It is recommended that the panel should not be installed near heat sources (radiators, air
conditioners, etc.).
The connecting wires are mounted, using the hole in the box.
5.2 A description of the PCB terminals
The FP9000E panel is mounted on a plastic chassis at the bottom of the panel. The connections to
the main power unit, indication board and earth points are factory mounted. The connection wires
for zones and control devices must be run out through the opening above the terminal rows. The
terminals are designed to accept wires with cross section up to 2.5mm2. The wires must be fed
from the upper side the terminals.
Fig.1
Description of the terminal row:
L1, L2
– Terminals for connecting the extinguishing zones, 2-wire cross-zoning connection of the
detectors in the flooding area.
L3
– Terminal for connecting the fire alarm conventional zone, 2-wire connection of detectors
and call points. This zone is only for fire alarm detection and signalization.
Manual Release
– Supervised balanced input. This input is used for sending a signal to the
control panel (via call point) for starting the extinguishing in the protected area. More than one
call point can be connected to this line.
Hold
- Supervised balanced input. This input is used for sending a signal to the control panel (via
call point or a pressure switch) for holding (delaying) the extinguishing in the protected area. The
active state of the input, NC (Normal closed) or NO (Normal open), can be configured through the
panel setup menu.
Mode Select
- Supervised balanced input. This input is used for sending a signal to the control
panel (via switch on/off contact) for the selected operation mode for the extinguishing. The
operation modes are “Manual” and “Automatic”, as the “Manual” mode is selected when the
switch is on, and the “Automatic” mode is selected when the switch is off.
On/Off Exting
- Supervised balanced input. This input is used for enabling/disabling of the
extinguishing from an external device. The active state of the input, NC (Normal closed) or NO
(Normal open), can be set via jumper J5.
Low Press
. - Supervised balanced input. This input is used for sending a signal to the control
panel (from a pressostat contact, balance or other device) for monitoring the pressure level of the
extinguishing agent (e.g. bottles, meaning that the gas from the bottle is released and the pressure