ADDITIONAL INFORMATION
Additional Power Supply
If the current draw for all keypads exceeds the panel output, provide additional current by
adding a Model 505-12 auxiliary power supply. Connect all keypad Black ground wires to
the power supply negative terminal. Run a jumper wire from the power supply negative
terminal to the panel common ground terminal. Connect all keypad power (+12 VDC) wires
to the power supply positive terminal. Do not connect the power supply positive terminal
to any panel terminal. Refer to the 505-12 Power Supply Installation Guide (LT-0453) for
more information.
Panic Key Options
2-Button Panic Keys
All keypads offer a panic key function that allows users to send Panic, Emergency, or Fire
reports to the central station. In order to use the panic keys, enable the functions in the
keypad user menu. See Programming Keypad Options later in this document. Install the
supplied icon labels below the top row of Select keys as shown in Figure 4.
Press and hold the two Select keys for two seconds until a beep from the keypad is heard.
At the beep, the panel sends the zone alarm reports shown in Table 1to the central station.
Note:
All 7300 keypads send address 8 as a default on panic alarms.