voltage is present at the switch and the LED does not illuminate, the residual current 
circuit-breaker must be replaced. The insulation test should be carried out using test 
devices according to DIN EN 61557-2. To carry out a simple insulation test for the 
electrical system, we recommend supplying power ‘from above’ for type B switches. 
This means only the switch needs to be switched off during the test and the measure-
ment can take place on the system side. Performing an insulation test when the re-
sidual current circuit-breaker is switched on or on the side with the odd-numbered 
terminals can lead to erroneous measurement values as a result of the internal adap-
tor. In this case, we recommend disconnecting the switch for the duration of the test.

Important information on operation of an AC-DC sensitive residual current circuit-

breaker (DFS 2/4 B/B+) with electronic equipment 

 

(such as frequency converters, inverters etc.)

1.  Electronic  equipment  and  its  associated  EMC  protective  provisions, 

 

such as integrated or in series-connected EMC filters, as well as shielded cables, 
can produce high capacitive leakage currents.

2.  The  maximum  number  of  items  of  electronic  equipment  connected 

 

downstream of the DFS 2 B/DFS 4 B is based on the level of leakage currents that occur. 

 

Excessive leakage currents may lead to undesired tripping. Relevant information 
concerning  the  leakage  currents  that  are  produced  can  be  requested  from  the 
manufacturers of the electronic equipment.

3.  During  operation  with  frequency  converters,  long,  shielded  motor  cables 

may  lead  to  high  leakage  currents  in  the  event  of  the  controller  release  of 
the  frequency  converter,  which  may  lead  to  undesired  tripping.  If  neces-
sary,  a  sinusoidal  output  filter  should  then  be  used  directly  behind  the 

 

frequency converter (before the shielded motor cable).

4.  When  switching  electrical  systems  with  electronic  equipment  on  and  off, 

 

it is possible that very high surge leakage currents will be produced, which will 
lead  to  tripping  in  the  event  of  an  appropriate  duration.  The  switch-on  and 
switch-off  operations  should  be  kept  as  short  as  possible.  Quick-switching, 

 

all-pole  contactors  or  switches  with  stored  energy  operating  mechanisms  are 
suitable (manual rotary switches should not be used).

5.  According to the instructions, a 3-conductor EMC filter should only be connected 

in series with the relevant electronic equipment. So that the filter effect is not 
impaired, under no circumstances should further single-phase consumers such as 
incandescent bulbs be connected on the output side of the EMC filter.

6.  As a rule, different clock frequencies (chopper) can be selected in the case of elec-

tronic equipment. In an unfavourable case, the clock frequency may lead to a ten-
dency to oscillation in an upstream EMC filter and therefore to greatly increased 
leakage currents, which then result in a tripping of the DFS 2/4 B. In this case, the 
clock frequency must be changed.

7.  Frequency converters with an integrated EMC filter often only allow a maximum 

shielded motor cable length of 5 to 10 m. Longer cable lengths lead to greatly 
increased  leakage  currents  and  to  the  ineffectiveness  of  the  integrated  EMC 

 

filter.  The  manufacturer's  specifications  must  always  be  observed  for  the 

 

frequency converter.

Guarantee

All  professionally  installed,  unaltered  devices  are  covered  by  warranty  during  the 
statutory guarantee period from the day of purchase by the end user. The guaran-
tee is not applicable to damage incurred during transport or caused by short-circuit, 
overloading  or  improper  use.  In  the  event  of  defects  in  workmanship  or  material, 
which are discovered within the guarantee period, the company will provide a repair 
or replacement free of charge. The guarantee will be rendered null and void if the 
device is opened without authorisation.

Wiring diagrams

2

4

1

3

~

 

1/N

7/N

3

5

8/N

2/N 4

6

~

 

V

two-pole (grey: type B only)

 

V

four-pole, neutral on left or right, 
depending on device version 
(grey: type B only)

Installation and operating instructions

for residual current circuit-breakers 

 

of model range DFS 2 and DFS 4

These  installation  and  operating  instructions  are  aimed  at  qualified 
electrical specialists. The installation of devices of this type is not ap-
propriate  for  electrical  laypersons  due  to  the  considerable  potential 
dangers.  These  installation  and  operating  instructions  must  be  re-
tained, so that they can be referred to at a later stage. The operator of 

the electrical installation must be informed about the use and function 
of this protective device.

Application instructions and warnings

The following notes and warnings must be observed in order to ensure safe operation:

1.  Devices with visible damage must not be installed or used.
2.  Operation  must  only  occur  under  normal  ambient  conditions  free  of  corro-

sive  gases  in  order  to  preserve  the  correct  tripping  function  in  the  long  term. 

 

Corrosive gases are chlorine, ammonia and sulphurous air, for example. Residual 
current circuit-breakers with "HD" specification are recommended for environ-
ments affected by corrosive gases.

 

3.  The user must be made aware of regular function testing using the test key T.
4.  The function test with the test key is not a substitute for regular testing of the 

electrical system.

5.  Erroneous  tripping  due  to  operation  related  leakage  currents  or  atmos-

pheric  interference  cannot  be  ruled  out  with  absolute  certainty.  The  conse-
quences  must  be  considered  and  countermeasures  taken  where  necessary. 

 

Selective residual current circuit-breakers as well as surge protection measures 
and system optimisations can provide a remedy.

6.  If the RCCB cannot be switched on, or if the consumer network is not connected, 

the device must be replaced.

7.  Disposal is subject to the statutory regulations of the European Union (WEEE/

German Electrical and Electronic Equipment Act).

For further information and data sheets, please visit www.doepke.de and search by 
the article number or scan the QR code on the front of the housing.

Intended use:

DFS  2  and  DFS  4  series  protective  devices  are  residual  current  circuit-breakers 
without integrated overcurrent protection. They provide protection through auto-
matic switch-off in electrical systems, e.g. in accordance with VDE 0100 part 410. 
They meet the requirements for residual current protection in accordance with their 
characteristics  on  the  name  plate.  The  switch-off  function  can  be  tested  using  a 
push-button which is also accessible to laypersons. Regular testing can also increase 
the endurance of the circuit-breaker, as the mechanism of the latch is moved when 
tripped in addition to the electrical test.

Electrical connection and installation:

The electrical connection must be as shown in the wiring diagram and must comply 
with the terminal designation on the device. With type B devices, it is preferable for the 
power to be supplied to the odd-numbered terminals (simplified insulation measure-
ment). If the device is to be operated without using all poles, it is essential (in order to 
ensure the connection is correct) to observe the position of the test key as per the wir-
ing diagram and the operating voltage range of the test circuit in accordance with the 
data sheet. DFS 4 devices have an N-left design as standard. N-right devices have an 
‘R’ in their designation. Scrape and grease aluminium conductors immediately before 

 

connection.  The  device  must  be  installed  on  a  mounting  rail  (TS  35)  according  to 
DIN EN 60715 in distribution boards that must ensure protection against direct con-
tact (which may be required depending on the location of use) and protection against 
environmental influences.

Testing and functional check

A simple function test with the assistance of test key T should be carried out after 
the mains voltage and the circuit-breaker are switched on. When the key is pressed, 
the DFS 2/DFS 4 must disconnect without delay; the toggle is then in centre position. 
Resetting to position ‘1’ is only possible if the toggle has first been moved down to 
position ‘0’. The operation indicator beneath the toggle indicates the status of the 
contacts: red = closed, green = open. This test must be carried out at least every six 
months where the device is used as intended and must be repeated every working 
day for non-stationary systems according to the regulation. If tripping does not oc-
cur, the device must be replaced immediately. The operator must be informed of this. 
All additional tests are covered by the prescribed acceptance test. Tests should be 
carried out according to DGUV Regulation 3 (BGV A3) depending on the location. 

The green LED on the front of the housing of the DFS 2 B/DFS 4 B AC-DC sensitive 
residual current circuit-breaker indicates that the AC-DC sensitive residual current 
detection is active. If the LED does not illuminate, then only tripping in the event of 
type A residual currents is guaranteed. If this is the case, it should be checked first 
if there is operating voltage of min. 50 V AC between two active conductors. If this 

Doepke

3930290 

|

 12/2018 