734INT Installation and Programming Guide | Digital Monitoring Products, Inc.
Zone 2 Bypass Time
Enter the number of seconds to elapse before the bypass
timer expires. The range is 20‑250 seconds. Press any select
key or area to enter the number of seconds. The default is
40
seconds. Figure 11 shows how the bypass option works.
Relock on Zone 2 Change
Selecting
YES
turns the relay off when zone 2 changes state.
Selecting
NO
leaves the relay on when zone 2 changes
state. Turning off the relay allows a long strike time to be
automatically ended upon zone 2 change and relocks the
door. The default is
NO
.
ZONE 2 BYPASS
TIME:
40
5-Second
Strike
40-Second Zone 2
Bypass Entry/Exit Timer
10 seconds before
the bypass time expires,
the device beeps if
the door is still open.
End of
Timer
40
Seconds
A zone open/short is
indicated if the door
remains open.
Figure 11: Zone 2 Bypass Timeline
RELOCK ON ZONE 2
CHANGE?
NO
YES