Relock on Zone 2 Change
Select
NO
(default) to leave the relay on when Zone 2
changes to an open or short condition during bypass. Select
YES
to turn the relay off when Zone 2 changes to open or
short during bypass.
Activate Zone 3 Exit
Select
YES
to activate Zone 3 Request to Exit (REX). Select
NO
for standard zone operation on Zone 3. Default is
NO
.
Connect a motion sensing device or a mechanical switch to
Zone 3 to enable REX. When Zone 3 shorts, the on-board
Form C relay activates for the programmed number of
seconds. See Zone 3 REX Strike Time.
During this time, the user can open the protected door to
start the Zone 2 bypass timer. After the programmed time
period elapses, the relay restores the door to locked.
The keypad provides a bypass-only option for REX on
Zone 3. When Zone 3 opens from a
NORMAL
state, only a
bypass occurs: the on-board relay does not activate. This
bypass-only option uses two methods of REX. The first REX
device provides the programmed bypass entry/exit timer. The
second REX unlocks the door.
RELOCK ON ZONE 2
CHANGE:
NO
YES
ACTIVATE ZONE 3
REX?
NO
YES