Zone 2 Bypass (Soft-Shunt)
Select YES to enable the bypass option on Zone 2. This
zone provides the bypass for door contacts. This zone must
be programmed into the panel.
Zone 2 Bypass (Soft-Shunt) Time
Enter the number of bypass seconds to elapse before the
bypass timer expires. Range is from twenty to 250 seconds.
Press the display to enter the number of seconds. Once
the door strike relay is activated, the user has five seconds
to open the door connected to Zone 2. The zone is then
bypassed for the programmed time or until the contact
restores to normal. Ten seconds before the bypass entry/
exit time expires, the keypad beeps once every second. If
the door remains open when the timer expires a zone open/
short is sent to the panel for Zone 2. The default is forty
seconds. Figure 10
shows how the bypass works using the
default forty–second timer.
ACTIVATE ZONE 2
BYPASS: NO YES
ZONE 2 BYPASS
TIME: 40
5 Second
Strike
40-Second Bypass
and entry/exit timer.
At 30 seconds,
the keypad beeps
if door is still open.
End of
timer.
40
Seconds
A zone fault is indicated
if door is still open.
DISARMED
Panic
Chime
Check-in
Fire Reset
MON 5:35 AM
Dealer Logo
TODAY
WEDNESDAY
82
CURRENT
HI LO
98 77
HI
80
LO
74
Figure 10: Door Strike Relay Operation Time Line