DOLD VARIMETER IMD RN 5897/240 Translation Of The Original Instructions Download Page 4

4

17.03.21 en / 371A

Indicators

Indicators

The operational status of the device is indicated on a 3-colour LED:

Off:

 

   

No auxiliary voltage connected

Green:

     

Normal operation (Insulation resistance in healthy 

                                 state)

Red:

 

   

Alarm (measured value below alarm response value)

Orange flashing: 

Test mode / Measurement stopped procedure 

                                 (see flashing code diagramm)

Red flashing: 

Failure code (see flashing code diagramm)

Flash code 

orange 

Status-LED

Description

1

Selftest

(measuring circuit, measuring voltage, 

internal tests)

2

Advanced Test

(additional control of indicator relays)

Continously

flashing

Measuring function stopped

Error Indication

Flash code 

red 

Status-LED

Failure cause

Failure recovery

1

Broken wire detection 

on L(+)/L(-).

Check measuring circuit 

L(+) and L (-)

2

Broken wire detection 

on PE1/PE2.

Check protective earth

connections 

PE1 and PE2 

3

Parameter failure

Check position of the rotary 

switches and avoid undefined 

setting positions.

Continously

flashing

Internal failure 

detected in 

test mode

Press test button again or restart 

the unit by interrupting the 

auxiliary supply temporarily. If the 

fault remains permanent, send 

device back to manufacturer for 

examination.

Continously

flashing

Faulty calibration 

values detected in 

device memory.

Send device back to manufacturer 

for recalobration and examination.

Notes

WARNING

  Risk of electrocution! 

      Danger to life or risk of serious injuries. 

•  Disconnect the system and device from the power supply and ensure  
  they remain disconnected during electrical installation.
•  Determine voltage free status by using appropriate instruments
•  The terminals of the control input X1-X2 have no galvanic separation 

to the measuring circuit L1(+) and L2(-) and are electrically connected 
together, therefore they have to be controlled by volt free contacts or 
bridge. These contacts ore bridges must provide a sufficient separation 
depending on the mains voltage on L1(+)-L2(-).

•  Please do not connect external voltage to terminals X1/X2. The control 

must only be made by bridging X1 and X2.

•  The coupling unit RL 5898 or RP 5898 must only be used in conjunction 

with the RP5897/240 on a voltage system and not just by itself.

!

 Attention! 

    

•  Before checking insulation and voltage, disconnect the monitoring device  

  RN 5897/240 from the power source!

•  In one voltage system only one insulation monitor can be used. This has  

  to be observed when interconnecting two separate systems..
•  Device terminals PE1 and PE2 must always be connected via separate  
  lines to different terminal points of the protective-conductor system.
•  The device must not be operated without PE1/PE2 connection!

nfo

 Attention! 

    

•  The main measuring circuit can be connected with its terminals L1(+) and 

L2(-) both to the DC and also AC side of a mixed network; it is done most 
practically where the primary incoming power supply takes place e.g. 
with battery networks with connected inverters on the DC side, with 
Generators/Transformers with connected Rectifiers or inverters on 
the AC-side. To monitor a 3NAC system the device can be connected 
single pole, (L(+) and L(-) are bridged, to the neutral of the 3p4w sy-
stem. The 3 phases have a low-

Ω

ic (approx. 3 – 5 

Ω

) connection via 

the transformer windings so also insulation failures of the not directly 
connected phases are detected. Via the rotary switch "UN" the correct 
type of network needs to be selected (see „Connection Examples“).

•  If a monitored AC system includes galvanically connected DC circuits 

(e.g. via a rectifier), an insulation failure on the DC side can only be 
detected correctly, when a current of min 10 mA can flow via the semi-
conductor connections.

•  If a monitored DC system includes galvanically connected AC circuits 

(e.g. via an inverter), an insulation failure on the AC side can only be 
detected correctly, when a current of min 10 mA can flow via the semi-
conductor connections.

•  The insulation monitor RN 5897/240 can only be used together with a 

coupling device.

•  If the insulation monitor RN 5897/240 is used in an application according 

to EN 61851-23 annex CC, the insulation resistance value has to be read 

and evaluated by the supervising PLC, in order to generate a warning 

according EN 61851-23 annex CC, when the resistance drops below 

500 Ohms/V.

Connection

coupling device

Auxiliary

voltage

Semiconductor

output

M12289_a

Indicator relay

alarm and system error

Protective
conductor

External

control input

Summary of Contents for VARIMETER IMD RN 5897/240

Page 1: ...l control input for combined test reset button with additional stop of the measuring function With semiconductor output to indicate the insulation resistance PWM 3 wide voltage input for auxiliary vol...

Page 2: ...oes not take place see internal resistance Broken wire detection As described in section Measuring circut the measuring circuits L 1 L2 and the protective conductors PE1 PE2 are constantly monitored f...

Page 3: ...wire detection in the measuring circuit is de activated Thethirdrotationalswitchselects UN selectsthevoltagesystemconnection and manual or auto reset it has also 2 sections In section one the unit is...

Page 4: ...n conjunction with the RP5897 240 on a voltage system and not just by itself Attention Before checking insulation and voltage disconnect the monitoring device RN 5897 240 from the power source In one...

Page 5: ...resistance 10 gn 11 ms 3 pulses IEC EN 60068 2 27 Climate resistance 40 070 04 IEC EN 60068 1 Terminal designation EN 50005 Meas ciruit L1 L2 to PE1 PE2 with coupling device RL RP 5898 RL 5898 RP 5898...

Page 6: ...Data Vibration and shock resistance Category 1 Class B IEC EN 61373 Ambient temperature OT1 OT2 compliant Protective coating of the PCB No Classification to DIN EN 50155 Wire connection DIN 46228 1 2...

Page 7: ...61 Article number 0068315 Coupling device for RN 5897 12 240 Extension of nominal voltage range UN to DC 500 V AC 400 V Weight Approx 60 g Dimensions Width x height x depth 35 x 90 x 71 mm RP 5898 61...

Page 8: ...299 2 A1 A2 UH 1 L1 L2 L3 UN L1 L2 Setting of type of network AC RL5898 RP5898 Ungrounded mains RL5898 3 AC 0 440V 40 1000Hz RP5898 3 AC 0 760V 40 1000Hz Y1 Y2 VSG1 VSG1 L L L L PE RN5897 240 X1 Exter...