714/715 Installation Guide  

Digital Monitoring Products

3

LX-Bus Zone Numbers

The 714-D22 module provides 4 zones. When set to an address, the module uses four zone numbers. For example, 

setting the module to the LX-Bus address 502 (

TENS 

= 0, 

ONES 

= 2) sets the module zone numbers to 502, 503, 504, 

and 505.

Refer to Table 2 for a partial listing of XR100/XR500 Series panel LX-Bus zone numbers.

Note:

 XR100 Series panels only use LX-Bus number one.

LX-Bus 

Address

LX-Bus 

Number

Switches 

 Tens  Ones

Zone 

Numbers

501

1

0

1

501 to 504

506

1

0

6

506 to 509

623

2

2

3

623 to 626

654

2

5

4

654 to 657

742

3

4

2

742 to 745

768

3

6

8

768 to 771

833

4

3

3

833 to 836

877

4

7

7

877 to 880

919

5

1

9

919 to 922

994

5

9

4

994 to 997

Table 2: LX-Bus Zone Numbers

Optional Accessories

You can replace the standard wiring harness with the optional 718T Plug-in Screw Terminal. The enclosure base can 

also accommodate the 719T Terminal Boards for the 714-D22, which passes through the panel LX-Bus wiring. The 

719T includes 1k EOL resistors.

Wiring Specifications for Keypad and LX-Bus

1. DMP recommends using 18 or 22-gauge 

unshielded 

wire for all keypad and LX-Bus circuits. 

Do Not

 use twisted 

pair or shielded wire for LX-Bus and keypad bus data circuits. To maintain auxiliary power integrity when 

using 22-gauge wire do not exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet. Install an 

additional power supply to increase the wire length or add devices.

2. Maximum distance for any one circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance 

can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. 

As wire distance from the panel increases, DC voltage on the wire decreases.

3. Maximum number of devices per 2,500 feet circuit is 40. 

Note:

 Each panel allows a specific number of supervised keypads. Add additional keypads in the unsupervised 

mode. Refer to the panel installation guide for the specific number of supervised keypads allowed.

4. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC. If the voltage 

at any device is less than the required level, add an auxiliary power supply at the end of the circuit. When 

voltage is too low, the devices cannot operate properly.

For additional information refer to the panel installation guide and LX-Bus/Keypad Bus Wiring Application Note 

(LT-2031) or the 710 Installation Guide (LT-0310).