11/2018 Subject to technical changes. 

domat R560 

All module settings are backed up in an EEPROM chip. The module is equipped with 
a watchdog circuit. 
 
See 

domat  -  Technical  application  notes

  for  connection  examples.  R560  is  a  more 

universal replacement of M550 (which has 8 inputs for passive sensors) and it can be 
used also as a replacement of M500 (8 voltage inputs) for most of the applications. 
Please note that the R560, unlike M500, has asymmetrical inputs (0 to 10 V rather 
than -10...10 V).  
____________________________________________________________________ 

Technical data 

Power 

10 V ÷ 35 V

 

DC, 14 V ÷ 24 V

 AC 

Consumption 

2,5 W 

Communication 

Galvanic isolation 

Max. bus length 

Max. amount of modules on the bus 

Modbus RTU RS485, 1200 ... 115200 bit/s 

1 kV 

1200 m 

256 

Number of analogue inputs 

Input ranges 

Pt1000* (-

50...150 °C), 20...1600 Ohm, 20...5000 Ohm, 

0...10 

V, 0...20 mA 

*Resistance ranges may be used for temperature 

measurement with Pt100, Pt1000, Ni1000/5000 and 

Ni100/6180 passive sensors. Linearisation must be done in 

controllers (Domat PLC… for example) just like at e.g.  MCIO2 

module. In the R560 module there is recalculation  to  

°C for 

the Pt1000 sensor only.

 

Sampling 

10 samples/s 

Effective resolution 

16 bit 

Measurement error 

The measurement deviation for all measured variables is 
0.25% of the whole range. 

Input impedance 

>10M

 

SW 

ModComTool 4.2.3.9 or higher parameters setting, GUI 

Merbon IDE, SoftPLC IDE 

 predefined modbus devices 

Housing 

Polycarbonate box (certification UL94V0) 

elbox 4 

Terminals 

screw terminals M3 (bus, power), M2 (AI inputs) 

Dimensions 

71 (l) x 90 (w) x 58 (h) mm 

Protection degree 

IP20 (EN 60529) 

Recommended wire  

0,14

1,5 mm

Ambient temperature 

External conditions: -5 

 45 

°C; 5 –

 95 % relative humidity; 

non-condensing  gases  and  chemically  non-aggressive 
conditions (according to EN 60721-3-3 climatic class 3K5) 

Storage:  -5 

  45 

°C;  5  –

  95 %  relative  humidity;  non-

condensing gases and chemically non-aggressive conditions 
(according to EN 60721-3-1 climatic class 1K3) 

 

 

 

 

Summary of Contents for R560

Page 1: ... to 20 mA current measurement inputs if the corresponding DIP switch is activated The module communicates by means of RS485 data bus The Modbus RTU communication protocol ensures smooth and easy integration in a variety of control and data acquisition systems It connects to process stations PLCs directly or through the M012 interface RS485 to RS232 converter with galvanic isolation Removable conne...

Page 2: ...may be used for temperature measurement with Pt100 Pt1000 Ni1000 5000 and Ni100 6180 passive sensors Linearisation must be done in controllers Domat PLC for example just like at e g MCIO2 module In the R560 module there is recalculation to C for the Pt1000 sensor only Sampling 10 samples s Effective resolution 16 bit Measurement error The measurement deviation for all measured variables is 0 25 of...

Page 3: ...dication RUN orange LED system cycle OK LED flashes periodically 1 s ON 1 s OFF ERROR LED flashes in other pattern LED is still ON or OFF TxD red LED RS485 transmitting data at COM1 flashing transmitting data OFF no data traffic PWR green LED power supply ON power OK OFF no power applied weak or damaged power supply DIP switches ADR AUTO if all switches are OFF the address is used according to Mod...

Page 4: ... to technical changes domat R560 0 20 mA For current measurement 0 20 mA on individual channels switch the particular DIP switch to ON The 0 20 mA range must be also set over Modbus e g using Domat ModComTool Connection ...

Page 5: ... 3 Addressing The Modbus address can be set as follows hardwarewise using DIP switches The switches increase their bit weight from right to left see image with example where address of 21 is set by activation of switches 4 6 and 8 with bit weight of 16 4 and 1 respectively Valid settable range is 1 to 254 Address 0 all switches OFF means that the address is set as entered in the Modbus table Addre...

Page 6: ...s set to 0 All changes apply after the module is switched off and on again Safety note The device is designed for monitoring and control of heating ventilation and air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks re...

Page 7: ...domat R560 11 2018 Subject to technical changes 7 Changes in versions 07 2017 First datasheet version 10 2017 Added measurement error value new image 02 2018 Added Safety note 11 2018 Minor changes ...

Reviews: