background image

Recommendations for the power supply of audio systems in conjunction with the 
DFS F Audio, with a view to improving sound:

The  following  recommendations  must  only  be  implemented  by  an  authorised  and 
qualified electrical specialist, who is familiar with the applicable national installation 
regulations. The recommendations exclusively refer to the circuit for connecting an 
audio system. Priority should always be given to ensuring that electrical installations 
are correctly implemented in line with the applicable installation regulations, over 
any sound objectives.

 

»

Use  an  outer  conductor  (L1,  L2  or  L3)  that  is  used  by  as  few  other  electrical 
consumers (e.g. lights or household appliances) as possible.

 

»

If possible, use a separate installation cable from the distribution installation 

to  the  installation  socket  to  which  the  audio  system  is  connected.  No  further 

electrical consumers should be connected to this circuit. 

 

»

When using multiple residual current circuit-breakers in a distribution installation, 

the DFS F Audio should be connected on the input side, if possible directly, to the 

connection cables from the meter board. Further residual current circuit-breakers 
can then be connected on the input side, e.g. with suitable busbars.

 

»

Connect  the  phase  conductor  to  which  your  audio  system  is  connected  to  the 
output side (load side) of the DFS F Audio via a suitable overcurrent protective 

device.

 

»

Through use of a busbar fork, it is also possible to connect to the upper wiring level 
for the DFS F Audio. This refines the sound image somewhat but does reduce the 

volume a little.

 

»

When connecting the neutral conductor to which your audio system is connected, 
avoid having a lot of terminal positions in the neutral conductor path. If necessary, 
it is possible to connect the neutral conductor directly to the neutral conductor 
pole  terminal  on  the  output  side  (load  side)  of  the  DFS  F  Audio  instead  of  to 
the  neutral  conductor  rail  on  the  distribution  board.  This  adds  volume  and 
authenticity to the audio image without losing precision.

 

»

If the installation cable to your audio system in the distribution installation needs 
to be extended or connected to installation terminals, avoid using ferromagnetic 
materials  (e.g.  copper-covered  steel)  as  direct  live  parts.  However,  parts  that 
are  not  directly  conductive  that  are  used  to  mechanically  secure  electrical 

conductors, e.g. clamping screws made from ferromagnetic material, have no 

adverse effect on sound.

Hints:

 

»

The  audio  image  may  initially  seem  rather  unsettled  following  installation  and 
wiring  work  on  the  distribution  board.  This  will  subside  after  a  few  operating 

hours.

 

»

In comparison to standard residual current circuit-breakers, the DFS F Audio 
provides a stable and clear audio image, without lessening the volume or 

musicality. The sound is, however, affected by many factors relating to an audio 
system’s power supply and, of course, by the components in an audio system and 
can therefore vary. 

 

»

If mains filters are in place at the output side (load side) of the DFS F Audio, in 
many cases, depending on the type of filter, it may be necessary to disconnect 
them from the mains if the audio image is clearly defined but too thin.

Break-in time of the DFS F Audio:

 

»

Immediately  after  it  is  first  commissioned,  the  audio  image  can  seem  more 
lightweight, particularly in the low range.

 

»

After around two to three operating hours, the audio image increasingly gains 

in volume.

 

»

The full potential of the sound is achieved after around 50–100 operating hours. 
An audio system does not necessarily have to be active during this time.

 

»

The residual current protection function of the DFS F Audio is of course available 
immediately after installation and at all times.

Wiring diagrams

1 3

2 4

 

N

3

5

7

N

4

6

8

1

3

5

N

2

4

6

N

 

S

two-pole

 

S

four-pole,  
neutral conductor on 
the left

 

S

four-pole,  
neutral conductor on 
the right

Installation and operating instructions

for two-/four-pole residual current circuit-breakers 
in the DFS F Audio series

These  installation  and  operating  instructions  are  aimed  at  qualified 
electrical  specialists.  The  installation  of  devices  of  this  type  is  not 
appropriate for electrical laypersons due to the considerable potential 
dangers.  These  installation  and  operating  instructions  must  be 
retained, so that they can be referred to at a later stage. The operator 

of the electrical installation must be informed about the use and 
function of this protective device.

Application instructions and warnings

The following notes and warnings must be observed in order to ensure safe operation:

1. 

Devices with visible damage must not be installed or used.

2.  Operation must only occur under normal ambient conditions free of corrosive 

gases in order to preserve the correct tripping function in the long term. 

Corrosive gases are chlorine, ammonia and sulphurous air, for example. 

 

3.  The user must be made aware of regular function testing using the test key T.
4.  The function test with the test key is not a substitute for regular testing of the 

electrical system.

5. 

Erroneous tripping due to operation related leakage currents or atmospheric 

interference cannot be ruled out with absolute certainty. The consequences must 
be considered and countermeasures taken where necessary.

6. 

If the RCCB cannot be switched on, or if the consumer network is not connected, 
the device must be replaced.

7.  Disposal is subject to the statutory regulations of the European Union (waste of 

electrical and electronic equipment (WEEE)).

Further information and product data sheets can be found at www.doepke.de.

Intended use:

DFS  2  and  DFS  4  series  protective  devices  are  residual  current  circuit-breakers 
without  integrated  overcurrent  protection.  They  provide  protection  through 
automatic  switch-off  in  electrical  systems,  e.g.  in  accordance  with  VDE  0100  part 
410. They meet the requirements for residual current protection in accordance with 
their characteristics on the name plate. The switch-off function can be tested using 
a push-button which is also accessible to laypersons. Regular testing can increase 

the endurance of the circuit-breaker, as the mechanism of the latch is moved when 
tripped in addition to the electrical test.

Electrical connection and installation:

The electrical connection must be as shown in the wiring diagram and must comply 

with the terminal designation on the device. If the device is to be operated without 

using all poles, it is essential (in order to ensure the connection is correct) to observe 
the  position  of  the  test  key  as  per  the  wiring  diagram  and  the  operating  voltage

 

range  of  the  test  circuit  in  accordance  with  the  data  sheet.  DFS  4  devices  have  a

 

N-left design as standard. N-right devices have a ‘R’ in their designation. The device 
must be installed on a mounting rail (TS 35) according to DIN EN 60715 in distribution 
boards that have to ensure protection against direct contact (which may be required 
depending on the location of use) and protection against environmental influences.

Testing and functional check

A simple function test with the assistance of test key T should be carried out after 
the mains voltage and the circuit-breaker are switched on. When the key is pressed, 
the DFS 2/DFS 4 must disconnect without delay; the toggle is then in centre position. 
Resetting to position ‘1’ is only possible if the toggle has first been moved down to 
position ‘0’. The operation indicator beneath the toggle indicates the status of the 
contacts: red = closed, green = open.

This test must be carried out at least every six months where the device is used as 
intended  and  must  be  repeated  every  working  day  for  non-stationary  systems 

according to the regulation. If tripping does not occur, the device must be replaced 

immediately. The operator must be informed of this. All additional tests are covered 
by the prescribed acceptance test. Tests should be carried out according to DGUV 
Regulation  3  (BGV  A3)  depending  on  the  location.  The  insulation  test  should  be 
carried out using test devices according to DIN EN 61557-2.

Guarantee

All  professionally  installed,  unaltered  devices  are  covered  by  warranty  during  the 
statutory guarantee period from the day of purchase by the end user. The guarantee 
is  not  applicable  to  damage  incurred  during  transport  or  caused  by  short-circuit, 
overloading  or  improper  use.  Should  any  defects  in  workmanship  or  material 
be  discovered  within  the  warranty  period,  the  company  will  provide  repair  or 
replacement free of charge. The warranty will be rendered null and void if the device 

is opened without authorisation.

Doepke

3930292

 | 

11/2019

 | 

Doepke Schaltgeräte GmbH, Stellmacherstraße 11, D-26506 Norden

DE EN

Reviews: