The parameter defines the number of degrees Celsius by which the temperature
must fall below the setpoint, at which the controller will resume the HEATING mode –
at this point the feeder will start regular operation as set by the parameters
Operating
parameters - HEATING - feeder operation
and
Operating parameters - HEATING
- feeder pause
) ,fan will be switch on and will keep running until the boiler reaches the
required temperature. Change range: from 1 °C to 9 °C.
Operating parameters - HYSTERESIS
Operating parameters - HEATING - feeder operation
The parameter defines the time (in seconds) of the duration of fuel feeding (feeder
operation) in the START and HEATING mode. Change range: from 1 s to 250 s.
Operating parameters - HEATING- feeder pause
This parameter specifies the time (in seconds) of the interval between cyclic fuel
delivery (feeder operation) in START and HEATING mode.
250 s.
Change range: from 1s to
Pressing again takes you to the next setting.
Pressing again takes you to the next setting.
Pressing again takes you to the next setting.
If a piston feeder is used, feeding of fuel into the furnace will be performed in cycles
(i.e. stroke of the fuel drawer and its return). Change range: from 1 to 20.
13