4
LG 5929 / 121113 / 284
Technical Data
Technical Data
Input
Nominal voltage U
N
:
AC / DC 24 V, AC / DC 110 / 115 V,
AC 110 / 115 V, AC 230 / 240 V*
)
*
)
see device label
Voltage range:
AC 0.85 ... 1.1 U
N
at 10% residual ripple:
DC 0.9 ... 1.1 U
N
at 48% residual ripple:
DC 0.85 ... 1.1 U
N
Nominal consumption at U
N
AC / DC 24 V:
1.8 VA
AC / DC 110/115 V:
2.0 VA
AC 110/115 V, 230/240 V:
3.0 VA
Nominal frequency:
50 / 60 Hz
Control current:
at 24 V over 2 relays:
75 mA
Output
Contacts
LG 5929.60,LG 5929.60/100: 5 NO contacts,
1 NC contact for feed back circuit
LG 5929.54,LG 5929.54/100: 4 NO contacts, 1 NC contact
1 NC contact for feed back circuit
Operate time:
max. 20 ms
release time:
max. 35 ms
Contact type:
relay, forcibly guided
Nominal output voltage:
AC 250 V
Thermal current I
th
:
see total current limit curve*
)
max. 5 A
*
)
see datasheet LG 5929 on
www.dold.com
Switching capacity
to AC 15:
NO contact:
3 A / AC 230 V
IEC/EN 60 947-5-1
NC contact:
2 A / AC 230 V
IEC/EN 60 947-5-1
to DC 13:
NO contact:
2 A / DC 24 V
IEC/EN 60 947-5-1
NC contact:
2 A / DC 24 V
IEC/EN 60 947-5-1
to DC 13:
NO contact:
4 A / 24 V at 0.1 Hz IEC/EN 60 947-5-1
NC contact:
4 A / 24 V at 0.1 Hz IEC/EN 60 947-5-1
Electrical life
to AC 15 at 2 A, AC 230 V:
10
5
switching cycles IEC/EN 60 947-5-1
Permissible switching
capacity:
1200 switching cycles / h
Short circuit strength
max. fuse rating:
10 A gL
IEC/EN 60 947-5-1
max. line circuit breaker:
B 6 A
General Data
Operating mode:
Continuous operation
Temperature range
operation:
- 15 ... + 55 °C
storage :
- 25 ... + 85
°
C
altitude:
< 2.000 m
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
4 kV / 2 (basis insulation) IEC 60 664-1
EmC
Electrostatic discharge:
8 kV (air)
IEC/EN 61 000-4-2
HF-irradiation:
10 V / m
IEC/EN 61 000-4-3
HF-wire guided:
10 V
IEC/EN 61 000-4-6
Fast transients:
4 kV
IEC/EN 61 000-4-4
Surge voltages
between
wires for power supply:
1 kV
IEC/EN 61 000-4-5
0.5 kV
IEC/EN 61 000-4-5
at AC/DC 24 V
between wire and ground:
4 kV
IEC/EN 61 000-4-5
Interference suppression:
Limit value class B
EN 55 011
Degree of protection
Housing:
IP 40
IEC/EN 60 529
Terminals:
IP 20
IEC/EN 60 529
Housing:
Thermoplast with V0 behaviour
according to UL subject 94
Vibration resistance:
Amplitude 0.35 mm IEC/EN 60 068-2-6
frequency 10 ... 55 Hz
Climate resistance:
15 / 055 / 04
IEC/EN 60 068-1
Terminal designation:
EN 50 005
Wire fixing:
Plus-minus terminal screws M 3.5
box terminals with wire protection or
cage clamp terminals
mounting:
DIN rail
IEC/EN 60 715
Weight:
205 g
Troubleshooting
Failure
Potential cause
LED "K1/K2" does not light up
Power supply not connected
maintenance and repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
UL-Data
The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, “general use
applications”
Switching capacity:
Ambient temperature 45°C:
Pilot duty B300
5A 250Vac G.P.
5A 24Vdc
Ambient temperature 55°C:
Pilot duty B300
4A 250Vac G.P.
4A 24Vdc
Wire connection:
60°C / 75°C copper conductors only
Fixed screw terminal:
AWG 20 - 12 Sol/Str Torque 0.8 Nm
Plug in screw terminal:
AWG 20 - 14 Sol Torque 0.8 Nm
AWG 20 - 16 Str Torque 0.8 Nm
Plug in cage clamp terminal:
AWG 20 - 12 Sol/Str
nfo
Technical data that is not stated here, can be found in the
general technical data.
LG 5929._ _ /100:
for 2-channel connection, with 2 LEDs
Variants
Summary of Contents for Safemaster LG 5929