22
UG 6960 / 05.12.17 en / 947
UG 6960 .04 _ _ / _ _ _ /61 DC 24 V 300 s
max. time range or fixed time
Nominal voltage
UL-approval
Time delay
0 = adjustable
1 = fixed
Delay function
0 = adjustable
Safety function
1 = e-stop,
with cross fault detection
2 = safety gate,
with cross fault detection
3 = two-hand control,
with cross fault detection
4 = safety mat / Safety edge,
with cross fault detection
5 = Exclusive or contacts,
with cross fault detection
6 = e-stop,
without cross fault detection
7 = safety gate,
without cross fault detection
8 = light curtain,
without cross fault detection
Type of terminals
PC (plug in cage clamp):
pluggable terminal blocks,
with cage clamp terminals
PS (plug in screw):
pluggable terminal blocks,
with screw terminals
PT (plug in Twin cage clamp):
pluggable terminal blocks,
with cage clamp terminals 2-wire
Contacts
Type
Variants
Failure
Potential cause
LED "ON" does not light up
- Power supply A1+/A2
not connected
LED "ERR" flashes
in relation 1:1
- Under- or overvoltage
(check power supply A1+/A2)
LED "ERR" flashes
in relation 4:1
- external failure (see flashing code)
LED "ERR"
continuously on
- system error
(if cannot be removed after restart
unit must be replaced)
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
Maintenance and Repairs
Troubleshooting
UG 6960.04PS/100/61 DC24V 300 s
Article number:
0065424
• Safety function:
e-stop
• Delay function:
adjustable
• Time delay:
adjustable
• Output:
2 NO contacts instantaneous contacts
2 NO contacts delayed contacts
• Nominal voltage:
DC 24 V
• Width:
22.5 mm
The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, “general use
applications”
Ambient temperature:
-15 … +55°C
Switching capacity:
Ambient temperature 55°C
Pilot duty B300, Q300
5A 250Vac Resistive or G.P.
5A 24Vdc Resistive
Ambient temperature 40°C:
Pilot duty B300, Q300
8A 250Vac Resistive or G.P.
8A 24Vdc G.P.
Wire connection::
60°C / 75°C copper conductors only
PS-terminal:
AWG 28 - 12 Sol/Str Torque 0.5 Nm
PC-terminal:
AWG 24 - 12 Sol/Str
PT-terminal:
AWG 24 - 16 Sol/str
nfo
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
UL-Data
Standard Type
Summary of Contents for SAFEMASTER C UG 6960
Page 4: ...4 UG 6960 05 12 17 de 947...
Page 16: ...16 UG 6960 05 12 17 en 947...
Page 28: ...28 UG 6960 05 12 17 fr 947...