734 Installation and Programming Guide | Digital Monitoring Products
14
Relock on Zone 2 Changes
Selecting
YES
turns the relay off when zone 2 changes state. Selecting
NO
leaves the
relay on when zone 2 changes state. Turning off the relay allows a long strike time to
be automatically ended upon zone 2 change and relocks the door. The default is
NO
.
Activate Zone 3 Request to Exit
Selecting
YES
activates the zone 3 Request to Exit (REX) option. Selecting
NO
allows
standard zone operation on zone 3. Default setting is
NO
.
Connect a motion sensing device or a mechanical switch to zone 3 to provide REX
capability to the system. Zone 3 can be used to activate the strike relay and bypass or
activate bypass only. For zone wiring details, refer to Figure 8.
Activate Strike Relay and Bypass
Wire zone 3 as normally open with a 1k Ohm EOL resistor.
When zone 3 shorts, the onboard Form C relay activates for the programmed number
of seconds. See “Zone 3 REX Strike Time”. During this time, the user can open the
protected door to start the programmed zone 2 bypass entry/exit timer. After the
programmed number of seconds, the relay restores the door to its locked state.
Activate Bypass Only
Wire zone 3 as normally closed with an in-line 1k Ohm resistor.
When zone 3 opens from a normal state, only a bypass occurs and the onboard relay
does not activate.
Zone 3 REX Strike Time
Enter the number of REX seconds to elapse. The range is 5 to 250 seconds. Press any
select key or area to enter the number of seconds. The default is
5
seconds.
Activate Onboard Speaker
Select
YES
to enable the onboard piezo for local annunciation, such as alarm and
trouble annunciations. Select
NO
to turn the speaker off for all operations. This does
not affect remote annunciator open collector (RA) operation. The default is
NO
.
Card Formats
Select
DMP
to allow credentials that use a 26 - 45 bit data string. The menu advances
Select
CUSTOM
to disable DMP format and program slots 1-8 as needed. The menu
advances to “Card Format Number”.
Select
ANY
to allow all card reads to activate the door strike relay. The door strike
relay is activated for the length of time programmed in
ZN 3 REX TIME
. No user code
information is sent to the panel. The menu advances to “No Communication with
Panel”.
The default card format is
DMP
.
RELOCK ON ZONE 2
CHANGE?
NO
YES
ACTIVATE ZONE 3
REX?
NO
YES
ZN 3 REX STRIKE
TIME:
5
ACTIVATE ONBOARD
SPEAKER?
NO
YES
CARD FORMATS
DMP
CUSTOM ANY