DOLD VARIMETER IMD RN 5897/240 Translation Of The Original Instructions Download Page 2

2

17.03.21 en / 371A

The device is supplied with DC auxiliary voltage via terminals A1(+) / A2. 
Switching on the auxiliary voltage (Power-On) is followed by an internal 
self-test for 10 s (see „Device test functions“). The test process is visible 
with the status LED. After this, measurement of the insulation resistance 
in the measuring circuits begins and the status LED changes into green.

Measuring circuit 
(Insulation measurement between terminals L1(+) / L2(-) on the 
coupling device and PE1/PE2 on the insulation monitor)

The insulation monitor RN 5897/240 can only be used with a coupling 
device. Max. mains voltage and connection diagrams have to be observed!

To connect the insulation Monitor RN5897/240 to a coupling device the 

terminals with identical designations are connected (VSG1, VSG2, L(+), 

L(-)) .The votage system to be monitored is connected to L1(+) und L2(-)  
of the coupling device.
A broken wire detection that can be disabled provides a fault signal if 
both terminals L1(+) and L2(-) are not linked by the connected network.

Broken wire between coupling device and insulation monitor cannot be 

directly detected but the the measured value of the insulation resistance 

when one or more connections are interrupted, is much lower then the real 

insulation value which will cause a tripping of the alarm relays. 

The type of the voltage system or the connection method (AC, DC, 3NAC) 
has to be correctly adjusted on the rotational switch "UN" 
Also the terminals PE1 and PE2 have to be connected with 2 separate 
wires to the protective earth. An interruption of a wire also causes a fault 
signal (see section ”Behavior on faulty connection”). The monitoring of 
the PE connection cannot be de-activated.
To measure the insulation resistance an active measuring voltage with 
changing polarity is connected between L1(+) and L2(-) and PE1/PE2.
The duration of the positive and negative measuring phase depends on 
the actual leakage capacity of the monitored system and in DC systems 
also on the level and duration of possible voltage variations. This allows 
a correct and fast measurement in different network conditions.
At the end of a measuring cycle the actual insulation resistance is produced 
and indicated. The relay for alarm K1 switch when dropping under the 
adjusted response value. In addition the status LED lights up red on alarm. 

Manual reset of fault message

With the 2-section rotational switch "UN",  manual or auto reset of the alarm 
can be selected. If manual reset is activated the insulation fault signal of 
the measuring circuit is stored when dropping under the adjusted response 
value also if the insulation resistance goes back to healthy state. Pressing 
the „Reset“ button on the front side for 2 s, the alarm signal is reset if the 
actual insulation resistance is in healthy state.

Indicator relay for insulation fault and device failure

The function of the relays K1 (contacts 11-12-14 for alarm) and K2 
(contacts 21-22-24) can be altered between energised on trip (relay n.o.) 
or de-energized on trip (relay n.c.). When energised on trip the relays 
energize when the value drops below the setting or at decive failure, when 
de-energised on trip, the relays de-energize when the value drops below 
the setting or at device failure.

Semiconductor output to indicate the insulation resistance

On terminals Y1(+)/Y2 a galvanically separated semiconductor output is 
available as PWM (Pulse width modulated) signal that shows the actual 
insulation resistance. It is an opto-coupler output with open collector. 
This means that an external circuit is required (ext. supply voltage and 
pull up/down resistor).

Disable the measuring function

Using the external control input X1/X2 the measuring function of the    
RN 5897/240 can be disabled. This could be used when several isolated 
voltage systems with individual insulation monitors need to be coupled.
The measuring voltage is set to -90V (negative measuring phase) and 
the evaluation of the measurement is stopped. The status of the output 
relays is frozen and not changed any more. If the measurement is disabled 
the status LED flashes continuously orange. Please be aware, only the 
evaluation of the measurement is stopped and the measuring pulse is 
interrupted! A high resistive disconnection to PE does not take place 
(see internal resistance).

Broken wire detection

As described in section "Measuring circut", the measuring circuits L(1+)/
L2(-) and the protective conductors PE1/PE2 are constantly monitored for 
wire breaks – not only at Power-On or a manual or occasional automatic 
test. The response time of PE1/PE2 monitoring is only a few seconds. 
The response time of monitoring of L1(+)/L2(-) can be up to approx. 
2 min. Broken wire detection between L1(+) and L2(-) is performed via 
coupled alternating voltage. This alternating voltage is short-circuited if 
the terminals are connected to the connected mains at low-resistance. 
The device detects that the mains to be monitored is properly connected.
Since this broken wire detection is carried out with alternating voltage, large
capacitances should be avoided between L1(+) and L2(-), since the 
capacitive reactance of these capacitances also short-circuits this 
alternating voltage. The device would no longer detect a connection fault 
on L1(+)/L2(-).
Especially parallel lines should be prevented over larger distances.
If larger capacitances between L1(+)/L2(-) cannot be avoided or if the coupled
alternating voltage interferes with the system, the broken wire detection can 
be de-activated on the 2-section rotational switch "Rel." It can be altered 
between continuously disabled (Broken Wire Detect OFF), or continuously 
enabled (Broken Wire Detect ON) for 10 seconds every 2 minutes. If the 
broken wire detection on L1(+)/L2(-) is de-activated no AC voltage is injected.  
The broken wire detection on PE1/PE2 cannot be de-activated.

Device test functions

Principally, 2 different test functions are implemented: The "self-test" and
the "expanded test":
The self-test of the device is performed automatically after Power-On and
every full operating hours. It can also be triggered manually at any time by
pressing the "Test" button at the device front for 2 s.
With the self-test, contrary to the expanded test, the status of the Indicator
relays is not affected; the sequence is as follows:

The self test is indicated by the status LED with flash code 1 in orange 

colour. First the negative measuring pules is activated for about 4 s and the 

internal measuring circuit is checked on failures. then the positive measuring 

pulse is activated for about 4 s and more internal tests are performed. If no 

failures are detected, the normal measurement continuous. The extended 

test is started, when during or at the end of above procedure the button 

"Test" is pressed again for 2 s. 

The procedure is the same as above (2 measuring phases with 4 sec each) 

but in addition the output relays K1 and K2 go into alarm state and the PWM 

on the semiconductor output drops to the lowest value. The Status LED 

shows flash code 2 in orange colour. The test phases will be continuously 

repeated. pressing the button "Test" for 2 s will end the extended test 
immediately. the device starts the again the insulation measurement.

Behaviour with internal device faults

If internal device faults were detected during the test function, the status LED 
flashes permanently  red. The indicator relay K2 switch to the alarm state.

Behavior on faulty connection

When detecting broken wire on terminals L1(+)/L2(-), the measurement is 
disabled. The reaction time could be up to 2 min. The monitoring relay K2 
goes in alarm state, the status LED shows flash code 1 in red colour. After 
removing the interruption the fault is automatically reset (max. reaction time 
up to 2 min) and the measurement of the insulation resistance is continued. 
Stored alarm values remain stored. An interruption of the protective earth 
connections PE1/PE2 causes the same reaction as interrupting the 
measuring circuit, only the status LED shows flash code 2 in red colour.

Behaviour at parameter failures 

With wrong settings on the rotary switches the device goes to failure mode. 
The indicator relay K2 changes to alarm state and the status LED shows 
the red flash code 3.

External control input

To terminals X1/X2 an external combined Test-/Reset button can be 
connected. If the terminals X1/X2 are bridged for approx. > 1,5 s and < 
10 s the test mode is started. This has the same function as pressing the 
internal test button. When bridging X1/X2 for < 1,5 s, a stored alarm will 
be reset. This has the same function as pressing the internal reset button.
If X1/X2 is activated for  > 10 s, the measuring function is stopped.
The measuring function remains suspended for the duration of the control 
of X1/X2.

Function

Function

Summary of Contents for VARIMETER IMD RN 5897/240

Page 1: ...l control input for combined test reset button with additional stop of the measuring function With semiconductor output to indicate the insulation resistance PWM 3 wide voltage input for auxiliary vol...

Page 2: ...oes not take place see internal resistance Broken wire detection As described in section Measuring circut the measuring circuits L 1 L2 and the protective conductors PE1 PE2 are constantly monitored f...

Page 3: ...wire detection in the measuring circuit is de activated Thethirdrotationalswitchselects UN selectsthevoltagesystemconnection and manual or auto reset it has also 2 sections In section one the unit is...

Page 4: ...n conjunction with the RP5897 240 on a voltage system and not just by itself Attention Before checking insulation and voltage disconnect the monitoring device RN 5897 240 from the power source In one...

Page 5: ...resistance 10 gn 11 ms 3 pulses IEC EN 60068 2 27 Climate resistance 40 070 04 IEC EN 60068 1 Terminal designation EN 50005 Meas ciruit L1 L2 to PE1 PE2 with coupling device RL RP 5898 RL 5898 RP 5898...

Page 6: ...Data Vibration and shock resistance Category 1 Class B IEC EN 61373 Ambient temperature OT1 OT2 compliant Protective coating of the PCB No Classification to DIN EN 50155 Wire connection DIN 46228 1 2...

Page 7: ...61 Article number 0068315 Coupling device for RN 5897 12 240 Extension of nominal voltage range UN to DC 500 V AC 400 V Weight Approx 60 g Dimensions Width x height x depth 35 x 90 x 71 mm RP 5898 61...

Page 8: ...299 2 A1 A2 UH 1 L1 L2 L3 UN L1 L2 Setting of type of network AC RL5898 RP5898 Ungrounded mains RL5898 3 AC 0 440V 40 1000Hz RP5898 3 AC 0 760V 40 1000Hz Y1 Y2 VSG1 VSG1 L L L L PE RN5897 240 X1 Exter...

Reviews: