712-8 INSTALLATION GUIDE     |     DIGITAL MONITORING PRODUCTS 

3

To communicate the status of the eight zones, the module 

responds to two addresses on the Keypad Bus and eight 

addresses on the LX‑Bus. You can set the module starting 

address to any bus address from 0 to 15. The module 

automatically responds to this address, the next address 

on the Keypad Bus, and the next seven addresses on the 

LX‑Bus.
To change the current address, move the slide switches to 

the appropriate address positions according to Figure 4.

Keypad Bus Addressing

The module can be set to the following keypad addresses 

according to panel model: 1 through 8 for XT30/XT50 

and XR150 Series panels, or 1 through 15 for XR550 Series 

panels. Additionally, the eight zones on the module occupy 

two keypad addresses.
For example, if the module is set to address 2, the first four expansion zones occupy address 2 and respond 

as zones 21‑24. The last four expansion zones occupy address 3 and respond to the panel as zones 31‑34. For 

more information about Keypad Bus addressing, refer to Table 1.

Note:

 Because the 712‑8 is supervised, both addresses must be selected in Device Setup of the 

XR150/XR550 Series programming when used on the Keypad Bus.

LX‑Bus Addressing

When connecting to the LX‑Bus, the module must be addressed to match the last two digits of the 

first zone being used. The next seven zone addresses are automatically used to communicate expander 

zones 2 through 8 status.
For example, on an XR150 panel using LX‑Bus 1 if you set the module address to 8, the eight zones on the 

expander respond as zones 508 to 515. When connected to an XR550 panel using LX‑Bus 2, the zones respond 

as 608 to 615. For more information about LX‑Bus addressing, refer to Table 2.

Note:

 Only two 712‑8 Modules can be connected to each LX‑Bus.

ADDRESS THE MODULE

Z1

Z2 Z3

Z4 Z5

Z6 Z7

Z8

GND

GND

GND

GND

KEYPAD 

LX-BUS

TXD

BLK

BLK

RED

RED

712-8

AC

1

2

3

4

5

6

7

8

10

11

12

13

14

15

16

17

18

9

+B

BELL GND

SMK

GND

RED YEL GRN BLK

Z1

Z2 Z3

Z4

Z5

20

Z6

AC

-B

GND

19

GND

21

Z7

22

GND

23

Z8

24

Z9

25

Z10+

26

Z10-

RED

PROG

XT30

To other zone 

expansion modules 

on the same bus.

1K EOL

1K EOL

1K EOL

1K EOL

1K EOL

1K EOL

1K EOL

1K EOL

Zone 1

Zone 2

Zone 3

Zone 4

Zone 8

Zone 7

Zone 6

Zone 5

Use supplied 1K EOL resistors on each zone.

Normal operating range is 650-1200 Ohms  

These 4-pin headers are connected 

together internally to allow bus 

connection of other zone expansion 

modules. 

ADDRESS

Figure 3: Wiring Diagram

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

ON

 1  2  3 4

1  2 3 4

5  6 7 8

9  10 11 12

13 14 15  0

Figure 4: Addressing the Module

Reviews: