
TDR9000
™
Circuit Breaker Test System User’s Guide
72A-1898 Rev. A 11/01
A-125
Monday
, November 26, 2001 1:09 pm
Within the phase, the Dead time is calculated as the difference
between the time required for the last Main Contact to close and the
first Main Contact to open.
B
Dead Time with a Circuit Breaker
This is the time when at least one Main Contact
within the circuit breaker is open during the
reclose operation (Figure A.148).
Figure A.148 Reclose Operation within a Circuit Breaker
Contact #1
Contact #2
First to open
Last to close
Dead Time
0
A
#1
#2
#1
#2
0
B
0
C
Summary of Contents for TDR9000
Page 26: ...xxii 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 50: ...Step 5 Saving Test Results 1 24 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 98: ...3 28 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 200: ...Disconnecting After the Test 4 102 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 362: ...B 34 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 388: ...D 6 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 392: ...E 4 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 394: ...F 2 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 442: ...I 32 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...
Page 454: ...I 12 72A 1898 Rev A 11 01 Monday November 26 2001 1 09 pm...