Short circuits between the Dupline signal conductors and the earth potential lead to
disturbances and have to be avoided. The correct polarity of the Dupline signal has
to be observed.

4. On insertion it must be observed, that the orientation of the PCB is so, that the 5-

pin terminal (C) runs into the five wholes of the base PCB (counted from center to
border). Please see also chapter 19 “Anschlussschema / Connection Diagram”.

5. Put the smoke detector into the base and lock it by slightly turning it clockwise.

14. Test Button / LED Indicator

With the test button which includes also the LED indicator, the test alarm can be re-
leased. After pressing the test button it will take approx. 11 s until the alarm signal will be
sent pulsing every 1.25 s via Dupline when using the smoke alarm object in ProLine. The
alarm siren responses with the same cycle time. The response time when detecting fire
approx. is 21 s.
Doing so, the internal operating readiness is signalled by the LED and the readiness on
the Dupline bus by switching the adjusted channel.
The LED indicates the condition of the device:

15. Safety Instructions

• The smoke detector must not be painted.

• Smoke detectors do not extinguish fires. If an alarm occurs, the source of the fire

must be located and, if necessary, the fire brigade alerted.

• The DRD 3 responds to the smoke of a fire, not to the flame itself.

• The smoke detector only monitors a defined area in its vicinity and will not neces-

sarily monitor another room or another floor (see also chapter 13.1 “Choice of
Mounting Location” on page 8). Therefor install a sufficient number of smoke detec-
tors to ensure optimum protection.

• The DRD 3 is a smoke detector designed for the Dupline bus system and thus not

equipped with an acoustic alarm. The alarm indication is carried out via the Dupline
bus. How the smoke detectors are integrated into Dupline is described in the ProLi-
ne respectively ProLine

NG

 manuals. They are available for free download on our ho-

mepage http://www.doepke.de/uk.

16. Maintenance and Care

To ensure proper functioning of the DRD 3, please pay attention to the following points:

• Monthly test the function by pressing the test button. The alarm must be indicated

at the device (short blinking of the LED in 1.25-s-pulses) as well as on the  Dupline

Indicator

Description

Red LED

Short blinking approx. one time every 50 s (life signal):
Device is functioning.
Short blinking approx. one time every second: Alarm

Summary of Contents for Dupline DRD 3

Page 1: ...3931271 2016 04 K Doepke Dupline Rauchmelder DRD 3 DRD 3 Smoke Detector Bedienungsanleitung Operating Instructions...

Page 2: ...doepke de 2 3931271 2016 04 K Technische nderungen vorbehalten Doepke Inhaltsverzeichnis 1 Allgemeines 3 2 Wichtige Hinweise vorab 3 3 Kodierung 3 4 Montage 4 5 Pr ftaste LED Anzeige 5 6 Sicherheitshi...

Page 3: ...on darf nur von einer autorisierten Fachkraft vorgenommen werden Die Dupline Signalversorgung muss aus Quellen erfolgen die den Anforderungen f r Schutzkleinspannung entsprechen ebenso wie die Install...

Page 4: ...klung m glich 4 2 Ungeeignete Montageorte Montieren Sie den Brandmelder nicht in der N he von L ftungsleitungen und starker Zugluft nicht direkt in der Dachspitze Abstand von 50 cm zur Dachspitze einh...

Page 5: ...rf nicht mit Farbe berstrichen werden Rauchmelder l schen keinen Brand Bei Alarm ist der Brandherd aufzusuchen und gegebenenfalls die Feuerwehr zu alarmieren Der DRD 3 erkennt den Rauch eines Brandes...

Page 6: ...tigungs und Materialfehlern die innerhalb der Gew hrleistungsfrist erkannt werden leistet unser Werk kostenlosen Ersatz Bei ffnen der Messkammer erlischt der Garantieanspruch 9 Technische Daten Min Ty...

Page 7: ...be carried out by an authorised technician The Dupline signal supply has to be delivered by sources which have to be installed in accordance with the regulations governing protective low voltage see...

Page 8: ...nd the bath here false alarms are possible due to steam development 13 2 Unsuitable Locations Never install the smoke detector near to ventilation ducting or strong draughts directly in the apex of pi...

Page 9: ...of the device 15 Safety Instructions The smoke detector must not be painted Smoke detectors do not extinguish fires If an alarm occurs the source of the fire must be located and if necessary the fire...

Page 10: ...in the guar antee period the company will provide a replacement free of charge The guarantee will be rendered null and void if the sensing chamber is opened or the device is tampered with 18 Technical...

Page 11: ...3931271 2016 04 K The right to make technical changes reserved 11 Doepke Zeichnungen Drawings 19 Anschlussschema Connection Diagram...

Page 12: ...12 3931271 2016 04 K The right to make technical changes reserved Doepke Zeichnungen Drawings...

Reviews: