Digital Monitoring Products, Inc. | 734INT Installation and Programming Guide
11
Connect a Wiegand Card Reader
The 734INT provides direct 12/24 VDC, 200 mA output to the reader on the Red
terminal connection. Figure 9 shows a reader with wire colors RED, WHT, GRN, and
BLK connecting to Terminals 1, 2, 3, and 4.
The green wire carries Data Zero (D0), and the white wire carries Data One (D1).
The red wire connects 12/24 VDC, 200 mA maximum power and the black wire is
ground.
The wire colors may be different depending on the reader being installed. Refer to
the literature provided with the reader for wire coding, wire distance, cable type
(such as shielded), and other specifications.
Wiegand Status Indicator Outputs
Terminals 5, 6, and 7 provide connections for Remote LED Control, Remote
Annunciation, and Armed Status indicators.
6