2. TECHNICAL PARAMETERS
Fire LINES
Lines:
Extinguishing–2 fixed lines (Line 1 and Line
2)
2
Fire Alarm – 1 fixed line (Line 3)
1
Maximum number of fire detectors in a line
32
Type of the joining line
biconductional
Plume maximum resistance
100
Current thresholds in the lines:
Interruption
from 1 to 12 mA
programmable
Duty mode
from 2 to 60 mA
programmable
Fire
from 12 to 99 mA
programmable
Short circuit
> 100 mA
Lines functional characteristics:
Verification quantity before entering Fire
mode:
1, 2 or 3
programmable
Verification and regestrating fault in a earth
conductor
yes
selectively
programmable
Supervised balanced inputs
Manual Release:
The “Manual Release” input is normally
open.
1
Hold:
The “Hold” input can be configured:
# input is normally open;
# input is normally closed.
1
selectively
programmable
Low Press.:
The “Low Press.” input can be
configured:
# input is normally open;
# input is normally closed.
1
selectively
programmable
Mode Select:
The “Mode Select” input is normally
open.
1
On/Off Exting (Enable/Disable Extinguishing):
The “On/Off Exting” input is normally
open.
1
Potential outputs
S 1 (Sounder 1) – Monitored:
Type
potentional relay
Electrical characteristics
24 VDC/ 0,5A
S 2 (Sounder 2) – Monitored:
Type
potentional relay