Activate Zone 2 Bypass
Select YES to activate the Zone 2 Bypass operation. Select
NO to allow standard Zone 2 operation. The default is NO.
You can program a bypass entry/exit timer on protected
(contact installed) doors by connecting the contact wiring to
keypad Zone 2. When the on-board Form C relay activates
and the user opens the protected door, the zone is delayed
by the
Zone 2 Bypass Time
. This allows the user to enter/exit
during an armed period.
If Zone 2 does not restore (the door doesn’t close) within the
programmed time, the keypad sounds every other second
during the last ten seconds and sends the open or short zone
condition to the panel. If Zone 2 does restore prior to the end
of the programmed time, the keypad silences.
Zone 2 Bypass Time
Enter the number of bypass seconds to elapse before the
bypass timer expires. Range is 20-250 seconds. Press any
select area to clear the keypad display and enter the number
of seconds. Default is
40
seconds.
ACTIVATE ZONE 2
BYPASS?
NO
YES
ZONE 2 BYPASS
TIME:
40