Standard Types

RN 5897.12/240/61 

DC 12 ... 24 V

Article number: 

0069124

•  Auxiliary voltage: 

DC 12 ... 24 V

RN 5897.12/240/61 

AC/DC 24 … 60 V

Article number: 

0069123

•  Auxiliary voltage: 

AC/DC 24 … 60 V

RN 5897.12/240/61 

AC/DC 85 … 230 V

Article number: 

0069125

•  Auxiliary voltage: 

AC/DC 85 … 230 V

•  Outputs: 

1 changeover contact for device fault 

   

1 changeover contact for alarm

•  Setting range alarm: 

1 k

Ω

 … 500 k

Ω

•  With connection facility of a coupling device RL 5898 or RP 5898
•  Max. line capacitance:  

5 µF

•  Energized or de-energized on trip
•  Selection of type of network
•  Width: 

52.5 mm

Ordering Example for variants

RN 5897  .12  /020  /61  AC/DC 24 … 60 V  1 k

Ω

 - 100 k

Ω

  20 k

Ω

 - 500 M

Ω

  

 
 

Setting range Pre-warning

 

Setting range alarm

 

Auxiliary voltage

 

UL approval

 

Variant, if required

 

Contacts

 

Type

Switching capacity

To AC 15

NO contact: 

3 A / AC 230 V

NC contact: 

1 A / AC 230 V

nfo

Technical data that is not stated in the CCC-Data, can be found 

in the technical data section.

CCC-Data

Technical Data

Vibration and 
shock resistance: 

Category 1, Class B 

IEC/EN 61373

Ambient temperature:

 

OT1, OT2 compliant

Protective coating of the PCB:

 No

Classification to DIN EN 50155

Wire connection 

 

DIN 46228-1/-2/-3/-4

Cross section:  

0.5 ... 4 mm² (AWG 20 - 10) solid or

 

0.5 ... 4 mm² (AWG 20 - 10)

 

stranded wire without ferrules

 

0.5 ... 2.5 mm² (AWG 20 - 10)

 

stranded wire with ferrules 

Stripping length:  

6.5 mm 

Wire fixing: 

 

Cross-head screw / M3 box terminals

Fixing torque: 

 

0.5 Nm 

Mounting:

 

DIN rail 

 

IEC/EN 60715

Weight:

 

Approx. 205 g

Dimensions

  

Width x height x depth:

 

52.2 x 90 x 71 mm

Meas. ciruit L1(+)/L2(-) to PE1/PE2 (with coupling device RL / RP 5898)

RL 5898

RP 5898

Max. voltage range U

N

:

AC 0 ... 400 V

AC 0 ... 600 V

DC 0 ... 500 V

DC 0 ... 600 V

Output voltage at
L(+)/L(-), VSG1/VSG2: 

Max. AC / DC 230 V

Temperature range

 

Operation: 

- 30 ... + 60 °C

Switching capacity: 

Pilot duty C300, R300

   

5A 250Vac

   

2A 30Vdc

Wire connection:  

60 °C / 75 °C copper conductors only

   

Torque 0.5 Nm

Test specification: 

 

ANSI/UL 60947-1, 5

th

 Edition 

ANSI/UL 60947-5-1, 3

rd

 Edition 

CAN/CSA-C22.2 No. 60947-1-13,  
2

nd

 Edition 

CAN/CSA-C22.2 No. 60947-5-1-14,  
1

st

 Edition

nfo

Technical data that is not stated in the UL-Data, can be found

in the technical data section.

UL-Data

Summary of Contents for VARIMETER IMD RN 5897/240

Page 1: ...l control input for combined test reset button with additional stop of the measuring function With semiconductor output to indicate the insulation resistance PWM 3 wide voltage input for auxiliary vol...

Page 2: ...oes not take place see internal resistance Broken wire detection As described in section Measuring circut the measuring circuits L 1 L2 and the protective conductors PE1 PE2 are constantly monitored f...

Page 3: ...wire detection in the measuring circuit is de activated Thethirdrotationalswitchselects UN selectsthevoltagesystemconnection and manual or auto reset it has also 2 sections In section one the unit is...

Page 4: ...n conjunction with the RP5897 240 on a voltage system and not just by itself Attention Before checking insulation and voltage disconnect the monitoring device RN 5897 240 from the power source In one...

Page 5: ...resistance 10 gn 11 ms 3 pulses IEC EN 60068 2 27 Climate resistance 40 070 04 IEC EN 60068 1 Terminal designation EN 50005 Meas ciruit L1 L2 to PE1 PE2 with coupling device RL RP 5898 RL 5898 RP 5898...

Page 6: ...Data Vibration and shock resistance Category 1 Class B IEC EN 61373 Ambient temperature OT1 OT2 compliant Protective coating of the PCB No Classification to DIN EN 50155 Wire connection DIN 46228 1 2...

Page 7: ...61 Article number 0068315 Coupling device for RN 5897 12 240 Extension of nominal voltage range UN to DC 500 V AC 400 V Weight Approx 60 g Dimensions Width x height x depth 35 x 90 x 71 mm RP 5898 61...

Page 8: ...299 2 A1 A2 UH 1 L1 L2 L3 UN L1 L2 Setting of type of network AC RL5898 RP5898 Ungrounded mains RL5898 3 AC 0 440V 40 1000Hz RP5898 3 AC 0 760V 40 1000Hz Y1 Y2 VSG1 VSG1 L L L L PE RN5897 240 X1 Exter...

Reviews: