............................................................................. < 0.6 mA
Pt100     (thin-layer) .............................................................................. < 1.0 mA
Ni1000  (DIN),  Ni1000 TK5000  ....................................................... < 0.3 mA
NTC xx  ...................................................................................................... < 2 mW 
LM235Z ....................................................................................... 400  µ A … 5 mA
KTY 81 - 210  .............................................................................................. < 2 mA

Limiting deviation according to classes:
Tolerances at 0 °C:

Platinum sensors (Pt100, Pt1000): 
DIN EN 60751, class B  ........................................................................ ± 0.3 K
1 ⁄  3 DIN EN 60751, class B  .................................................................± 0.1 K

Nickel sensors: 
NI1000 DIN EN 43760, class B  .............................................................. ± 0.4 K
NI1000 1 ⁄  2 DIN EN 43760, class B  ..................................................... ± 0.2 K
NI1000 TK5000 ................................................................................... ± 0.4 K

Summary of Contents for THERMASGARD ETF 7

Page 1: ...ns You have bought a German quality product High performance encapsulation against vibration mechanical stress and humidity High Performance Verguss gegen Vibration mechanischer Belastung und Feuchtigkeit PS PROTECTION PERFECT SENSOR PROTECTION Provedení krytu odolné vůči vibracím mechanickému namáhání a vlhkosti 6000 2150 0000 1XXD1 21500 2020 D1 V104 03 2020 Domat Control System s r o U Panasoni...

Page 2: ...THERMASGARD ETF7 G Rozměry ETF7 Dimensional drawing ETF7 s rychloupínacími šrouby with quick locking screws 14 8 37 8 M16x1 5 107 ø6 ø6 ø4 35 14 33 EL SW 27 G1 2 39 49 ø 4 3 72 64 ...

Page 3: ...THERMASGARD ETF7 G Instalační schéma TH Mounting diagram ...

Page 4: ...A 1 4571 G SW 27 pmax 6 bar Ø 6 mm zkosený do Ø 4 mm viz rozměrový výkres hrdla délka HL 25 mm montážní délka EL 100 250 mm viz tabulka Provozní připojení Šroubovací objímka se závitem G Přípustná vzdušná vlhkost 95 r H bez kondenzujících par Třída ochrany III podle EN 60 730 Stupeň krytí IP 65 podle EN 60 529 THERMASGARD ETF 7 Šroubovací ponorné čidlo teploty s hrdlovou trubicí Typ WG01 Senzor Vý...

Page 5: ...řipojovací části se nachází v připojovací hlavici Standardní připojení ponorných čidel je pomocí G závitu pro kanálová čidla je připojení zajištěno montážní přírubou Pokud je jímkové čidlo umístěno v prodlužovací trubici je jeho teplotní rozsah obvykle poněkud větší jelikož stoupající teplo nemůže proudit přímo do připojovací hlavice Dbejte na to zejména při instalaci čidla U vestavěných senzorů j...

Page 6: ...hu mechanické a tepelné zatížení ochranných trubek podle DIN 43763 nebo podle zvláštních standardů S S Poznámky k procesnímu připojení vestavěných čidel Pokud je to možné vyberte snímač jehož ochranný plášt je z materiálu který nejvíce odpovídá materiálu potrubí nebo nádrže ve které bude instalován Maximální teploty Tmax a maximální tlaky pmax jsou následující pro mosaznou jímku TH ms je 150 C pma...

Page 7: ......

Page 8: ...m single tapered to Ø 4 mm see dimensional drawing length of neck tube HL 25 mm inserted length EL 100 250 mm see table Process connection screwed socket with G straight pipe thread Humidity 95 r H non precipitating air Protection class III according to EN 60 730 Protection type IP65 according to EN 60 529 Housing tested TÜV SÜD Report No 713139052 Tyr 1 THERMASGARD ETF 7 Screw in immersion temper...

Page 9: ...nguished into temperature sensors with interchangeable measuring insert and without interchangeable measuring insert Connection parts are placed inside a connecting head Standard process connection for immersion sensors is a pipe thread sizes in inches and a mounting flange for duct sensors However it may be designed differently When a built in sensor has a neck tube the application range is usual...

Page 10: ...Terms and Conditions for Business together with the General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry ZVEI conditions including supplementary clause Extended Retention of Title apply as the exclusive terms and conditions Notes regarding mechanical mounting and attachment Mounting shall take place while observing all relevant regulations and stand...

Page 11: ...zchybnou kvalitu zaručujeme v rámci našich Všeobecných obchodních podmínek Subject to errors and technical changes All statements and data herein represent our best knowledge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are used under a wide range of diff...

Page 12: ...461 1760 1625 4 3552 3817 3930 120 130 149 8 1498 1833 3676 4008 130 140 153 6 1536 1909 3802 4166 140 150 157 3 1573 1987 3929 4280 150 NTC 1 8 kOhm NTC 2 2 kOhm NTC 3 kOhm NTC 5 kOhm NTC 10 kOhm NTC 10 kPRE NTC 20 kOhm NTC 50 kOhm C Ω Ω Ω Ω Ω Ω Ω Ω C 50 50 40 39073 806800 2017000 40 30 22301 27886 53093 88488 175785 135200 413400 1033500 30 20 13196 16502 29125 48541 96597 78910 220600 551500 20...

Reviews: