Digital Monitoring Products
714/715 Installation Guide
2
Setting Address Switches
714-D22 Zone Expanders use two rotary switches (TENS and ONES) to set the module address. For keypad bus
addresses, set the switches to match the device address. For LX-Bus addresses, set the switches to match the last
two digits of the addresses. For example, for address
02
set the switches to
TENS
= 0 and
ONES
= 2 as shown in
Figure 2.
0 1
2
3
4
5
6
7
8
9
S2
0 1
2
3
4
5
6
7
8
9
S1
TENS ONES
Figure 2: Switches
Keypad Bus Zone Numbers
Refer to Table 1 for keypad bus zone numbers and the panels where they operate.
Keypad
Bus
Address
Switches
Tens Ones XT30/XT50 XR100 Series XR500 Series
1
0
1
11 to 14
11 to 14
11 to 14
2
0
2
21 to 24
21 to 24
21 to 24
3
0
3
31 to 34
31 to 34
31 to 34
4
0
4
41 to 44
41 to 44
41 to 44
5
0
5
51 to 54
51 to 54
51 to 54
6
0
6
61 to 64
61 to 64
61 to 64
7
0
7
71 to 74
71 to 74
71 to 74
8
0
8
81 to 84
81 to 84
81 to 84
9
0
9
N/A
N/A
91 to 94
10
1
0
N/A
N/A
101 to 104
11
1
1
N/A
N/A
111 to 114
12
1
2
N/A
N/A
121 to 124
13
1
3
N/A
N/A
131 to 134
14
1
4
N/A
N/A
141 to 144
15
1
5
N/A
N/A
151 to 154
16
1
6
N/A
N/A
161 to 164
Table 1: Keypad Bus Zone Numbers