InstallatIon GuIde
XR150fc/XR550fc
seRIes Panel
Page 1: ...Installation Guide XR150fc xr550FC Series Panel ...
Page 2: ...he installer is encouraged to try to correct the interference by one or more of the following measures Reorient the receiving antenna Relocate the computer with respect to the receiver Move the computer away from the receiver Plug the computer into a different outlet so that computer and receiver are on different branch circuits If necessary the installer should consult the dealer or an experience...
Page 3: ...ting Keypads and Zone Expansion Modules 7 Primary Power Supply 5 1 Transformers and AC Power Connection 8 Secondary Power Supply 6 1 Battery Terminals 3 and 4 9 6 2 Earth Ground GND 9 6 3 Battery Only Restart 9 6 4 Battery Replacement Period 9 6 5 Discharge Recharge 9 6 6 Battery Supervision 9 6 7 Battery Cutoff 9 6 8 Power Requirements 10 6 9 Standby Battery Selection 12 Bell Output 7 1 Terminals...
Page 4: ... Wiring 15 13 3 Model 860 Relay Module 15 Wireless Bus Expansion 14 1 Description 16 14 2 Wireless Bus LEDs 16 LX Bus Expansion 15 1 LX Bus Headers 16 15 2 LX Bus LEDs 16 15 3 OVC LEDs 16 J1 Ethernet Connector 16 1 Description 16 16 2 Ethernet LEDs 16 16 3 Network Transient Suppression 16 J3 Telephone RJ Connector 17 1 Description 17 17 2 J10 893A or 277 Connector 17 17 3 Notification 17 17 4 Phon...
Page 5: ...Zones Eight 1k Ohm EOL burglary zones zones 1 to 8 Two 3 3k Ohm EOL powered zone with reset zones 9 and 10 1 4 Keypad Bus You can connect the following supervised keypads and expansion modules to the keypad bus Alphanumeric keypads Sixteen eight four and or single zone expansion modules Single zone detectors Access control modules 1 5 LX Bus You can connect the following devices to the LX Bus conn...
Page 6: ... Bus circuits 2 3 Output Expansion In addition to the two SPDT relays and four programmable open collector outputs on the panel you can also connect up to 25 programmable Model 716 Output Expansion Modules to each LX Bus These modules can provide an additional 500 or 100 programmable SPDT relays The XR150FC XR550FC Series provides 100 Output Schedules you can use for programming the 716 to perform...
Page 7: ...ed All circuits are inherent Power Limited except the red battery wire and AC terminal NFPA 72 This equipment should be installed in accordance with Chapter 11 of the National Fire Alarm Code ANSI NFPA 72 2002 National Fire Protection Association Batterymarch Park Quincy MA 02269 Printed information describing proper installation operation testing maintenance evacuation planning and repair service...
Page 8: ... use on the LX Bus only 734 734N Wiegand Interface Modules Provides system codeless entry and arming and disarming using access control readers DMP Two Way Wireless Devices 1100X 1100XH Wireless Receiver Supports up to 500 devices in residential or commercial wireless operation 1100R Repeater Provides additional range for wireless devices 1101 Universal Transmitter Provides both internal and exter...
Page 9: ...r supply The 866 can supervise 2 wire Style W circuits for opens and shorts 867 Style W LX Bus Notification Circuit Module Provides supervised alarm current using the XR150FC XR550FC Series panel bell output and up to 5 Amps at 12 or 24 Vdc when using a listed auxiliary power supply The 867 connects to the XR150FC XR550FC Series panel LX Bus and provides one 2 wire Style W notification circuit for...
Page 10: ...elf holds up to two batteries Maintain minimum spacing of 1 4 between the batteries and any modules mounted in enclosure XR550FC Panel Figure 2 XR150FC XR550FC Series enclosure 4 2 Fire Command Center LCD Keyboard A Fire Command Center LCD Keyboard has been factory installed on the XR150FC XR550FC enclosure door A keyswitch has also been installed and pre wired to the left of the keyboard The user...
Page 11: ...n planning an LX Bus and keypad bus installation keep in mind the following information 1 DMP recommends using 18 or 22 gauge unshielded wire for all keypad and LX Bus circuits Do not use twisted pair or shielded wire for LX Bus and keypad bus data circuits 2 On keypad bus circuits to maintain auxiliary power integrity when using 22 gauge wire do not exceed 500 feet When using 18 gauge wire do not...
Page 12: ...s The panel must be properly grounded before connecting any devices or applying power Proper grounding protects against Electrostatic Discharge ESD that can damage system components The 16 VAC transformer must be wired to a dedicated unswitched 120 VAC 60 Hz circuit with at least 87A available Install cover over screw terminals after completing connection WHITE BLACK Ground Wire Connected to Enclo...
Page 13: ...s panel without AC power briefly short across the battery start pads to pull in the battery cutoff relay The leads need a momentary short only Once the relay has pulled in the battery voltage holds it in that condition If the XR150FC XR550FC Series panel is powered up with an AC transformer the battery cutoff relay is pulled in automatically For more information refer to Figure 1 6 4 Battery Repla...
Page 14: ...our relays active Qty _______ x 34mA 138mA ______ ______ Qty _______ x 34mA 138mA ______ ______ 865 Style Y or Z Notification Module Qty _______ x 26mA ______ Qty _______ x 85mA ______ 866 Style W Notification Module Qty _______ x 45mA ______ Qty _______ x 76mA ______ 867 LX Bus Style W Notification Module Qty _______ x 30mA ______ Qty _______ x 86mA ______ 869 Dual Style D Initiating Module Qty _...
Page 15: ...______ Qty _______ x x x 7mA 30mA 1mA ______ ______ ______ 715 8 715 16 Zone Expansion Modules Active Zones EOL Installed 2 Wire Smokes Qty _______ Qty _______ Qty _______ x x x 20mA 4mA 1mA ______ ______ ______ Qty _______ Qty _______ Qty _______ x x x 20mA 30mA 1mA ______ ______ ______ 716 Output Expansion Module Active Form C Relays Qty _______ x 13mA ______ Qty _______ Qty _______ x x 13mA 12m...
Page 16: ...atteries Max Ah Available No of Batteries Max Ah Available No of Batteries Max Ah Available No of Batteries Max Ah Available No of Batteries Max Ah Available No of Batteries 8 2 6 1 6 1 8 1 16 1 12 3 12 2 13 2 16 2 32 2 16 4 18 3 20 3 24 3 48 3 20 5 24 4 27 4 32 4 24 6 31 5 34 5 40 5 28 7 37 6 41 6 32 8 43 7 36 9 Note 48 hours is the typical battery recharge time for any of the Number of Batteries...
Page 17: ...current rating See Power Supply in the Compliance Listing Guide LT 1330 for maximum current in a fire listed application 8 3 Terminal 8 YELLOW Terminal 8 receives data from keypads and zone expansion modules It cannot be used for any other purpose 8 4 Terminal 9 GREEN Terminal 9 transmits data to keypads and zone expansion modules It cannot be used for any other purpose 8 5 Terminal 10 BLACK Termi...
Page 18: ... condition Condition Resistance on zone Voltage on positive terminal Open over 1300 ohms over 2 0 Vdc Normal 600 to 1300 ohms 1 2 to 2 0 Vdc Short under 600 ohms under 1 2 Vdc 10 3 Zone Response Time A condition must be present on a zone for 500 milliseconds before it is detected by the panel Ensure detection devices used on the protec tion zones are rated for use with this delay Zones 1 10 can al...
Page 19: ...mmon Gray Output 1 normally open Orange Output 2 normally closed Violet with white stripe Output 2 common White with gray stripe Output 2 normally open Orange with white stripe The relay contacts must be connected to devices located within the same room as the XR150FC XR550FC Series panel Annunciator Outputs 13 1 Description The four programmable annunciator outputs can be programmed to indicate t...
Page 20: ...en to indicate the panel is transmitting LX Bus data The right LED flashes yellow to indicate the panel is receiving LX Bus data 15 3 OVC LEDs The Overcurrent LEDs OVC light Red when the devices connected to the Keypad Bus and LX Bus es draw more current than the panel is rated for The first OVC is located to the left of the 893A Connector and the second is to the right of the J24 Cell Module Each...
Page 21: ... determine if panel is seizing the line 1 Unplug phone cord from RJ31X 2 Place butt set on pins 4 and 5 3 Listen for dial tone With dial tone present lift either wire from pins 1 or 8 4 Listen for dial tone again If the dial tone is present RJ31X wiring is correct If no dial tone is present the RJ31X wiring is backwards Rewire so dial tone is coming IN on 4 and 5 If you still have trouble with the...
Page 22: ...erification of Line Seize capability should be made immediately after installation and periodically thereafter in order to ensure that this equipment can initiate a call even when other equipment telephone answering system computer modem etc connected to the same line is in use Reset and Tamper Headers 18 1 J16 Reset Header The reset header is located to the left of the J7 Expansion Header on the ...
Page 23: ...XR150FC XR550FC Series Installation Guide Digital Monitoring Products 19 ...
Page 24: ... CSFM FCC Part 15 FCC Part 68 Registration ID CCKAL00BXR550 New York City FDNY COA 6167 ANSI UL 294 Access Control System Units ANSI UL 1610 Central Station Burglar ANSI UL 2017 General Purpose Signaling Devices and Systems ANSI UL 864 Fire Protective Signaling Compatible with Devices listed for ANSI UL 268 Smoke Automatic Fire Detectors ANSI UL 346 Waterflow Indicators for Fire Protective Signali...