The telephone company may make changes in its facilities, equipment, operations or procedures that could affect
the operation of the equipment. If this happens the telephone company will provide advance notice in order for you
to make necessary modifications to maintain uninterrupted service.
If trouble is experienced with the Model XR150FC/XR550FC Series, for repair or warranty information, please contact
DMP at the address and telephone number listed on the back of this document. If the equipment is causing harm to
the telephone network, the telephone company may request that you disconnect the equipment until the problem is
resolved.
If your premises has specially wired alarm equipment connected to the telephone line, ensure the installation of the
XR150FC/XR550FC Series does not disable your alarm equipment. If you have questions about what will disable alarm
equipment, consult your telephone company or a qualified installer.
Caution
: To ensure proper operation, this equipment must be installed according to the installation instructions in
this manual. To verify that the equipment is operating properly and can successfully report an alarm, this equipment
must be tested immediately after installation, and periodically thereafter, according to the test instructions in this
document and the XR150/XR350/XR550 Series Programming Guide (LT-1232). Additionally, verification of Line Seize
capability should be made immediately after installation, and periodically thereafter, in order to ensure that this
equipment can initiate a call even when other equipment (telephone, answering system, computer modem, etc.)
connected to the same line is in use.
Reset and Tamper Headers
18.1 J16 Reset Header
The reset header is located to the left of the J7 Expansion Header on the right
side of the circuit board and is used to reset the XR150FC/XR550FC Series
microprocessor. To reset the panel when first installing the system, install the
reset jumper before applying power to the panel. After connecting the AC and
battery, remove the reset jumper.
To reset the panel while the system is operational, for example, prior to
reprogramming, install the reset jumper without powering down the system.
Remove the reset jumper after one or two seconds.
After resetting the panel, begin programming within 30 minutes. If you wait
longer than 30 minutes, you must reset the panel again.
18.2 J4 Tamper Header
The J4 header is for use with the optional DMP 306 Tamper Harness. The harness
connects to one or more tamper switches mounted inside the panel enclosure
to supervise against unauthorized enclosure opening or removal. Refer to the
wiring diagram on the enclosure door for correct tamper switch wiring.
How the Tamper Works
If the enclosure is opened or removed while one or more of the system areas
are armed, a panel tamper alarm is indicated. If all areas are disarmed, a panel
tamper trouble is indicated.
Figure 10: XR550FC Series
Panel Showing the Reset
Jumper
Momentarily place the Reset
jumper over both of the J16
pins to reset the panel.