dIXEL

 

Installing and Operating Instructions 

1592020570

 

 

1592020570 XR70CX RTC GB r1.0 28.05.2008.doc 

XR70CX 

4/5 

12.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure the average room temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message 

appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

 key if you 

want to restart the upload again or remove the “

Hot key

” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the Controller ON. 

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller memory, 

the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then 

on if you want to restart the download again or remove the “

Hot key

” to abort the operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and “COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

"LA2" 

Condenser low temperature 

It depends on the “bLL” parameter 

“dA” 

Door open 

Compressor and fans restarts  

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious external alarm (i1F=bAL)  All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL)  All outputs OFF 

“rtc” 

Real time clock alarm 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. “IdF” Set real time clock 
has to be set 

rtF 

Real time clock board failure 

Alarm output ON; Other outputs unchanged; 
Defrosts according to par. “IdF” Contact the 
service 

14.1

 

ALARM RECOVERY  

Probe alarms 

P1

”, “

P2”,

 “

P3

” and “

P4

” start some seconds after the fault in the related probe; they 

automatically stop some seconds after the probe restarts normal operation. Check connections 
before replacing the probe. 
Temperature alarms “

HA

”, “

LA

” “

HA2

” and “

LA2

” automatically stop as soon as the temperature 

returns to normal values. 
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is disabled. 

Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

14.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

15.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: XR70CX 

frontal 32x74 mm; depth 60mm; 

Mounting: XR70CX 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: XR70CX 

IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%;  230Vac 

±

10%, 

50/60Hz, 110Vac 

±

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: Up to 4 NTC or PTC probes.

 

Digital input: 

 free voltage contact 

Relay outputs: compressor 

SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac

 

 

defrost: 

SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac 

 

fan: 

SPST 5A, 250Vac or SPST 16(6)A 250Vac 

 

aux: 

SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac 

Data storing

: on the non-volatile memory (EEPROM). 

Internal clock back-up:

 24 hours 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0÷60 °C;

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F);  

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 

16.

 

CONNECTIONS 

The X-REP

 

output

 

excludes

 the TTL output.. It’s present in the following codes:  

XR70CX- xx

2

xx, XR70CX –xx

3

xx; 

16.1

 

XR70CX – 8A OR 16A COMP. RELAY - 12VAC/DV OR 24 VAC/DV 

 

NOTE: 

The 

compressor relay is 
8(3)A or 16(6)A 
according to the 
model. 

24Vac/dc supply

connect to the 
terminals 5 and 6. 
 

16.2

 

XR70CX –4 X 16A - 12VAC/DC 

 

 

17.

 

DEFAULT SETTING VALUES  

Labe

Name Range 

°C/°F 

Level 

Set 

Set point 

LS÷US 

-5.0 

- - - 

rtc 

Real time clock menu 

Pr1 

Hy 

Differential 

0,1

÷

25.5°C/ 1

÷

 255°F 

2.0 Pr1 

LS 

Minimum set point 

-50°C

÷

SET/-58°F

÷

SET 

-50.0 Pr2 

US 

Maximum set point 

SET

÷

110°C/ SET 

÷

 230°F 

110 Pr2 

Ot 

Thermostat probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 Pr1 

P2P 

Evaporator probe presence 

n=not present; Y=pres. 

Pr1 

OE 

Evaporator probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 Pr2 

P3P 

Third probe presence 

n=not present; Y=pres. 

Pr2 

O3 

Third probe calibration 

-12

÷

12°C /-120

÷

120°F 

0 Pr2 

P4P 

Fourth probe presence 

n=not present; Y=pres. 

Pr2 

O4 

Fourth probe calibration 

-12

÷

12°C /-120

÷

120°F 

0 Pr2 

OdS 

Outputs delay at start up 

0÷255 min 

Pr2 

AC 

Anti-short cycle delay 

÷

 50 min 

1 Pr1 

rtr 

P1-P2 percentage for regulation 

 0 ÷ 100 (100=P1 , 0=P2) 

100 

Pr2 

CCt 

Continuos cycle duration 0.0÷24.0h 

0.0 

Pr2 

CCS 

Set point for continuous cycle 

 (-55.0÷150,0°C) (-67÷302°F) -5  Pr2 

COn 

Compressor ON time with faulty probe 

÷

 255 min 

15 Pr2 

COF 

Compressor OFF time with faulty probe  0 

÷

 255 min 

30 Pr2 

CF 

Temperature measurement unit 

°C 

÷

 °F 

°C  

Pr2 

rES 

Resolution 

in=integer; dE= dec.point

 

dE  

Pr1 

Lod 

Probe displayed 

P1;P2 

P1 Pr2 

rEd

X-REP display 

P1 - P2 - P3 - P4 - SEt - dtr 

P1 

Pr2 

dLy 

Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

Pr2 

dtr 

P1-P2 percentage for disply 

 1 ÷ 99 

50 

Pr2 

tdF 

Defrost type 

EL=el. heater;  in= hot gas 

EL Pr1 

dFP 

Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 

Pr2 

dtE 

Defrost termination temperature 

-50 

÷

 50 °C 

8 Pr1 

IdF 

Interval between defrost cycles 

÷

 120 ore 

6 Pr1 

MdF 

(Maximum) length for defrost 

÷

 255 min 

30 Pr1 

dSd 

Start defrost delay 

0÷99min 

0 Pr2 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it Pr2 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 

Pr2 

Fdt 

Draining time 

0÷120 min 

Pr2 

dPo

 

First defrost after startup 

n=after IdF; y=immed. 

Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 

Pr2 

Fnc 

Fan operating mode 

C-n, o-n, C-y, o-Y 

o-n 

Pr1 

Fnd 

Fan delay after defrost 

0÷255min 

10 

Pr1 

Fct 

Differential of temperature for forced 
activation of fans 

0÷50°C 

10 Pr2 

FSt 

Fan stop temperature 

-50÷50°C/-58÷122°F 2 

Pr1 

Fon 

Fan on time with compressor off 

0÷15 (min.) 

Pr2 

FoF 

Fan off time with compressor off 

0÷15 (min.) 

Pr2 

FAP 

Probe selection for fan management 

nP; P1; P2; P3; P4 

P2 

Pr2 

ALc 

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab Pr2 

Summary of Contents for XR70CX

Page 1: ...controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 3 CONTROL OF EVAPORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON and OFF with the compressor and not run during defrost FnC o_n fans will run even if the compressor is off and...

Page 2: ...on 0 100 100 P1 0 P2 it allows to set the regulation according to the percentage of the first and second probe as for the following formula rtr P1 P2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays on without interruption for the CCt time Can be used for instance when the room is filled with new products CC...

Page 3: ...kdays ISE Energy Saving cycle start on holidays 0 23h 50 min dSE Energy Saving cycle length on holidays 0 24h 00 min TO SET DEFROST TIMES Ld1 Ld6 Workday defrost start 0 23h 50 min These parameters set the beginning of the 6 programmable defrost cycles during workdays Ex When Ld2 12 4 the second defrost starts at 12 40 during workdays Sd1 Sd6 Holiday defrost start 0 23h 50 min These parameters set...

Page 4: ...a 71x29mm panel cut out Protection IP20 Frontal protection XR70CX IP65 Connections Screw terminal block 2 5 mm2 wiring Power supply according to the model 12Vac dc 10 24Vac dc 10 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3VA max Display 3 digits red LED 14 2 mm high Inputs Up to 4 NTC or PTC probes Digital input free voltage contact Relay outputs compressor SPST 8 3 A 250Vac SPST 16 6 A...

Page 5: ... restart with door open alarm n Y y Pr2 HES Differential for Energy Saving 30 C 30 C 54 F 54 F 0 Pr2 Hur Current hour 0 23 rtc Min Current minute 0 59 rtc dAY Current day Sun SAt rtc Hd1 First weekly holiday Sun SAt nu nu rtc Hd2 Second weekly holiday Sun SAt nu nu rtc ILE Energy Saving cycle start during workdays 0 23h 50 min 0 rtc dLE Energy Saving cycle length during workdays 0 24h 00 min 0 rtc...

Reviews: