8. Maintenance and Storage
8.1 Maintenance
1.
Ensure that the ventilation holes are not blocked.
2.
Ensure that the UPS is not dusty.
3.
Ensure that there are no traces of moisture on the UPS.
4.
Perform a battery status check in accordance with section 8.3.
8.2 Storage
Connect the UPS to the mains to charge the UPS for at least 8–10 hours before storing
the UPS.
Disconnect the UPS, turn it off and place in a clean and dry place.
Temperature, °С
Период
Время зарядки
From 10 to 25
Once in 6 months
8-10 hours
From 25 to 40
Once in 3 months
8-10 hours
Table 5. Recommended battery charging frequency
Allowable storage temperature is in the range from 0 to +40 ° С.
8.3 Battery control
Batteries are the key component of the UPS. Its service life depends on the temperature,
as well as on the time of charging and discharging. High temperatures and over
discharge can shorten battery life.
1. Maintain ambient temperature in the range of 15 - 25°C.
2. In case of the UPS isn’t used for long time, it is recommended to fully charge the
batteries every 6 months.
3. Batteries should not be replaced individually.
4. Under normal working conditions, the battery life is about 2-4 years. If the batteries
were kept in a humid, dusty environment, or in low temperature conditions, their service
life will be reduced.
Algorithm of battery test are described below (battery performance may drop
dramatically as the end of its service life approaches, it is recommended to check it at
least once every 6 months):
1.
Connect the UPS to the mains and charge for 8-10 hours.
2.
Turn on the UPS, connect users and measure the power of their consumption.
3.
Disconnect the mains so that the UPS switches to battery mode and control the
discharge time before shutting down.
4.
Check whether the discharge time corresponds to the values given in figures 4 to 10.
If the discharge time decreases by more than 50%, replace the batteries.
The UPSs work with V.R.L.A. type lead-acid batteries, which are charged in the presence
of a mains supply.
Summary of Contents for INFO1200
Page 2: ......
Page 5: ...3...
Page 6: ...4...
Page 7: ...5 1 2 2 1 1 2 3 4 5 3 6 7 2 2 1 2 3 Info Info LCD 4 5 10 6...
Page 8: ...6 2 3 1 2 3 1 2 5 3 4 5...
Page 9: ...7 4 4 1 1 USB USB RS232 USB RS232 2 3 4 0 40 C 20 1 RJ11 IN OUT RS232 USB USB RS232 50 60...
Page 14: ...12 6 INFO800 INFOLCD800 7 INFO1200 INFOLCD1200...
Page 15: ...13 8 INFO1500 INFOLCD1500 9 INFO2000 INFOLCD2000...
Page 18: ...16 4 4 10 50 V R L A 1 2 3 4 5 6 7...
Page 19: ...17 9 2 batt dkc ru service_center 8 800 250 52 63 www dkc ru...
Page 20: ...18...
Page 21: ...19 Lingua Italiana...
Page 22: ...20...
Page 36: ...34 English language...
Page 37: ...35...
Page 45: ...43 Figure 4 Runtime graph INFO800 INFOLCD800 Figure 5 Runtime graph INFO1200 INFOLCD1200...
Page 50: ...48...
Page 51: ......
Page 52: ......