XWEB SERIES
Installation Guide
1592010850
23/05/2007
Pg. 7/72
3 RS 485 CONNECTION
To be connected to the serial line all the Dixell Modbus instruments
must be provided with direct RS485 terminals or the “TTL”-RS485
interface (XJRS485 or XJ485). Check the instrument manuals for
more information. The RS485 line is mainly based on two polarised
terminals. Please pay respect to the right sequence for all the
devices connected to the serial line.
Follow these important instructions :
•
The RS485 serial line must reach all the instruments where they
are installed.
•
Make sure of the wire polarities when screwing them into the
instrument terminals.
•
The cable must have 2 or 3 wires with shield, minimum section
0,5mm
2
(eg. the BELDEN 8772).
•
From the XWEB5000 position the cable reaches all the
instrument positions.
•
Do not execute loops or derivations:
Summary of Contents for XWEB5000 EVO
Page 1: ...INSTALLATION GUIDE Ver 1 0...
Page 2: ......
Page 22: ...XWEB SERIES Installation Guide Pg 22 72 23 05 2007 1592010850...
Page 28: ...XWEB SERIES Installation Guide Pg 28 72 23 05 2007 1592010850 6 Click Finish...
Page 29: ...XWEB SERIES Installation Guide 1592010850 23 05 2007 Pg 29 72...
Page 32: ...XWEB SERIES Installation Guide Pg 32 72 23 05 2007 1592010850 8 Click the Finish button...
Page 37: ...XWEB SERIES Installation Guide 1592010850 23 05 2007 Pg 37 72 22 Click the Yes button...
Page 40: ...XWEB SERIES Installation Guide Pg 40 72 23 05 2007 1592010850 Chose Dial up to the Internet...
Page 45: ...XWEB SERIES Installation Guide 1592010850 23 05 2007 Pg 45 72 The first part is done...
Page 53: ...XWEB SERIES Installation Guide 1592010850 23 05 2007 Pg 53 72...
Page 55: ...XWEB SERIES Installation Guide 1592010850 23 05 2007 Pg 55 72 5 Click Next...
Page 64: ...XWEB SERIES Installation Guide Pg 64 72 23 05 2007 1592010850...
Page 67: ...XWEB SERIES Installation Guide 1592010850 23 05 2007 Pg 67 72...
Page 68: ...XWEB SERIES Installation Guide Pg 68 72 23 05 2007 1592010850...