Digital Monitoring Products, Inc. | 7360/7363 Installation and Programming Guide
11
Emergency Key (E 0)
Use this option to configure the top two middle Select keys as 2-button
Emergency keys. The display shows the current emergency key setting. The
far left position displays
E
(Emergency)and the far right position displays the
emergency key setting. To enable the emergency key operation press the
number one key. This toggles between one (
1
) and zero (
0
) on the display.
Zero (
0
) disables this option. The default is
0
.
Fire Key (F 0)
Use this option to configure the top two right Select keys as 2-button Fire
keys. The display shows the current fire key setting. The far left position
displays
F
(Fire) and the far right position displays the fire key setting. To
enable the fire key operation press the number one key. This toggles between
one (
1
) and zero (
0
) on the display. Zero (
0
) disables this option. The default
is
0
.
Number of User Code Digits (U 4)
from Proximity Card Read (7363)
The 7363 keypad will convert proximity credential data into a four, five or six
digit code which is then sent to the control panel. Enter the user code digit
length used by the panel. The far left digit displays
U
(User Code) and the far
right position displays the user code digit length. The default is
4
and is the
proper setting for XT30/XT50 panels.
When searching the bit string from the reader for the user code, the digits are
identified and read from left to right. When a four-digit user code is selected
only the first four digits of the string are read.