XR150FC/XR550FC Series Installation Guide
6
IntroductIon
Installation
4.1
Mounting the Enclosure
The metal enclosure for the XR150FC/XR550FC Series must be mounted using screws in the four mounting holes
shown in Figure 2. Mount the enclosure in a secure, dry place to protect the panel from damage due to tampering or
the elements. It is not necessary to remove the XR150FC/XR550FC Series PCB when installing the enclosure.
The enclosure dimensions are 13.44” tall, 17.1” wide, by 4.8” deep.
Note
: When using the XR150FC/XR550FC Series panel for listed applications, use the Model 350, 349, 341, or 352S
enclosure for standby batteries.
Enclosure Mounting Holes
3-Hole
Pattern for
Accessory
Modules
Dual 1 3/4" and 1 3/8" Conduit Knockouts
Battery shelf holds up to two batteries. Maintain minimum spacing of
1/4” between the batteries and any modules mounted in enclosure.
XR
550
FC Panel
Figure 2: XR150FC/XR550FC Series enclosure
4.2
Fire Command Center LCD Keyboard
A Fire Command Center LCD Keyboard has been factory installed on the XR150FC/XR550FC enclosure door. A
keyswitch has also been installed and pre-wired to the left of the keyboard. The user can turn the keyswitch to
enable the four function keys without opening the enclosure door.
POWER
TROUBLE
ALARM
COMMAND
1
2
3
4
5
6
7
8
9
0
ABC
DEF
GHI
JKL
MNO
PQR
STU
VWX
YX
ENABLE
SILENCE
RESET
TEST
DRILL
Fire Command Center
Figure 3: Fire Command Center LCD and Keyboard
4.3
Connection
The display and keyboard are factory pre-wired to the XR150FC/XR550FC J8 header. For standby battery
calculations, the display draws 92mA of current in normal standby or alarm condition. See Panel Standby Battery
Calculations. The keyswitch is pre-wired to the membrane keyboard.