ALARM SIGNALLING

Message Cause

Outputs

“P1”

Thermostat probe failure

Compressor and heating outputs off

“P3”

Humidity  probe failure

Humidity regulation off

“HA”

High temperature alarm

Outputs unchanged

“LA”

Low temperature alarm

Outputs unchanged

“HHA” High humidity alarm

Outputs unchanged

“HLA” Low humidity alarm

Outputs unchanged

“dA”

Door switch alarm

Outputs depending on the odC parameter

The alarm message is displayed until the alarm condition recoveries.
All the alarm messages are showed alternating with the room temperature except for the “P1”
which is flashing. To reset the “EE” alarm and restart the normal functioning press any key, the

rSt

” message is displayed for about 3s.

12.1

 

SILENCING BUZZER

Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.

12.2

 

ALARM RECOVERY

Probe alarms

 : “

P1

” (probe1 faulty), “

P3

” ; they automatically stop 10s after the probe restarts

normal operation. Check connections before replacing the probe.

Temperature alarms

 “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature

returns to normal values or when the defrost starts.

Humidity alarms

  “

HHA

” and “

LHA

” automatically stop as soon as the humidity returns to

normal values.

Door switch alarm

 “

dA

”  stop as soon as the door is closed.

13.

 

TECHNICAL DATA

VH620 keyboard
Housing: 

self extinguishing ABS; 

Case: 

facia 100x64 mm; depth 23mm

Mounting:

 panel mounting in a 56x72 mm panel cut-out with two screws. 

 3 x 2mm.

Distance between the holes 40mm

Protection: 

IP20.

Frontal protection:

 IP65 with frontal gasket mod RG-V. (optional)

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring

Power supply: 

from

 XH240K;  Display

: double d icons.

Optional output: 

buzzer

XH240K board
Housing: 

open board; 

Case: 

77x102mm

Mounting:

 panel with two screws. 

 3x2mm.

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston

Power supply: 

230Vac 

±

 10%; 

Power absorption: 

7VA max.

Inputs

: 1 NTC probe +  4÷20mA probe

Digital input

: 1 free voltage

Relay outputs:

compressor:

 relay SPST 20(8) A, 250Vac

heather: 

relay SPST 16(6) A, 250Vac

fans:

 relay SPST 8(3) A, 250Vac

humidifier:

 relay SPST 8(3) A, 250Vac

Data storing

: on the non-volatile memory (EEPROM).

Kind of action: 

1B.; 

Pollution grade: 

normal; 

Software class: 

A.

Operating temperature: 

0÷60 °C.; 

Storage temperature: 

-25÷60 °C.

Relative humidity:

 20

÷

85% (no condensing)

Measuring and regulation range:

NTC probe: 

-40÷110°C (-58÷230°F)

Resolution: 

0,1 °C or 1°C or 1 °F (selectable).

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit

14.

 

WIRING CONNECTIONS

in

16A

250Vac

Thermostat

Probe

Humidity

Probe

20A

250Vac

Supply

230Vac

Comp

Fan

Heather

8A

250Vac

Hum

8A

250Vac

+

gnd

12V

+

Digital

Input

15.

 

DEFAULT SETTING VALUES

Label Value Menu

Description

Range

Set T

5.0

- - - Temperature Set Point

LS ÷ uS ( nu = temperature

regulation disabled )

Set H

50.0

- - - Humidity Set Point

LSH ÷ uSH ( nu = humidity

regulation disabled)

dbt

2.0

Pr1

Half dead band width for temperature

0.1°C o 1°F ÷ 25°C o 77°F

dbH

5.0

Pr1

Half dead band width for humidity

0.5 ÷ 50

LS

-40.0

Pr2

Minimum temperature set point limit

-50.0°C o –58°F ÷ Set T

uS

110

Pr2

Maximum temperature set point limit

Set T ÷  110°C o 230°F

odS

1

Pr2

Outputs activation delay at start up

0 ÷ 250 min

Ac

1

Pr1

Anti-short cycle delay

0 ÷ 30 min

LSH

0.0

Pr2

Minimum humidity set point limit

Lci ÷ Set H

uSH

100

Pr2

Maximum humidity set point limit

Set H ÷ uci

cF

°C

Pr2

Measurement unit

°C ÷°F

rES

dE

Pr2

Resolution (for °C):

in = integer / dE = decimal

rEH

Hd

Pr2

Resolution for RH%:

in = integer / Hd = half digit

idF

8

Pr1

Interval between defrosts

1 ÷ 120 h

MdF

20

Pr1

Duration of defrost

0 ÷ 250 min

dFd

it

Pr2

Display during defrost

rt / it / SEt / dEF / dEG

dAd

30

Pr2

Defrost display time out

0 ÷ 250 min

Hud

no

Pr2

Humidity control during defrost

no; yES

Fnc

c-n

Pr2

Fan operating mode

c-n / c-Y / o-n / o-Y

ALc

Ab

Pr2

Temperature alarm configuration

rE = relative / Ab = absolute

ALL

-40.0

Pr1

Low temperature alarm setting

0°C ÷ 50.0°C / -50.0°C ÷ ALu

ALu

110

Pr1

High temperature alarm setting

0°C ÷ 50.0°C / ALL ÷ 110°C

ALH

1.0

Pr2

Temperature alarm recovery differential

0.1°C o 1°F ÷ 25°C o 77°F

ALd

15

Pr2

Temperature alarm delay

0 ÷ 250 min

dAo

1.3

Pr2

Delay of temperature alarm at start-up

0.0 ÷ 23.5 h

EdA

20

Pr2

Alarm delay at the end of defrost

0 ÷ 250 min

dot

20

Pr2

Delay of temp. alarm after closing the
door

0 ÷ 250 min

AHc

Ab

Pr2

Humidity alarm configuration

rE = relative / Ab = absolute

AHL

0.0

Pr1

Low humidity alarm setting

0 ÷ 50 / Lci ÷ AHu

AHu

100

Pr1

High humidity alarm setting

0 ÷ 50 / AHL ÷ uci

AHH

2.0

Pr2

Humidity alarm recovery differential

0.5 ÷ 25

AHd

15

Pr2

Humidity alarm delay

0 ÷ 250 min

dHo

1.3

Pr2

Delay of humidity alarm at start-up

0.0 ÷ 23.5 h

doH

20

Pr2

Alarm delay at the end of defrost

0 ÷ 250 min

doA

20

Pr2

Open door alarm delay

0 ÷ 250 min ( 250 = nu )

nPS

0

Pr2 Pressure switch number

0÷15

ot

0.0

Pr1 Thermostat probe calibration

-12.0 ÷ 12.0

o3

0.0

Pr1 Humidity probe calibration

-10 ÷ 10

P3P

yES

Pr2 Humidity probe presence

yES; no

Lci

0

Pr2 Readout with 4 mA

-999 ÷ 999

uci

100

Pr2 Readout with 20 mA

-999 ÷ 999

i1P

oP

Pr2 Digital input polarity

cL =open / oP = close

i1F

dor

Pr2 Digital input configuration

dor / PAL / EAL / bAL / Ht

odc

oFF

Pr2 Outputs status when open door

on / Fan / oFF

rrd

YES

Pr2 Outputs restarting after doA alarm

no = no / YES = yes

did

0

Pr2 Digital input alarm delay

0÷255 min.

Adt

1

Pr2

Serial address for temperature

0÷247

AdH

1

Pr2

Serial address for humidity

0÷247

Ptb

1

Pr2 Parameter table

- - -

rEL

1.0

Pr2 Software release

- - -

Pr2

321

Pr1 Access to the protected parameter list

- - -