Parameter
Description
Navigation
Values
Default
Value
Car priority
Time of elevator car at floor without direction
before taking landing calls. In case of combined
automatic doors, timing starts when doors have
closed and the shock, photocell and re-opening
contacts are not activated
▲▼
(Increase/Decrease)
2 s <-> 30
s
10 s
Floor call
registration
Set the blinking for floor buttons upon registration
◄► (Selection)
Permanent;
Blinking at
floors
Permanent
AUX output
Selection of the output type on the 16 relays
boards and for dynamic outputs on LOP:
Type 0 = Car at floor and Out of Service
Type 1 = Arrows
Type 2 = Car at floor and Car is coming
Type 3 = 3 Wire Display
◄► (Selection)
1 wire per
floor;
Car at
floor;
Floor light;
Gray
indicator;
9 segm.
indicator;
Lift is
coming;
1 wire per
floor HYD
1 wire per
floor
Automatic
floor
designation
Automatic setting of numeric characters for serial
position indicators. The value increases/decreases
automatically at each floor starting from Lowest
floor
▲▼
(Increase/Decrease)
-9 <-> 30
Lowest fl.:
0
Manual
floor
designation
Manual setting of alphanumeric characters for
serial position indicators. Setting must be done for
each floor
◄► (Selection)
▲▼ (Change value)
- ;
0 <-> 9 ;
A <-> Z
Trigger on
PV
It is possible to start trigger (speech synthesiser /
next direction arrows) on deceleration point (Yes)
or to floor arrival (No).
◄► (Selection)
No
yes
No
Next
direction
arrows
In case of parameter activation, arrow outputs are
activated only when lift stops at floor (or on slowing
down if trigger parameter on PV is active).
◄► (Choice)
No
yes
No
LTMP
Delay
This function handle the delay between a floor/car
call and the light turning on. The output is
deactivated XX seconds after the call has been
served.
0 sec means no timer active (light ON)
▲▼
(Increase/Decrease)
0 s <-> 240
s
1 sec.
EME Delay
This function handles the delay between the black
out signal (IEME) and output command (OEME)
before system switch in automatic emergency
procedure.
▲▼
(Increase/Decrease)
0 s <-> 30
s
0 sec.
Buzzer 81-
21
For 81-21 installation: use the 81-20’s acoustic
buzzer (bypass door) on the top of car as acoustic
alarm when protections are not in active position.
◄► (Choice)
No
yes
No