XR70CX 

3/5 

ALU  MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm

: (-50.0 ÷ SET°C; -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

AFH Differential for temperature alarm/ fan recovery: 

(0,1÷25,5°C; 1÷45°F) Intervention 

differential for recovery of temperature alarm. It’s also used for the restart of the fan when the 
FSt temperature is reached  

ALd  Temperature alarm delay

: (0÷255 min) time interval between the detection of an alarm 

condition and alarm signalling. 

dAO Exclusion of temperature alarm at startup

: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

AL2 Low temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

LA2 alarm is signalled, possibly after the Ad2 delay. 

Au2 High temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

HA2 alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery

:

 

(0,1÷25,5°C; 1÷45°F) 

Ad2 Condenser temperature alarm delay

: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2 Condenser temperature alarm exclusion at start up

: (from 0.0 min to 23.5h, res. 10min) 

bLL  Compressor off with low temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

AC2 Compressor off with high temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

FOURTH RELAY  
tbA  Alarm relay silencing (with oA3=ALr):  

n

= silencing disabled: alarm relay stays on till alarm condition lasts,  

=silencing enabled: alarm relay is switched OFF by pressing a key during an alarm 

oA3 Fourth relay configuration:

 

ALr

: alarm; 

Lig

: light;

 AuS

: Auxiliary relay; 

onF

: always on with 

instrument on; 

db = 

do not select it; 

dEF: 

do not select it!.

; FAn: 

do not select it!.

; dF2: 

do not 

select it.

 

AoP Alarm relay polarity: 

it set if the alarm relay is open or closed when an alarm happens. 

CL

terminals 1-2 closed during an alarm; 

oP

 = terminals 1-2 open during an alarm

 

DIGITAL INPUT  
i1P  Digital input polarity: oP: 

the digital input is activated by opening the contact; 

CL: 

the digital 

input is activated by closing the contact.

 

i1F Digital input configuration: EAL 

= external alarm: “EA” message is displayed; 

bAL 

= serious 

alarm “CA” message is displayed. 

PAL 

= pressure switch alarm, “CA” message is displayed; 

dor

 = door switch function; 

dEF

 = activation of a defrost cycle; 

AUS 

=not enabled; 

Htr 

= kind of 

action inversion (cooling – heating); 

FAn = not set it; ES = 

Energy saving. 

did

:

 

(0

÷

255 min) 

with

 

i1F= EAL or i1F = bAL digital input alarm delay:

 delay between the 

detection of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay 

with i1F = PAL: time for pressure switch function: 

time interval to calculate the number of 

the pressure switch activation. 

nPS Pressure switch number:

 (0 

÷

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

odc  Compressor and fan status when open door:

   

no

 = normal; 

Fan

 = Fan OFF; 

CPr 

Compressor OFF; 

F_C

 = Compressor and fan OFF.  

rrd  Outputs restart after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm;  

HES Temperature increase during the Energy Saving cycle :

 (-30,0°C

÷

30,0°C/-22÷86°F) it sets 

the increasing value of the set point during the Energy Saving cycle.  

TO SET CURRENT TIME AND WEEKLY HOLIDAYS 
Hur Current 

hour 

(0 ÷ 23 h) 

Min Current 

minute

 (0 ÷ 59min) 

dAY Current 

day

 (Sun ÷ SAt) 

Hd1  First weekly holiday 

(Sun ÷ nu) Set the first day of the week which follows the holiday 

times. 

Hd2  Second weekly holiday 

(Sun ÷ nu) Set the second day of the week which follows the 

holiday times. 

N.B.   Hd1,Hd2 

can be set also as

 “nu” 

value (Not Used).

  

 
TO SET ENERGY SAVING TIMES 
ILE 

Energy Saving cycle start during workdays

: (0 ÷ 23h 50 min.) During the Energy Saving 

cycle the set point is increased by the value in HES so that the operation set point is SET + 
HES.  

dLE 

Energy Saving cycle length during workdays

: (0 ÷ 24h 00 min.) Sets the duration of the 

Energy Saving cycle on workdays.  

ISE 

Energy Saving cycle start on holidays

. (0 ÷ 23h 50 min.) 

dSE 

Energy Saving cycle length on holidays

 (0 ÷ 24h 00 min.) 

 

TO SET DEFROST TIMES 
Ld1÷Ld6 Workday defrost start

 (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles during workdays. Ex. When 

Ld2

 = 12.4 the second defrost starts 

at 12.40 during workdays.  

Sd1÷Sd6 Holiday defrost start

 (0 ÷ 23h 50 min.) These parameters set the beginning of the 6 

programmable defrost cycles on holidays. Ex. When 

Sd2

 = 3.4 the second defrost starts at 

3.40 on holidays.  
N.B. :

To disable a defrost cycle set it to “nu”(not used). 

Ex. 

 If

 Ld6

=nu

 ; 

 the sixth defrost 

cycle is disabled 

OTHER 
Adr   Serial  address

 (1÷244): Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntc 

NTC probe. 

onF  on/off key enabling: nu = 

disabled; 

oFF = 

enabled; 

ES = not set it

dP1  Thermostat probe display 

dP2  Evaporator probe display 
dP3  Third probe display

optional

dP4  Fourth probe display

rSE  Real set point:

 it shows the set point used during the energy saving cycle or during the 

continuous cycle. 

rEL Software release 

for internal use

Ptb  Parameter table code: 

readable only

8.

 

DIGITAL INPUT (ENABLED WITH P3P = N) 

The free voltage digital input is programmable in different configurations by the “

i1F

” parameter. 

8.1

 

DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 

= normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

did

”, the door alarm is 

enabled, the display shows the message “

dA

” and 

the regulation restarts is rtr = yES.

 The alarm 

stops as soon as the external digital input is disabled again. With the door open, the high and low 
temperature alarms are disabled. 

8.2

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the 

EAL

” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 

de-activated. 

8.3

 

SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

CA

” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

8.4

 

PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of 

activation of  the “

nPS

” parameter, the “

CA

” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is always 
OFF. 

If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

8.5

 

START DEFROST (i1F = dFr) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation 
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety 
time is expired. 

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES 
(parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows by means of the external 
TTL/RS485 converter, 

XJ485-CX

, to connect the instrument to a monitoring system 

ModBUS-RTU

 

compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the HOY KEY 
connector. The X-REP output 

EXCLUDES 

 the serial connection.

 

 

To connect the X-REP to the 
instrument the following connectors 
must be used CAB-51F(1m), CAB-
52F(2m), CAB-55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR70CX

 shall be mounted on vertical panel, in a 

29x71 mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0

÷

60 °C. 

Avoid places subject to strong vibrations, corrosive gases, 
excessive dirt or humidity. The same recommendations apply to 
probes. Let air circulate by the cooling holes. 
 

12.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 
mm

2

. Before connecting cables make sure the power supply complies with the instrument’s 

requirements. Separate the probe cables from the power supply cables, from the outputs and the 
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier 
loads use a suitable external relay. 

Summary of Contents for XR70CX

Page 1: ...controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON and OFF with the compressor and not run during defrost FnC o_n fans will run even if the compressor is off and...

Page 2: ...on 0 100 100 P1 0 P2 it allows to set the regulation according to the percentage of the first and second probe as for the following formula rtr P1 P2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays on without interruption for the CCt time Can be used for instance when the room is filled with new products CC...

Page 3: ...kdays ISE Energy Saving cycle start on holidays 0 23h 50 min dSE Energy Saving cycle length on holidays 0 24h 00 min TO SET DEFROST TIMES Ld1 Ld6 Workday defrost start 0 23h 50 min These parameters set the beginning of the 6 programmable defrost cycles during workdays Ex When Ld2 12 4 the second defrost starts at 12 40 during workdays Sd1 Sd6 Holiday defrost start 0 23h 50 min These parameters set...

Page 4: ...a 71x29mm panel cut out Protection IP20 Frontal protection XR70CX IP65 Connections Screw terminal block 2 5 mm2 wiring Power supply according to the model 12Vac dc 10 24Vac dc 10 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3VA max Display 3 digits red LED 14 2 mm high Inputs Up to 4 NTC or PTC probes Digital input free voltage contact Relay outputs compressor SPST 8 3 A 250Vac SPST 16 6 A...

Page 5: ... restart with door open alarm n Y y Pr2 HES Differential for Energy Saving 30 C 30 C 54 F 54 F 0 Pr2 Hur Current hour 0 23 rtc Min Current minute 0 59 rtc dAY Current day Sun SAt rtc Hd1 First weekly holiday Sun SAt nu nu rtc Hd2 Second weekly holiday Sun SAt nu nu rtc ILE Energy Saving cycle start during workdays 0 23h 50 min 0 rtc dLE Energy Saving cycle length during workdays 0 24h 00 min 0 rtc...